14
Document 36 II Stormaster Version 1.02 © Copyright 2008 LPI
4. Upper termination the HVSC downconductor and connection to the Stormaster ESE
terminal.
5. Preparation and raising of the mast into position.
LPI Stormaster ESE should only be installed during storm-free periods.
If the Stormaster ESE terminal needs to be raised prior to connection to the lightning earth
or immediate connection is not possible then connect the lower end of the downconductor to
structural steel reinforcing or other suitable earth point.
Installation of the Lightning Earth
Before installation of the lightning protection earth, consult site drawings of underground
services so that these are not damaged during installation of the earthing system.
Figure 9.