3
Supporting Construction
Classification
Horizontal duct system
EI120 (v
ed
- i
↔
o)S 1000 C
mod
HOT 400/30 AA Multi
EI120 (v
ed
- i
↔
o)S 1000 C
mod
HOT 400/30 MA Multi
Vertical duct system
EI 120 (h
od
- i
↔
o)S 1000 C
mod
HOT 400/30 AA Multi
EI 120 (h
od
- i
↔
o)S 1000 C
mod
HOT 400/30 MA Multi
Wall construction
EI120 (v
ew
- i
↔
o)S 1000 C
mod
HOT 400/30 AA Multi
EI90 (v
ew
- i
↔
o)S 1500 C
mod
HOT 400/30 AA Multi
EI90 (v
ew
- i
↔
o)S 1500 C
mod
HOT 400/30 MA Multi*
Ceiling construction
EI 120 (h
ow
- i
↔
o) S1500C
mod
HOT 400/30 MA Multi
EI 120 (h
ow
- i
↔
o) S1500C
mod
HOT 400/30 AA Multi
EI 90 (h
ow
- i
↔
o) S1000C
mod
HOT 400/30
AA
Multi*
lindab | we simplify construction
Smoke Control Damper
SDR
2
-M
Lindab reserves the right to make changes without prior notice
Last modified: 2021-10-26
Rev: 2021-03-26
* In practice dampers are not in the open position at the beginning of smoke threat.
• Cycling test in class C
mod
acc. to EN12101-8
• Certificate of constancy of performance No. 1391-CPR-
2021/0008
• Declaration of Perfomance SDR2-M DoP
• Hygienic assessment of fire dampers - Report No.1.6
pos/19/19c
1.3. Working conditions
Exact damper function is provided under the following
conditions:
a)
maximum air velocity 15m/s
b)
underpressure max. -1500Pa or overpressure
max. 500Pa.
Dampers can be installed in arbitrary position (horizontal
or vertical blade axis).
Dampers are designed for macroclimatic areas with mild
climate according to EN60 721-3-3. Temperature in the
place of installation is permitted to range from -30°C to
+50°C.
1.4.
The duck can be ended by grilles. During grilles instal-
lation blade overlaps has to be respected see chapter 3.
Tab. 1.2.1. Classification of Dampers
1. Description
Smoke control dampers - multi are shutters in the smoke
exhaust piping systems. The dampers are designed to
remove heat and combustible products (e.g. smoke) from
effected fire compartments. In the event of fire the Smoke
and Fire ventilation system opens the damper in the
affected section and removes combustion products and
heat from this section.
The damper blade is controlled by electrical actuating
mechanism.
Dampers are fire resistant and are intended for sys-
tems with manual or automatic activation. Dampers are
designed for using in fire compartments that can be con-
nected to the smoke exhaust ducts (tested according to
EN1366-8) or they can be installed in or on the construc-
tion of the fire compartment.
Dampers can be delivered with or without flanges.
1.2. Damper characteristics
• CE certified acc. to EN12101-8
• Tested in accordance with EN1366-10
• Classified acc. to EN13501-4+A1
• Fire resistance according Tab. 1.2.1
• External Casing leakage class C, Internal leakage min.
class 2 acc. to EN1751
General information