16
(24)
LIFTINGITALIA S.r.l.
Via Cadu� del Lavoro, 16 - 43058 Bogolese, Sorbolo (PR) - Italy
Phone +39 0521.695311 - Fax +39 0521.695313
www.li� ingitalia.com - info@li� ingitalia.com
XQ16
XQ7
XQ4
XQ1
XQ8
XQ9
XQ10
XQ11
XQ12
XQ13
XQ14
XQ15
XQ17
XQ18
XQ19
RS485
B
IP0
BUZZER
ON
XQ2
XQ5
XQ6
XQ3
24
1
1
1
4
1
1
1
1
1
4
1
1
1
1
8
1
6
10
1
1
12
1
3 2 1
2 1
4 3 2 1
KCH0
KAP0
KA-ELT
KA-BR2
KA-BR1
KA-SIC1
KA-SIC2
24Vdc
RESET
TM
RS
232-485
F0 5x20
F1 5x20
I23
I22
O10
O9
O8
O7
O6
I24
I21
I20
O5
O4
O17
O16
O13
I25
I10
I6
I5
I4
I3
I2
I1
I8
I7
I9
O2
O1
I14I13I12 I11
I16I15
I18 I17
8.
DIAGNOSTICA INGRESSI / USCITE
IM.TEC.077.IT_rev.2
- May 2019
EN
To check the status of the logic signals on the card, refer to the LEDs located in the respective terminals.
Each led is identified by a name to make reading easier:
•
I = INPUT;
•
O = OUTPUT;
are accompanied by a plate that has a short acronym to help identify the function.
CONTROL PROCEDURE ON FIRST START-UP
•
Bring the car to the bottom floor;
•
Close all doors and all safety devices, so that the system is ready to be called (system on Standby);
•
Move the MAINTENANCE / NORMAL MODE switch to the NORMAL MODE position and reset by pressing UP and DOWN for
more than 3 seconds;
•
The status of the card must be as shown in the INPUT table.
•
Below is an example diagram to help recognise inputs and outputs.
•
Check all card inputs using the indications in the following table; if the input status does not match, follow the indications given
in the row "IF STATUS NOT CORRECT".
PLC INPUT / OUTPUT DIAGNOSTICS