XAC77 Profibus-DP
®
4.3 Connecting the cables
Figure 1 - Connection cap
The connection cap is fitted with three PG9 cable glands for bus-IN and bus-
OUT connections and power supply connection. The bus cables can be connected
directly to the terminal connectors located in front of each cable gland.
We recommend Profibus-DP certificated cables to be used. Core diameter
should not exceed Ø 1,5 mm (0.06 inches).
Terminal connector
Description
-
0 VDC Supply voltage
+
+10VDC +30VDC Supply voltage
L
Profibus B (Red)
H
Profibus A (Green)
PG
Shield
1
1
Connect the cable shield to cable gland
MAN XAC77 PX I_E 1.0.odt
32
Electrical connections