Linear H-S Installation And Owner'S Manual Download Page 10

4)  Depress the limit nut retaining Plate (D) so it disengages 
from the slots in the limit nuts.  Turn the OPEN limit nut (E) on 
the shaft until it engages the Open Limit Switch (A). You will 
need to listen for an audible click.  Release the retaining plate 
and be sure that it engages in slots of both limit nuts. 

5)  Manually lower the door to approx. 4 inches shy of the 
fully closed position and repeat Step #4 with the Close Limit nut 
(C) and the Close Limit switch (B). 

6)  Manually move the door to a half open position.  With the 
door in a mid position there will be time to stop the door if 
something or someone were in the door path when initially 
starting the door. 

7)  An additional limit adjustment may be necessary after the 
connection of the power supply in order to ensure the door stops 
at the proper Open and Close positions. 

8)    If needed, a fine adjustment of the Close Limit switch (B) 
or Open Limit switch (A) is possible by loosening the screws  
slightly that hold the switch to the V bracket and moving the 
switch within its mounting slots.  Ensure to retighten the switch 
mounting screw.  Moving the Reverse Cutout switch closer to 
the center of the box will increase the point where the reversing 
feature cuts out (to allow for irregularity in the floor, etc.).  The 
reverse cutout point is factory adjusted to approx. 4 inches off 
the floor.

 

TO AVOID RISK OF ENTRAPMENT AND 

POSSIBLE DAMAGE TO THE DOOR AND 

OPERATOR THE LIMITS MUST BE ADJUSTED 

BEFORE APPLYING POWER TO THE 

OPERATOR. 

WARNING

 

A -  OPEN LIMIT SWITCH 
B -  CLOSE LIMIT SWITCH 
C -  CLOSE LIMIT NUT 
D -  LIMIT NUT RETAINING PLATE 
E -   OPEN LIMIT NUT 
F -   “V” BRACKET 

 

113116 

Figure 8 

Limit Assembly 

SETTING THE LIMIT SWITCHES

 

 

1)  With the cover open on the electrical enclosure, reference 
Figure 8 below.  There are two (2) switches (A and B) mounted to 

the „V‟ bracket (F).  The Close Limit switch (B) and the Open 
Limit switch (A) are mounted to the top side of the „V‟ bracket as 

shown.  These switches are activated by the two limit nuts (E & C) 
on the threaded shaft which move laterally along the shaft as the 
operator opens and closes the door.  When a limit nut nears the 
end of the shaft it activates a switch. 

2)  Depress the Limit Nut Retention Plate (D) so it disengages 
from the slots in the limit nuts and move the Limit nuts to the 
center of the threaded shaft.  Re-engage the Limit Nut Retention 
Plate (D). 

3)  Manually  raise the door to a fully open position. 

10 

INSTALLATION INSTRUCTIONS 

Summary of Contents for H-S

Page 1: ...operators J S H S J H SERIES WITH SOLID STATE CONTROL CIRCUITRY JACKSHAFT COMMERCIAL VEHICULAR DOOR OPERATORS READ THIS MANUAL CAREFULLY BEFORE INSTALLATION OR USE SAVE THESE INSTRUCTIONS Serial Date...

Page 2: ...on 5 Table 1 Component Identification Listing 5 Installation Instructions 6 13 Figure 2 Operator Footprint J S H S 6 Figure 5 Release Hand Chain Wall Bracket Installation 7 Figure 6 Mounting Positions...

Page 3: ...hoto beam are provided Constant Contact To Close Standard operating mode The operator can be converted to Momentary Contact To Close when the photo beam as described above or one of the Miller Edge fa...

Page 4: ...ing carton inspect the nameplate on the cover of the operator control box to verify that it is the correct model for the intended application and that the voltage and phase are in accordance with elec...

Page 5: ...pedestrian door is available for entrance and exit to the building In addition YOU MUST install an auxiliary entrapment protection device reversing door edge or photoelectric beam device Connect an au...

Page 6: ...inch diameter bolts through the wall If it is not feasible to go through the wall then use lag bolts to fasten the operator to the mounting surface Locate the four holes within the tracings of the slo...

Page 7: ...chain is too long standard length for 16 foot high doors and below is 26 feet total length of chain shorten it to the desired length using the method described above and discard the unused portion Fa...

Page 8: ...Figure 6 100719 Right Side Mount Ceiling Mount Left Side Mount Ceiling Mount Center Mount Direct Couple Wall Mount Wall Mount 8 FIGURE 4 OPERATOR MOUNTING POSITIONS...

Page 9: ...107841 Figure 7 Dimensions Model H S Figure 7A Dimensions Model J S 108203 9 FIGURE 5 OPERATOR DIMENSIONS MODEL J S H S...

Page 10: ...ut switch closer to the center of the box will increase the point where the reversing feature cuts out to allow for irregularity in the floor etc The reverse cutout point is factory adjusted to approx...

Page 11: ...vices exactly as shown Warning Control voltage of the opener is 5 volts DC Class 2 Do not run the power leads and control circuit wiring in the same electrical conduit Note J S and H S Series model op...

Page 12: ...USE AN INTERLOCK SWITCH IF A LOCK IS REQUIRED TO RETAIN FUNCTIONALTY CAUTION Figure 8 Door Edge Device Note See the door edge manufacturer s installation instructions for the complete installation pr...

Page 13: ...n of this device will not enable the Momentary Contact to Open Mode Any Miller Edge ME MT MU and CPT family of edges must be connected to the SM 102 Edge Module Recognized by UL as per UL325 2010 on 0...

Page 14: ...y is clear Figure 11 PCB 112695 REV B TSLK OPEN C25 PB1 PB2 PB3 U5 STOP CLOSE OPEN C1 R84 R2 R3 D12 COM CLOSE STOP NO REV NC REV PHOTO MOTOR CONTROL BOARD Single 3 Button Station MOTOR CONTROL BOARD C...

Page 15: ...over adjust the force setting to compensate for a poorly working door To prevent the motor protector from tripping Do not exceed 10 door cycles per hour IMPORTANT The hardware box contains a caution l...

Page 16: ...open button will bypass mid stop Auto Close Timer N A D1 Operation Open Button Constant activation open override of closing door Close Button Constant activation door will stop when button is release...

Page 17: ...limit if the auto close timer has not been previously deactivated SETUP MODES Setup Modes Various operating characteristics can be modified via the setup modes The operator is moved to the close limi...

Page 18: ...lose Timer Setup This feature allows for a modification of the amount of time between the door reaching either the Mid Stop or the Full Open position and automatically starting in the close direction...

Page 19: ...RDWARE BINDING IN THE TRACK RUBBING AGAINST THE DOOR STOPS OR DEFECTIVE OR MISADJUSTED SPRINGS ANY SERVICE REQUIRED TO THE DOOR DOOR SPRINGS OR DOOR OPERATOR MUST BE PREFORMED BY A QUALIFIED PROFESSIO...

Page 20: ...OPERATION ADJUSTMENT INSTRUCTIONS 20...

Page 21: ...ON DO NOT STAND UNDER DOOR TO TEST REVERSING FEATURE USE A CORRUGATED BOX OR OTHER SIMILAR OBJECT If the operator is equipped with other means of control such as additional 3 button stations or radio...

Page 22: ...OR DIRECTION SWITCH INCOMING LEADS TO TERMINALS 5 AND 8 DUAL VOLTAGE MOTOR 230V 1P RED AU BLUE T J H WHITE 4 8 BALDOR YELLOW 5 1 2 3 BRAKE BL BLK BL BLK CDOMCB 2005 EDGE RADIO c p ALLSTAR CORP P4 24V...

Page 23: ...1P RED AU BLUE T J H WHITE 4 8 BALDOR YELLOW 5 1 2 3 BRAKE BL BLK BL BLK CDOMCB 2005 EDGE RADIO c p ALLSTAR CORP P4 24V S1 R58 R56 R55 R54 R45 R46 K4 K3 K5 K6 COM OLS CLS COM HIGH VOLTAGE OPEN MO4 MO...

Page 24: ...24 NOTES...

Page 25: ...r 1 2 HP 56 ODP 230 460 VAC 3 PH 005038 Motor 3 4 HP 56 ODP 230 460 VAC 3 PH Ref Part Description Parts 1 009221 Shaft Collar 1 2 008071 Flange Bearing 3 4 3 100487 Flange Bearing 1 4 105549 Snap Ring...

Page 26: ...CONTROL BOX SOLID STEEL DRIVE SHAFTS INTEGRAL MANUAL CHAIN HOIST WITH FLOOR LEVEL FULLY ADJUSTABLE INTERNAL SHAFT DRIVEN LIMITS ENGAGEMENT AND DISCONNECT ADVANCED OPERATIONAL FEATURES STANDARD P N230...

Reviews: