Document 36 II Guardian Version 1.02 © Copyright 2008 LPI
9
LPI GUARDIAN CAT TERMINAL
THREADED GI ADAPTOR (FEMALE
THREAD 2 INCH BSP)
LPI SADDLES FOR
CANTILEVERING MAST
MAST ASSEMBLY WITH GI ADAPTOR
SUITABLE MOUNTING SADDLES
IMPORTANT:
One third of the mast height must be
securely fixed to the structure.
Guardian CAT terminal to be a minimum
of 2 metres above the highest point of
the building.
Recommended clearance height = 5
metres.
BASE OF MAST PIPE
EXISTING
STRUCTURE
MOUNTING BOLTS &
STAINLESS STEEL WASHERS
COMPRESSION LUG
COPPER CABLE
ORDERING CODE: CAT IGI-G
CAT IIGI-G
CAT IIIGI-G
ORDERING CODE: CATGI-ADPT
ORDERING CODE: ALUM3M-MGI
ALUM4M-MGI
ALUM5M-MGI
ALUM6M-MGI
ORDERING CODE: CANTSAD (3 PER SET)
Lightning Protection International Pty Ltd
Drawn
Date
Scale
Title
File
Version
CTA-05
Guardian CAT terminal assembly
component details
CAT Installation Type 5.dwg
NTS
28/7/2008
John Davey
V1.01
Figure 6.
Guardian Install Manual V12.indd 11