background image

     www.limotec.be 

HG2400E02C 

 

 

2

 

DESCRIPTION 

The MD2400 repeater panel is integrated into a synthetic housing. The dimensions are 253x327x54mm 
(H x B x W). 

The MD2400 repeater panel duplicates the information reported on the MD2400 operator console and 
thus offers the possibility to provide this information at different locations in the building. 

The  operating  front  of  the  MD2400  repeater  panel  is  equipped  as  standard  with  an  LCD  (4x40 
characters), a number of general visual indications (LED for fire alarm and failure), a number of control 
buttons (Silence, Test LED, Reset, Evacuation Delayed and scroll buttons), a key switch for setting the 
2 control levels and with a key switch for evacuation. 

Communication between the MD2400 fire detection control panel and the MD2400 repeater panel is 
serially by means of an RS485 signal. 

Up to eight (8) MD2400 repeater panels can be connected to an MD2400 fire detection control panel. 

 

 

 

 

 

 

General LED indications 

Scroll buttons 

Key switch 

OPERATION 

Key switch 

EVACUATION 

Control buttons 

LCD 

Summary of Contents for MD2400

Page 1: ...www limotec be HG2400E02C 1 USER MANUAL MD2400 repeater panel 01 07 2018 LIMOTEC bvba Bosstraat 21 B 8570 Vichte Tel 32 0 56 650 660 www limotec be ...

Page 2: ...ANNOUNCEMENTS IN CASE OF A FAILURE 4 3 1 3 ANNOUNCEMENTS IN CASE OF A FIRE ALARM 4 3 2 CONTROLS ON THE REPEATER PANEL 5 3 2 1 KEY SWITCH OPERATION 5 3 2 2 GREEN CONTROL BUTTON SILENCE 5 3 2 3 GREEN CONTROL BUTTON TEST LED 5 3 2 4 ORANGE CONTROL BUTTON RESET 5 3 2 5 ORANGE CONTROL BUTTON EVAC DELAYED 5 3 2 6 KEY SWITCH EVACUATION 6 3 2 7 SCROLL BUTTONS AND 6 4 DISPLAY INFORMATION 7 ...

Page 3: ...tandard with an LCD 4x40 characters a number of general visual indications LED for fire alarm and failure a number of control buttons Silence Test LED Reset Evacuation Delayed and scroll buttons a key switch for setting the 2 control levels and with a key switch for evacuation Communication between the MD2400 fire detection control panel and the MD2400 repeater panel is serially by means of an RS4...

Page 4: ...the help of the scroll buttons and the information relating to the fault messages can still be displayed on the LCD General failures such as a siren error a power failure a loop error and a printer error are reported in the same way 3 1 3 ANNOUNCEMENTS IN CASE OF A FIRE ALARM The built in buzzer is activated The red LED ALARM lights up The name of the group to which the detector belongs together w...

Page 5: ...he built in warning buzzer of the respective MD2400 repeater panel stops The warning buzzers of the other MD2400 operator consoles and repeater panels continue to be activated The relay contacts connected to the silent function do not switch back to the resting position Only the yellow LED Silence of the respective MD2400 repeater panel lights up This LED is switched off in case of a new message o...

Page 6: ...em will immediately switch to evacuation the red LED Evacuation on the MD2400 operator consoles and repeater panels and the programmed outputs during evacuation will be activated immediately 3 2 7 SCROLL BUTTONS AND These control buttons are available at any time If several messages are present on the MD2400 fire detection control panel these buttons allow you to request the intermediate messages ...

Page 7: ... line shows In operation No messages The scroll key can be used to request the software version number the address of the repeater panel software version x xx address x and the setting of the Silence function general or local The LCD is divided into a number of fields As soon as a message is present on the MD2400 fire detection control panel the LCD takes the form described below Line 1 Line 2 Lin...

Page 8: ...help of the scroll keys all intermediate information can be displayed on the 2 upper text lines The alarm information always has priority over the fault information That is why all alarms are shown first followed by the pre alarms with a new sequence of numbers box d and then the faults again with a separate numbering for the order The LCD is equipped with a backlight which lights up automatically...