B-8
OPERATION
B-8
BIG RED™ 600
AUXILIARY POWER:
The auxiliary power is independent of the welding
power and thus not effected by the weld control
settings.
Simultaneous Welding and Auxiliary Power Loads
The auxiliary power ratings are with no welding
load. Simultaneous welding and power loads are
specified in the following Table B.4.
Weld
Amps
0
100
200
300
400
500
600
1 PHASE (120V)
WATTS AMPS
2400 20
2400 20
2400 20
2400 20
1200 10
0 0
0 0
1 PHASE (240V)
WATTS AMPS
3600 15
3600 15
3600 15
2400 10
1200 5
0 0
0 0
BIG RED™ 600 Simultaneous Welding and Power Loads
PLUS
OR
TABLE B.4
BIG RED™ 600 Extension Cord Length Recommendations
(Use the shortest length extension cord possible sized per the following table.)
Current
(Amps)
15
20
15
Voltage
Volts
120
120
240
Load
(Watts)
1800
2400
3600
30
60
(9)
(18)
40
30
75
(12)
(9)
(23)
75
50
150
(23)
(15)
(46)
125
88
225
(38)
(27)
(69)
175
138
350
(53)
(42)
(107)
300
225
600
(91)
(69)
(183)
Maximum Allowable Cord Length in ft. (m) for Conductor Size
Conductor size is based on maximum 2.0% voltage drop.
14 AWG
12 AWG
10 AWG
8 AWG
6 AWG
4 AWG
TABLE B.5