6 - DIL switch settings
The unit is fitted with two 8-position DIL switches; one (DIL1) is located on the
top side while the other (DIL2) is located on the bottom side of the unit. These
switches provide customer-specific settings of desired operating modes in a
very quick way.
NOTE
Changes in the switch settings will become effective only after the next power-
up cycle!
Positions 7 and 8 of switch DIL2
are intended for internal factory use only
and must be set both to OFF at any time during normal operation.
6.1 Basic mode of operation and power-down memory setting
Positions 2 and 3 of switch DIL1
on the upper side set the mode of operation;
while
position 4
allows to set the power-down behavior of the unit.
Position 4 OFF: Power-down memory OFF. Upon power up the counter either
resets to zero or sets to the value programmed next to the items
and
).
Position 4 ON: Power-down memory ON. Upon power up the counter re-loads
the value stored previously before power down.
MAN IF50 I_E 1.0.odt
6 - DIL switch settings