Engineering Data - HRV

Model RNC155

THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE

The cross-flow heat recovery core transfers heat between the two air streams. 
It is easily removed for cleaning or service.

MOTORS AND BLOWERS

Each air stream has one centrifugal blower driven by a common PSC motor. 2 speed fan operation.

FILTERS

Washable air filters in exhaust and supply air streams.

MOUNTING THE HRV

Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are
supplied with the unit.

DEFROST

Recirculating damper defrost system.

CASE

Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent
exterior condensation. Drain connections  two - 1/2" (12mm) OD.

WEIGHT

71 lbs. (32.5 kg)

SHIPPING WEIGHT

73 lbs. (33.5 kg)

CONTROLS - HRV System Control

HRV defaults to LOW SPEED when plugged in. HIGH SPEED option is accessible by connecting remote
controls to designated terminals inside electrical box of HRV.

Standard LOW SPEED SETTING can be increased to medium low. 
Off (Standby)/Low or OFF/HIGH speed operation is also available.

OPTIONAL MAIN CONTROLS

(only one main control can be installed on the system)

99-116

Dehumidistat Ventilation Control

- Dehumidistat Dial, ON/OFF Switch and

LOW/HIGH Switch (3 wire) 20 gauge wire (min.) 100' length (max.)

99-2040

20/40 ON/OFF Dehumidistat

- Dehumidistat Dial, ON/OFF Switch and 20/40 Switch.

The 20/40 Switch will toggle from continuous low speed ventilation to intermittent low
speed ventilation of 20 minutes fan ON and 40 minutes fan OFF. (4 wire) 20 gauge wire
(min.) 100' length (max.)

99-RECIRC

Recirculation Control

- Dehumidistat Dial, ON/OFF Switch and Recirculation Switch.

The Recirculation Switch will toggle from continuous low speed ventilation to continuous
low speed recirculation. (4 wire) 20 gauge wire (min.) 100' length (max.)

99-130

Remote Dehumidistat

- Dehumidistat Dial only. (2 wire) 20 gauge wire (min.) 100'

length (max.)

OPTIONAL TIMERS

99-132

20 Minute Fan Timer 

- initiates high speed ventilation for 20 minutes. (3 wire) 20 gauge

wire (min.) 100’ length

99-104

Digital Electronic Timer

- initiates high speed ventilation for 20, 40 or 60 minutes, (3

wire) 20 gauge wire (min.) 100' length

99-101

60 Minute Crank Timer - 

initiates high speed ventilation for up to 60 minutes, (2 wire)

20 gauge wire (min.) 100' length (max.)

WARRANTY

Units carry a lifetime warranty on the heat recovery core and a 5 year replacement parts warranty.

BALANCING DAMPER

33 5/8"

(850mm)

FRESH AIR

FROM OUTSIDE

STALE AIR

TO OUTSIDE

FRESH AIR

TO INSIDE

14 3/4"

(375)

19"

(483)

*All Duct Connections 
6" (150mm) 

CONDENSATE DRAINS

FILTERS

BLOWERS

*NOTE: 

Front clearance 

of 25 inches (635 mm)  
is recommended for 
ser vicing unit. 

RECIRCULATING

DEFROST

DAMPER

MOTOR

CORE

STALE AIR

FROM INSIDE

DIMENSIONS
RNC155

inches (mm)

*Sensible Efficiency – thermal **Latent Efficiency – moisture

Note: Effectiveness - based on temp. differential between the 2 airstreams
Efficiency – takes into account all power inputs

3

2

1

20

40

60

80

100

120

140

160

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

Static Pressure (in w .g.)

A

ir

 Fl

ow

 (c

fm

)

3 - High Speed 
*2 - Medium Low Speed
*1 - Low speed

* Manufacturers Data

Performance

(HVI certified)

Net supply air flow in cfm (L/s) against external static pressure

E.S.P

(external static pressure)

[cfm (L/s)]

@ 0.1" (25 Pa)

150 (71)

@ 0.2" (50 Pa)

146 (69)

@ 0.3" (75 Pa)

134 (63)

@ 0.4" (100 Pa)

121 (57)

@ 0.5" (125 Pa)

106 (50)

@ 0.6" (150 Pa)

92 (43)

Max. Temperature Recovery

78%

Sensible Effectiveness
@ 65 cfm (31 L/s)

32°F (0°C)

76%

*Sensible Efficiency
@ 65 cfm (31 L/s)

32°F (0°C)

64%

*Sensible Efficiency
@ 68 cfm (32 L/s)

-13°F (-25°C)

66%

VAC @ 60HZ

120

WATTS / Low speed.

49

WATTS / High speed

120

Amp rating

1.4

SP-RNC155

Date: _______________________________________________

Tag: __________________________Qty:__________________

Project: _____________________________________________

Engineer:____________________________________________

Contractor: __________________________________________

Supplier: ____________________________________________

Quote#: _____________________________________________

Submitted by: ________________________________________

All units conform to CSA and UL standards

Summary of Contents for RNC10

Page 1: ...Heat Recovery Ventilators HRV Manufactured with 2 Speed RNC Electronics Installation Instructions for Heat Recovery Ventilators with 2 Speed RNC Electronics RNC Series Models RNC95 RNC155 RNC200 RNC10...

Page 2: ...in this manual The RNC circuit board also includes an interlock relay which is used to Interlock the HRV to an Air Handler Furnace Refer to Interlocking HRV Operation to an Air Handler Furnace Blower...

Page 3: ...aning or service MOTORS AND BLOWERS Each air stream has one centrifugal blower driven by a common PSC motor 2 speed fan operation FILTERS Washable air filters in exhaust and supply air streams MOUNTIN...

Page 4: ...ve film underneath Then cut the solid tabs between the slits using tin snips or side cutters and remove the knock out plate If any protective film still blocks the opening remove it now In order to ma...

Page 5: ...L TIMERS 99 132 20 Minute Fan Timer initiates high speed ventilation for 20 minutes 3 wire 20 gauge wire min 100 length 99 104 Digital Electronic Timer initiates high speed ventilation for 20 40 or 60...

Page 6: ...ion for 20 minutes 3 wire 20 gauge wire min 100 length 99 104 Digital Electronic Timer initiates high speed ventilation for 20 40 or 60 minutes 3 wire 20 gauge wire min 100 length 99 101 60 Minute Cra...

Page 7: ...h max 99 2040 20 40 ON OFF Dehumidistat Dehumidistat Dial ON OFF Switch and 20 40 Switch The 20 40 Switch will toggle from continuous low speed ventilation to intermittent low speed ventilation of 20...

Page 8: ...100 length max 99 RECIRC Recirculation Control Dehumidistat Dial ON OFF Switch and Recirculation Switch The Recirculation Switch will toggle from continuous low speed ventilation to continuous low spe...

Page 9: ...OFF Switch and 20 40 Switch The 20 40 Switch will toggle from continuous low speed ventilation to intermittent low speed ventilation of 20 minutes fan ON and 40 minutes fan OFF 4 wire 20 gauge wire m...

Page 10: ...peed ventilation to intermittent low speed ventilation of 20 minutes fan ON and 40 minutes fan OFF 4 wire 20 gauge wire min 100 length max 99 RECIRC Recirculation Control Dehumidistat Dial ON OFF Swit...

Page 11: ...IEW FOR VERTICAL MOUNT Connect drain hose to the two field installed spouts located on the bottom of the unit 9 1 8 232 mm 25 1 8 637 mm 22 559 mm HANGING STRAPS STALE AIR TO OUTSIDE FRESH AIR FROM OU...

Page 12: ...trol Features The amount of ventilation required in your home will fluctuate according to the activity level in the house Higher activity levels require more ventilation Main controls can be mounted i...

Page 13: ...ed WIDE HEAD NAILS not supplied DETAIL NOTE Front clearance of 25 inches 635 mm is recommended for servicing unit 19 483 14 3 4 375 31 787 Suspending the HRV using the Provided Hanging Straps Unit mus...

Page 14: ...top end corners mounting screws are already located on the HRV case Securely fasten the other end of the straps to the ceiling making sure the UNIT IS LEVEL The straps are designed to reduce the poss...

Page 15: ...drawn up the hose and into the fresh air supply of the HRV Drain Connections Note Secondary drain pan may be required to protect from condensate leakage Use drain spout provided in door P trap must b...

Page 16: ...d heat if required Air Duct Design and Installation A well designed and installed ducting system will allow the HRV to operate at its maximum efficiency Always try to keep duct runs as short and strai...

Page 17: ...furnace Check local codes authority having jurisdiction for acceptance HRV must be balanced Refer to Airflow Balancing in this manual WARNING RETURN AIR DIRECT CONNECTION of both the HRV SUPPLY AIR ST...

Page 18: ...speed with furnace blower ON EXHAUST AIR from various parts of home i e bathrooms if required kitchens if required Cool Air Return NOTES 1 Furnace blower is recommended to operate when HRV is on to p...

Page 19: ...cing in this manual WARNING FOUR PORT MODELS Models RNC155 RNC200 Unit is normally balanced on HIGH speed with furnace blower ON Outdoors Unit is normally balanced on HIGH speed with air handler blowe...

Page 20: ...filter Canadian building codes require that kitchen grilles be equipped with washable filters Field supplied balancing dampers should be installed external to the unit to balance the amount of stale a...

Page 21: ...r to Remote Control Devices in this manual will shut the entire system down when the remote control is in the OFF position Changing the remote control from OFF to STANDBY can be achieved by Setting th...

Page 22: ...Crank Timer Part No 99 101 Red to Red Black to Black Recirculation Control Part No 99 RECIRC Remove factory installed jumper when installing this control Remove factory installed jumper when installin...

Page 23: ...unit After the defrost period the damper operates in the opposite direction to reopen the fresh air port Defrost cycle repeats until the temperature again rises above 27 F 3 C Defrost Operation Length...

Page 24: ...stances but the actual installation may limit the amount of straight duct The Pitot tube should be connected to a magnehelic gauge or digital manometer capable of reading from 0 to 0 25 in 0 62 Pa of...

Page 25: ...pressure is released When connecting ductwork to the collar take note where screws are located Screws should be located no further than 1 2 from outside edge of collar so as not to impede operation of...

Page 26: ...tep 3 Attach tubes to balancing gauge Step 4 Place gauge on metal door gauge is equipped with a magnetic strip Ensure gauge is level plumb Step 5 Connect tubes to door ports as illustrated in step 5 r...

Page 27: ...ance the system The fresh airflow must equal the stale airflow Step 8 Repeat steps 4 to 7 as required to confirm airflows Magnehelic Door Port Balancing Kit Part No 99 206 Use the Magnehelic Gauge Kit...

Page 28: ...terface relay contacts from initializing the condenser unit This problem can occur at the thermostat because the Y terminal is connected to the G terminal internal to the stat When R and G are closed...

Page 29: ...TPD DEFROST DETAILS P1 1 2 3 4 PIN 1 RED PIN 2 ORANGE PIN 3 BLACK PIN 4 SPARE PCB PLUG IN RED BLACK PLUG IN CONNECTOR BI DIRECTIONAL DAMPER MOTOR ORANGE RED BLACK ORANGE Model RNC5 Only TO MOTORS BLUE...

Page 30: ...ontrol Box DEFROST DETAILS P1 1 2 3 4 PIN 1 RED PIN 2 ORANGE PIN 3 BLACK PIN 4 SPARE PCB PLUG IN RED BLACK PLUG IN CONNECTOR BI DIRECTIONAL DAMPER MOTOR ORANGE RED BLACK ORANGE TO MOTORS INTERFACE REL...

Page 31: ...MOTOR ORANGE RED BLACK ORANGE Model RNC5 Only 12VAC P4 N C COMMON N O TO MOTOR K1 K2 K3 K4 3 4 AMP FUSE CR1 C1 VDR1 VDR2 VDR3 AUTO TRANS T9 T8 T6 T5 T4 T3 T2 P1 SPARE FAN O P C4 C5 P5 1 8 GREEN WHITE...

Page 32: ...ed diffuser or grilles so as not to directly spill the supply air on the occupant eg over a sofa turn down the HRV supply speed A small duct heater 1kw could be used to temper the supply air placement...

Page 33: ...tops on the back of the cabinet NOTE Core will appear to stick out from cabinet approximately 1 8 3mm This is designed this way so that the access door will fit tight against the core 4 Motors Mainten...

Page 34: ...34...

Page 35: ...35...

Page 36: ...36...

Reviews: