NOTE
Always save the new values after setting in order to store them in the non-
volatile memory permanently. Use the
Should the power supply be turned off all data that has not been saved
previously will be lost!
WARNING
For safety reasons the following holding register parameters
not stored in the memory. So they are required to be set after each power-on.
Distance per revolution [0x00]
[Register 1, Unsigned16, rw]
This parameter sets the number of pulses per each complete revolution of the
shaft. It is useful to relate the revolution of the shaft and a linear measurement.
For example: the unit is joined to a warm screw having 5 mm pitch; by setting
Distance per revolution [0x00]
= 500, at each shaft revolution the system
performs a 5 mm pitch with one-hundredth of a millimetre resolution.
Default = 4096 (min. = 1, max. = 4096)
WARNING
After having changed this parameter you must then set new values also next to
the
parameter. For a detailed explanation see on page 45
and relevant parameters.
Please note that the parameters listed hereafter are closely related to the
Distance per revolution [0x00]
parameter; hence when you change the value
Distance per revolution [0x00]
also the value in each of them necessarily
NOTE
Distance per revolution [0x00]
is not a power of 2 (2, …, 512, 1024), at
position control a positioning error could occur having a value equal to one
pulse.
MAN RD6 MB E 1.1
Programming parameters
64 of 92
RD6 Modbus®