Cable Requirements

Belden 9535 or equivalent. Multi-conductor stranded with foil shield, minimum 24AWG.  Maximum length 400ft (152m).

Output Formats

26 to 37-bit Wiegand formats.

Grounding

Shield must run continuously from the reader to the panel.  At the panel, the reader ground, shield line, and earth ground must be 
connected together at a single point. 

Notes:

 

•  Do not ground the shield line at the reader end, as this will create a potential ground loop.
•  Ensure the shield foil and wire are taped and not exposed.

Power

A non-switching power supply at the panel is recommended to power the reader for the highest noise immunity and best performance.  
We recommend using Linear’s stand-alone power supplies for optimum performance. 

Voltage

•  Current Draw: 100 - 200 mA typical, 225 mA max peak @ 12 VDC in low-power mode.
•  At the Reader: +5.5 - 16 VDC. 12.0 VDC is recommended. A regulated power supply and 12 VDC at the reader is recommended 

for best operation.

Note:

 The reader is in Low Power Mode by default. High-Power Mode can be confi gured via the Phone App.

Connection

Connections must be in accordance with NFPA 70.

WARNING: DO NOT connect this reader’s power supply to a receptacle controlled by a switch.

Reader Wiring

Wiegand

Conductor

Purpose

Red

DC +6 VDC - 16 VDC

Black

Ground

Green

Data 0

White

Data 1

Purple

Red LED

Orange

Buzzer

Yellow

Card Present

Blue

Green LED

Drain

Shield Ground

Voltage:  +5.5 VDC – 16.0 VDC (12 VDC Nominal) at the reader
Curent Draw:  100 - 200 mA (typical @ 12 VDC), 225 mA max
peak @ 12 VDC low-power mode.

Summary of Contents for BluePass 2N1-BTPRX

Page 1: ...P N 10019179 X15 BluePass 2 N 1 BluePass Multi Tech Reader Manual Installation Instructions...

Page 2: ...nd protocol End users can present any combination of 125 KHz prox cards and Fobs or Bluetooth Low Energy Credentials via a supported smart device such as Android and Apple mobile devices to request ac...

Page 3: ...mend using Linear s stand alone power supplies for optimum performance Voltage Current Draw 100 200 mA typical 225 mA max peak 12 VDC in low power mode At the Reader 5 5 16 VDC 12 0 VDC is recommended...

Page 4: ...rian gate must be isolated from the unit Note Placing a unit directly on a moving door or gate will damage the reader s sensitive functionality Choose a well lit location near the controlled opening W...

Page 5: ...BluePass Reader Note Ensure power supply is not energized until all wires are properly connected and terminated 10 Feed excess cable into wall 11 Mount BluePass Reader into upper and lower mounting s...

Page 6: ...LVER BLK WHT BLU BLU BluePass Reader Wiring Diagram 6 Place mounting bracket on wall aligning screw mounting positions with wall anchors 7 Screw in two 2 screws 8 Connect Reader wires to corresponding...

Page 7: ...the reader to enter a door The allowed distance between reader and mobile device is configurable by the facility manager on a per reader basis The range can be restricted such that a user must present...

Page 8: ...the system in a multi tenant residential condominium complex The property management company wants to re use mobile credentials from departing tenants reissuing them to the new tenants moving in Is t...

Reviews: