
LINCOLN ELECTRIC
SAE-300® HE Service Manual
14
Observe Safety Guidelines
detailed in the beginning of this manual.
TROUBLESHOOTING GUIDE
PROBLEMS
(SYMPTOMS)
POSSIBLE AREAS OF
MISADJUSTMENT(S)
RECOMMENDED
COURSE OF ACTION
OUTPUT PROBLEMS
There is no or very low weld
output. Auxiliary output is
normal.
1. Check that the remote/local
switch is positioned correctly.
2. If a remote current control is
being used, try switching to
local control. The remote
current control may be faulty.
3. Check all leads and cables
for damaged or poor
connections.
1. Perform the
Circuit Voltage Test Procedure
4. Check for damaged or poor
connections at the brush
holders, series and interpole
coils, coarse current control
unit, weld output terminals and
all the conductors connecting
these components.
6. The armature may be faulty.
There is no auxiliary voltage at
receptacles but weld output is
normal.
1. Check that the auxiliary
power circuit breakers are not
tripped.
2. If the machine is equipped
with a ground fault circuit
interrupter (GFCI), it may be
tripped or defective.
NOTE:
GFCIs will not reliably
reset, unless engine is
operating at high idle RPM.
3. Check all leads and cables
for damaged or poor
connections.
1. Check for auxiliary voltage at
the receptacle input terminals;
if normal voltage is present,
replace terminals.
2. Check for auxiliary voltage at
the connections closest to the
exciter stator windings. See
Wiring Diagram.
• If normal voltage is present,
check the wiring and circuit
breakers between the test
points and the receptacle.
Repair or replace any defective
parts or wiring.
If for any reason you do not understand the test procedures or are unable to perform the test/repairs safely, contact the
Lincoln Electric Service Department for electrical troubleshooting assistance before you proceed. Call 1-888-935-3877.
Summary of Contents for SAE-300 HE
Page 8: ...LINCOLN ELECTRIC SAE 300 HE Service Manual 3 Theory of Operation Figure F 1 Block Diagram ...
Page 51: ...LINCOLN ELECTRIC SAE 300 HE Service Manual 46 Figure F 13 Rocker w marks ...
Page 64: ...LINCOLN ELECTRIC SAE 300 HE Service Manual 59 Figure F 22 Rheostat terminal locations ...
Page 68: ...LINCOLN ELECTRIC SAE 300 HE Service Manual 63 Figure F 25 Rotor removal ...
Page 75: ...LINCOLN ELECTRIC SAE 300 HE Service Manual 70 Figure F 28 Sling lift ...
Page 79: ...LINCOLN ELECTRIC SAE 300 HE Service Manual 74 Figure F 30 Current sense board plug location ...
Page 83: ...LINCOLN ELECTRIC SAE 300 HE Service Manual 78 Figure F 32 Rheostat terminal locations ...