Installation remote from construction support
EI 120 S
(300 Pa)
EI 90 S
(500 Pa)
EI 60 S
(500 Pa)
EI 30 S
(500 Pa)
Rigid w
all
EI 120 S Installation remote from the vertical rigid wall
Wall minimum thickness 100 mm
Wall minimum density 550 kg/m³
Mortar or plaster putty sealing
ve (i
↔
o)
W
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
EI 120 S Installation remote from the vertical rigid wall with Fire Batt (Weichschott) sealing
Wall minimum thickness 100 mm
Wall minimum density 550 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ve (i
↔
o)
D
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Fle
xible w
all
EI 120 S Installation remote from the vertical light wall (plasterboard)
Wall minimum thickness 100 mm
Wall rock wool density up to 100 kg/m³ (optional)
Plasterboard and rock wool 100 kg/m³ or mortar or plaster putty
sealing
ve (i
↔
o)
D/W
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
EI 120 S Installation remote from the vertical light wall (plasterboard) with Fire Batt (Weichschott) sealing
Wall minimum thickness 100 mm
Wall rock wool density up to 100 kg/m³ (optional)
Rock wool density 140 kg/m³ and endothermic varnish sealing
ve (i
↔
o)
D
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
EI 120 S Installation remote from the vertical light wall (gypsum blocks wall)
Wall minimum thickness 100 mm
Wall minimum density 995 kg/m³
Mortar or plaster putty sealing
ve (i
↔
o)
W
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
EI 120 S Installation remote from the vertical light wall (gypsum blocks wall) with Fire Batt (Weichschott) sealing
Wall minimum thickness 100 mm
Wall minimum density 995 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ve (i
↔
o)
D
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Floor
EI 120 S Installation remote from the floor
Floor minimum thickness 150 mm
Floor minimum density 650 kg/m³
Mortar or plaster putty sealing
ho (i
↔
o)
W
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
EI 90 S Installation remote from the floor
Floor minimum thickness 100 mm
Floor minimum density 650 kg/m³
Mortar or plaster putty sealing
ho (i
↔
o)
W
-
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Installations within vertical light wall (Shaft wall)
EI 90 S
(300 Pa)
EI 60 S
(300 Pa)
EI 30 S
(300 Pa)
Fle
xible w
all
EI 90 S Installation within vertical light wall (Shaft wall)
Wall minimum thickness 90 mm
Plasterboard and mortar or plaster putty sealing
ve (i
↔
o)
W
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
ELEC TRICAL CONNEC TIONS
Electrical wiring
Electrical connections must be done by qualified and trained people.
Switch off the power supply before starting any work on the electric
elements. Never switch on the power supply during electrical con-
nections.