Lifebreath RNC10 Installation Instructions Manual Download Page 24

24

It is necessary to have balanced air flow in an HRV. The volume of air
brought in from the outside must equal the volume of air exhausted by
the unit. If the air flow is not properly balanced, then:

• The HRV may not operate at its maximum efficiency 

• A negative or positive air pressure may occur in the house

• The unit may not defrost properly

• Failure to balance HRV properly may void warranty

Excessive negative pressure may have several undesirable effects. In
some geographic locations, soil gases such as methane and radon gas
may be drawn into the home through basement/ground contact areas. 

Read the Application Warning in Clearances & Requirements section
of this manual!

Prior to balancing, ensure that:

1. All sealing of the duct system has been completed.

2. All of the HRV’s components are in place and 

functioning properly.

3. Balancing dampers are fully open.

4. Unit is on HIGH speed.

5. Air flow in branch lines to specific areas of the house should be

adjusted first prior to balancing the unit. A smoke pencil used at the

grilles is a good indicator of each branch line's relative air flow.

6. After taking readings of both the stale air to the HRV duct and fresh

air to the house duct, the duct with the lower CFM ([L/s] velocity)

reading should be left alone, while the duct with the higher reading

should be dampered back to match the lower reading.

7. Return unit to appropriate fan speed for normal operation

8. A field-supplied balancing damper for the stale air side is required

for system balancing.

Balancing Procedure

The following is a method of field balancing an HRV using a Pitot
tube, which is advantageous in situations when flow stations are not
installed in the duct system. Procedure should be performed with the
HRV on high speed.

The first step is to operate all mechanical systems on high speed, which
have an influence on the ventilation system, i.e. the HRV itself and the
air handler, if applicable. This will provide the maximum pressure that
the HRV will need to overcome, and allow for a more accurate balance
of the unit.

Drill a small hole in the duct (about 3/16"), three feet downstream of
any elbows or bends, and one foot upstream of any elbows or bends.
These are recommended distances but the actual installation may limit
the amount of straight duct.

The Pitot tube should be connected to a magnehelic gauge or digital
manometer capable of reading from 0 to 0.25 in. (0-62 Pa) of water,
preferably to 3 digits of resolution. The tube coming out of the end of
the Pitot is connected to the high pressure side of the gauge. The tube
coming out of the branch of the Pitot is connected to the low pressure
or reference side of the gauge.

Insert the Pitot tube into the duct; pointing the tip into the air flow.

For general balancing it is sufficient to move the Pitot tube around in
the duct and take an average or typical reading. Repeat this procedure
in the other (supply or return) duct. Determine which duct has the
highest air flow (highest reading on the gauge). Then damper that air
flow back to match the lower reading from the other duct. The flow
should now be balanced.

Actual air flow can be determined from the gauge reading. The value
read on the gauge is called the velocity pressure. The Pitot tube comes
with a chart that will give the air flow velocity based on the velocity
pressure indicated by the gauge. This velocity will be in either feet per
minute or meters per second. To determine the actual air flow, the
velocity is multiplied by the cross sectional area of the duct being
measured.

This is an example for determining the air flow in a 6" duct. 

The Pitot tube reading was 0.025 inches of water.

From the chart, this is 640 feet per minute.

The 6" duct has a cross sectional area of    

= [3.14 x (6"÷12)

2

]÷4

= 0.2 square feet

The air flow is then:

640 ft./min. x 0.2 square feet  = 128 cfm

For your convenience, the cross sectional area of some common round
duct is listed below:

DUCT DIAM.

(inches)

CROSS SECTION AREA

(sq. ft.)

5

0.14

6

0.20

7

0.27

The accuracy of the air flow reading will be affected by how close to
any elbows or bends the readings are taken. Accuracy can be increased
by taking an average of multiple readings as outlined in the literature
supplied with the Pitot tube. 

Ensure balanced air flow in HRV. Excessive 
positive pressure may drive moist indoor air into 
the external walls of  the building where it may 
condense (in cold weather) and degrade 
structural components. May also cause key 
holes to freeze up. 

CAUTION

Ensure balanced air flow in HRV/ERV. Excessive 
negative pressure may also cause the back- 
drafting of vented combustion equipment.

WARNING

Air Flow Balancing

Summary of Contents for RNC10

Page 1: ...Heat Recovery Ventilators HRV Manufactured with 2 Speed RNC Electronics Installation Instructions for Heat Recovery Ventilators with 2 Speed RNC Electronics RNC Series Models RNC95 RNC155 RNC200 RNC10...

Page 2: ...in this manual The RNC circuit board also includes an interlock relay which is used to Interlock the HRV to an Air Handler Furnace Refer to Interlocking HRV Operation to an Air Handler Furnace Blower...

Page 3: ...aning or service MOTORS AND BLOWERS Each air stream has one centrifugal blower driven by a common PSC motor 2 speed fan operation FILTERS Washable air filters in exhaust and supply air streams MOUNTIN...

Page 4: ...ve film underneath Then cut the solid tabs between the slits using tin snips or side cutters and remove the knock out plate If any protective film still blocks the opening remove it now In order to ma...

Page 5: ...L TIMERS 99 132 20 Minute Fan Timer initiates high speed ventilation for 20 minutes 3 wire 20 gauge wire min 100 length 99 104 Digital Electronic Timer initiates high speed ventilation for 20 40 or 60...

Page 6: ...ion for 20 minutes 3 wire 20 gauge wire min 100 length 99 104 Digital Electronic Timer initiates high speed ventilation for 20 40 or 60 minutes 3 wire 20 gauge wire min 100 length 99 101 60 Minute Cra...

Page 7: ...h max 99 2040 20 40 ON OFF Dehumidistat Dehumidistat Dial ON OFF Switch and 20 40 Switch The 20 40 Switch will toggle from continuous low speed ventilation to intermittent low speed ventilation of 20...

Page 8: ...100 length max 99 RECIRC Recirculation Control Dehumidistat Dial ON OFF Switch and Recirculation Switch The Recirculation Switch will toggle from continuous low speed ventilation to continuous low spe...

Page 9: ...OFF Switch and 20 40 Switch The 20 40 Switch will toggle from continuous low speed ventilation to intermittent low speed ventilation of 20 minutes fan ON and 40 minutes fan OFF 4 wire 20 gauge wire m...

Page 10: ...peed ventilation to intermittent low speed ventilation of 20 minutes fan ON and 40 minutes fan OFF 4 wire 20 gauge wire min 100 length max 99 RECIRC Recirculation Control Dehumidistat Dial ON OFF Swit...

Page 11: ...IEW FOR VERTICAL MOUNT Connect drain hose to the two field installed spouts located on the bottom of the unit 9 1 8 232 mm 25 1 8 637 mm 22 559 mm HANGING STRAPS STALE AIR TO OUTSIDE FRESH AIR FROM OU...

Page 12: ...trol Features The amount of ventilation required in your home will fluctuate according to the activity level in the house Higher activity levels require more ventilation Main controls can be mounted i...

Page 13: ...ed WIDE HEAD NAILS not supplied DETAIL NOTE Front clearance of 25 inches 635 mm is recommended for servicing unit 19 483 14 3 4 375 31 787 Suspending the HRV using the Provided Hanging Straps Unit mus...

Page 14: ...top end corners mounting screws are already located on the HRV case Securely fasten the other end of the straps to the ceiling making sure the UNIT IS LEVEL The straps are designed to reduce the poss...

Page 15: ...drawn up the hose and into the fresh air supply of the HRV Drain Connections Note Secondary drain pan may be required to protect from condensate leakage Use drain spout provided in door P trap must b...

Page 16: ...d heat if required Air Duct Design and Installation A well designed and installed ducting system will allow the HRV to operate at its maximum efficiency Always try to keep duct runs as short and strai...

Page 17: ...furnace Check local codes authority having jurisdiction for acceptance HRV must be balanced Refer to Airflow Balancing in this manual WARNING RETURN AIR DIRECT CONNECTION of both the HRV SUPPLY AIR ST...

Page 18: ...speed with furnace blower ON EXHAUST AIR from various parts of home i e bathrooms if required kitchens if required Cool Air Return NOTES 1 Furnace blower is recommended to operate when HRV is on to p...

Page 19: ...cing in this manual WARNING FOUR PORT MODELS Models RNC155 RNC200 Unit is normally balanced on HIGH speed with furnace blower ON Outdoors Unit is normally balanced on HIGH speed with air handler blowe...

Page 20: ...filter Canadian building codes require that kitchen grilles be equipped with washable filters Field supplied balancing dampers should be installed external to the unit to balance the amount of stale a...

Page 21: ...r to Remote Control Devices in this manual will shut the entire system down when the remote control is in the OFF position Changing the remote control from OFF to STANDBY can be achieved by Setting th...

Page 22: ...Crank Timer Part No 99 101 Red to Red Black to Black Recirculation Control Part No 99 RECIRC Remove factory installed jumper when installing this control Remove factory installed jumper when installin...

Page 23: ...unit After the defrost period the damper operates in the opposite direction to reopen the fresh air port Defrost cycle repeats until the temperature again rises above 27 F 3 C Defrost Operation Length...

Page 24: ...stances but the actual installation may limit the amount of straight duct The Pitot tube should be connected to a magnehelic gauge or digital manometer capable of reading from 0 to 0 25 in 0 62 Pa of...

Page 25: ...pressure is released When connecting ductwork to the collar take note where screws are located Screws should be located no further than 1 2 from outside edge of collar so as not to impede operation of...

Page 26: ...tep 3 Attach tubes to balancing gauge Step 4 Place gauge on metal door gauge is equipped with a magnetic strip Ensure gauge is level plumb Step 5 Connect tubes to door ports as illustrated in step 5 r...

Page 27: ...ance the system The fresh airflow must equal the stale airflow Step 8 Repeat steps 4 to 7 as required to confirm airflows Magnehelic Door Port Balancing Kit Part No 99 206 Use the Magnehelic Gauge Kit...

Page 28: ...terface relay contacts from initializing the condenser unit This problem can occur at the thermostat because the Y terminal is connected to the G terminal internal to the stat When R and G are closed...

Page 29: ...TPD DEFROST DETAILS P1 1 2 3 4 PIN 1 RED PIN 2 ORANGE PIN 3 BLACK PIN 4 SPARE PCB PLUG IN RED BLACK PLUG IN CONNECTOR BI DIRECTIONAL DAMPER MOTOR ORANGE RED BLACK ORANGE Model RNC5 Only TO MOTORS BLUE...

Page 30: ...ontrol Box DEFROST DETAILS P1 1 2 3 4 PIN 1 RED PIN 2 ORANGE PIN 3 BLACK PIN 4 SPARE PCB PLUG IN RED BLACK PLUG IN CONNECTOR BI DIRECTIONAL DAMPER MOTOR ORANGE RED BLACK ORANGE TO MOTORS INTERFACE REL...

Page 31: ...MOTOR ORANGE RED BLACK ORANGE Model RNC5 Only 12VAC P4 N C COMMON N O TO MOTOR K1 K2 K3 K4 3 4 AMP FUSE CR1 C1 VDR1 VDR2 VDR3 AUTO TRANS T9 T8 T6 T5 T4 T3 T2 P1 SPARE FAN O P C4 C5 P5 1 8 GREEN WHITE...

Page 32: ...ed diffuser or grilles so as not to directly spill the supply air on the occupant eg over a sofa turn down the HRV supply speed A small duct heater 1kw could be used to temper the supply air placement...

Page 33: ...tops on the back of the cabinet NOTE Core will appear to stick out from cabinet approximately 1 8 3mm This is designed this way so that the access door will fit tight against the core 4 Motors Mainten...

Page 34: ...34...

Page 35: ...35...

Page 36: ...36...

Reviews: