Page 28 of 44
Screen nr. 3: ”Manual run”
This tab is used to set the basic movement parameters of the actuator.
• “Run Out”/”Run In” will start the actuator in the selected direction and it will run until it is either
stopped or until it reaches an end-stop.
• “Step Out”/”Step In” is used to adjust the position in small steps in either outgoing or ingoing
direction.
• “Initialise In”/”Initialise Out” is used to repeat the initialisation as done in factory.
• “Current limit In/Out” and maximum “Speed” for the manual run can be controlled by moving
the sliders. This speed setting is not persistent – after the manual run the setting is reset to
previous value (except if you disconnect the data cable during the run).
• “Set Limit in”/”Set Limit out” is used to define the operational position-limits after having
positioned the actuator to the position where you want these limits.
Please be aware to use ONLY one virtual endstop (‘Limit in’ or ‘Limit out’) at a time,
in order to ensure that one end is always open for initialisation of the actuator.
Initialise In/Out and Run Out/In will not respect the Limit in/out setting.
Be aware of potential mechanical destruction.
Actuator current is monitored in the upper-right part of the screen. Here you can see the actual and maximum
measured current in both outgoing and ingoing direction - together with actual cut-off values.
The actuator figure in the lower part of the screen visually shows the actual position of the actuator (dashed
line) together with the actual setting of Limit In (corresponding to off-set) and Limit Out (corresponding to Max.
stroke length).