Byte 1
Not used.
WARNING
Extra commands register [0x29]
parameter is not stored in the memory. So it is required to be set after each
power-on.
Control Word [0x2A]
[Register 43, Unsigned16, rw]
This variable contains the commands to be sent in real time to the Slave in order
to manage it.
Byte structure of the
register:
byte
MSB
LSB
bit
15
…
8
7
…
0
msb
lsb
msb
lsb
Byte 0
Jog +
bit 0
Slave moves toward the positive direction; otherwise if the
bit 4
= 1, the activation of this bit causes a
single step toward the positive direction having the length,
expressed in pulses, set next to the
item to be executed at rising edge; then the actuator stops
and waits for another command. Velocity, acceleration and
deceleration are performed according to the values set next
to the
parameters respectively. For a detailed
description of the jog control see on page 42.
simultaneously. For instance: if a
the Slave while it is moving to the target position, the jog
command will be ignored; if
and
commands are
sent simultaneously, the device will not move or, if already
moving, it will stop its movement.
Jog -
bit 1
Slave moves toward the negative direction; otherwise if the
bit 4
= 1, the activation of this bit causes a
MAN RD6 MB E 1.1
Programming parameters
70 of 92
RD6 Modbus®