background image

It is necessary to have balanced air flows in an HRV. The volume of air 
brought in from the outside must equal the volume of air exhausted by 
the unit. If the air flows are not properly balanced, then;

The HRV may not operate at its maximum efficiency

A negative or positive air pressure may occur
in the building

The unit may not defrost properly

Failure to balance HRV properly may void warranty

Excessive

 

positive

 

pressure

  may  drive  moist  indoor  air  into  the 

external  walls  of  the  building  where  it  may  condense  (in  cold 
weather)  and  degrade  structural  components.  May  also  cause  key 
holes to freeze up.

Excessive

 

negative

 

pressure

  may  have  several  undesirable 

effects.  In  some  geographic  locations,  soil  gases  such  as  methane 
and  radon  gas  may  be  drawn  into  the  home  through 
basement/ground  contact  areas.  Excessive  negative  pressure  may 
also cause the backdrafting of vented combustion equipment.

Read

 

the

 

Application

 

Warning

 

on

 

the

 

front

 

of

 

this

 

manual!

Prior

 

to

 

balancing,

 

ensure

 

that:

1. All sealing of the ductwork system has been completed.
2. All of the HRV's components are in place and functioning properly.
3. Balancing dampers are fully open.
4. Unit is on HIGH speed.
5. Air flows  in branch lines to  specific  areas  of  the  house should be

adjusted  first  prior  to  balancing  the  unit.  A  smoke  pencil  used  at

the  grilles  is  a  good  indicator  of  each  branch  line's  relative  air

flow.

6. After  taking  readings  of  both  the  stale  air  to  the  HRV  duct  and

fresh  air  to  the  house  duct,  the  duct  with  the  lower  CFM ([L/

s] velocity) reading should be left alone, while the duct with the

higher reading  should  be  adjusted  back  to  match  the  lower  read-

ing. See 

Adjusting

 

the

 

Airflow

.

7. Return unit to appropriate fan speed for normal operation

BALANCING

 

PROCEDURE

The  following  is  a  method  of  field  balancing  an  HRV  using  a  Pitot 

tube, advantageous  in  situations  when  flow  stations  are  not  installed 

in  the ductwork. Procedure should be performed with the HRV on high 

speed.
The  first  step  is  to  operate 

all

  mechanical  systems  on  high  speed, 

which  have  an  influence  on  the  ventilation  system,  i.e.  the  HRV 

itself and  the  forced  air  furnace  or  air  handler  if  applicable.  This  will 

provide the  maximum  pressure  that  the  HRV  will  need  to  overcome, 

and allow for a more accurate balance of the unit.
Drill a small hole in the duct (about 3/16"), three feet 

downstream  of  any  elbows  or  bends,  and  one  foot 

upstream  of  any  elbows  or  bends.  These  are 

recommended  distances  but  the  actual  installation 

may limit the amount of straight duct.
The  Pitot  tube  should  be  connected  to  a  

manometer  capable  of  reading  3  digits  of 

resolution.  The  tube  coming  out  of  the  top  of 

the pitot  is  connected  to  the  high  pressure  side  of 

the gauge.  The  tube  coming  out  of  the  side  of  the 

pitot is  connected  to  the  low  pressure  or  reference 

side of the gauge.

I

nsert  the  Pitot  tube  into  the  duct;  pointing  the tip 

into the airflow.

For  general  balancing  it  is  sufficient  to  move  the  pitot  tube  around 
in the  duct  and  take  an  average  or  typical  reading.  Repeat  this 
procedure  in  the  other  (supply  or  return)  duct.  Determine  which 
duct has  the  highest  airflow  (highest  reading  on  the  manometer). 
Adjust  the  higher  airflow  by  reducing  the  fan  speed  (see 
“Adjusting  the  Airflow”).  The  flows  should  now  be  balanced. 
Actual  airflow  can  be  determined  from  the  gauge  reading.  The 
value  read  on  the  gauge  is called  the  velocity  pressure.  The  Pitot 
tube  comes  with  a  chart  that will  give  the  air  flow  velocity  based 
on  the  velocity  pressure  indicated  by  the  gauge.  This  velocity  will 
be  in  either  feet  per  minute  or  meters  per  second.  To  determine 
the  actual  airflow,  the  velocity  is  multiplied  by  the  cross  sectional 
area of the duct being measured.
This is an example for determining the airflow in a 6" duct.
The Pitot tube reading was 0.025 inches of water.
From the chart, this is 640 feet per minute.
The 6" duct has a cross sectional area of

= [3.14 x (6"÷12)

2

]÷4

= 0.2 square feet 

The airflow is then:
640 ft./min. X 0.2 square feet  = 128 cfm

For your convenience, the cross sectional area of some common round duct 
is listed below:

DUCT

 

DIAM.

 (inches)

5 (127 mm) 
6 (152 mm) 
7 (178 mm)

CROSS

 

SECTION

 

AREA

 (sq. ft.) 

0.14
0.20
0.27

The accuracy of the air flow reading will be affected by how close to 
any  elbows  or  bends  the  readings  are  taken.  Accuracy  can  be 
increased by taking an average of multiple readings as outlined in the 
literature supplied with the Pitot tube.

DUCT

AIR

FLOW

Pitot tube

Digital manometer

Pitot

 

tube

 

and

 

gauge

Place pitot tube  a minimum 

of 18"

 

from

 

blower or 

elbows

Note:

 

Duct

 

connections may vary,

depending on model.

Outdoors

Pitot

tube

Pitot

tube

Pitot

 

Tube

 

Air

 

Flow

 

Balancing

 

-

 

Commercial

Pitot

 

Tube

 

Air

 

Flow

Balancing

 

Kit

c/w digital manometer, 

Pitot tube, hose and tool 

bag.

PART NO. 99-BAL-KIT

Digital Manometer

 

2

0

Summary of Contents for 1200 POOL

Page 1: ...POOL 1200POOL Operation and Installation Manual Lifebreath Pool Room HRVs provide fresh clean air without sacrificing the savings of your energy conserving home The aluminum cores of the HRV provide effective and efficient heat recovery and air exchange Models 700POOL 1200POOL ...

Page 2: ...erse Installation of the HRV 24 25 Never install an HRV in a situation where its normal operation lack of operation or partial failure may result in the backdrafting or improper functioning of vented combustion equipment It is always important to assess how the operation of any HRV may interact with vented combustion equipment ie Gas Furnaces Oil Furnaces Wood Stoves etc Do not apply electrical po...

Page 3: ...er the system Outside air is prevented from entering the HRV during recirculation by the supply damper closing off The exhaust fan to the outside is shut off during this recirculation mode Outside air does not enter the system again until the pool room humidity exceeds the setpoint of the dehumidistat HRV Aluminum Core A Heat Recovery Ventilator HRV is designed to provide fresh air into a building...

Page 4: ...eed Fan setting Low Medium High 4 wire connection 20 gauge wire minimum CORES Modular 2 section patented aluminum heat recovery cores arranged for efficient counter flow ventilation MOTORS Two PSC 3 speed single shafted 120 VAC 4 5 Amps each 9 total on high speed HP 1 4 1450 RPM Watts total on high speed 1032 MCA 11 3 MOP 15 FILTERS Washable air filters in exhaust and supply air streams BLOWERS Sl...

Page 5: ...mm H MOUNTING Unit to be set on support brackets hung by threaded rod type apparatus brackets and rods not provided CASE Unit has front and back access doors and electrical panel can be switched to either side giving installer flexibility in duct direction 20 gauge prepainted galvanized steel G60 for superior corrosion resistance Insulated with elastomeric insulation where required to prevent exte...

Page 6: ...ng flow Rate factor depending on the indoor air temperature outdoor temperature and room relative humidity Flow Rate Factor 21 70 Evaporation rate X Flow Rate CFM square foot of water surface area 0 052 X 21 70 1 12 4 Multiply the value in step 3 by the area of the pool X Value for step 3 CFM Area of pool 512 X 1 12 573 Calculating the Ventilation Rate for the Pool Room Spas Hot Tubs must be consi...

Page 7: ... 0 053 0 082 0 073 0 064 0 094 0 085 0 076 0 107 0 098 0 089 0 121 0 112 0 103 78 0 059 0 049 0 039 0 069 0 059 0 049 0 080 0 070 0 060 0 091 0 082 0 072 0 104 0 095 0 085 0 118 0 109 0 099 80 0 056 0 046 0 035 0 066 0 056 0 045 0 077 0 067 0 056 0 089 0 079 0 068 0 102 0 091 0 081 0 116 0 105 0 095 82 0 053 0 042 0 031 0 063 0 052 0 041 0 074 0 063 0 052 0 086 0 075 0 064 0 099 0 088 0 077 0 113 ...

Page 8: ... 39 40 29 80 24 00 34 70 26 40 21 30 30 70 23 50 19 00 27 30 21 00 17 00 15 56 20 41 00 32 20 48 50 35 80 28 30 42 10 31 40 25 00 36 80 27 60 22 10 32 40 24 50 19 60 28 60 21 70 17 50 20 63 40 44 70 34 50 53 70 38 50 30 00 46 00 33 50 26 30 39 70 29 30 23 10 34 60 25 70 20 40 30 30 22 70 19 10 25 74 90 50 10 37 60 61 70 42 50 32 40 51 80 36 40 28 10 44 00 31 50 24 50 37 80 27 40 21 50 32 70 24 10 ...

Page 9: ...be mounted on an equipment platform providing the drain hoses are clear and there is sufficient space to open the doors for servicing Install the drain pans in the bottom of the HRV so the drain connections protrude through the holes provided Use drain hoses with hose clamps to connect the drain pan outlets to a floor drain or standpipe Make sure the drain line slopes down to the outlet If this is...

Page 10: ...es of contaminants such as automobile exhaust fumes gas meters garbage cans containers etc not exposed to prevailing winds The outside perimeter of the weatherhood must be caulked to prevent leakage into the building The design and size of the weatherhoods or louvers chosen by the installer must allow for adequate free area Water and snow penetration of the system is minimized when the airflow doe...

Page 11: ...e of room EXPOSED WALL Min 10 0 HRV Typical Duct Layout Sketch 1 Sample Duct Layout 1 System Installation It is necessary to design and size the duct distribution system for both the supply and the exhaust air streams Proper duct design will Minimize air flow requirements Ensure a comfortable environment by using reheat if required Optimize humidity control including eliminating condensation on wi...

Page 12: ...le air from opposite side of room Typical Duct Layout Sketch 2 Sample Duct Layout 2 System Installation It is necessary to design and size the duct distribution system for both the supply and the exhaust air streams Proper duct design will Minimize air flow requirements Ensure a comfortable environment by using reheat if required Optimize humidity control including eliminating condensation on wind...

Page 13: ...ated when outside temperatures drop below 27 F 3 C A motor driven damper door mechanism opens the pool and defrost air port and closes off the supply air from outside port This defrost cycle operates for about 3 minutes and then the damper reverts to its previous run time position 2 RECIRCULATION MODE TO POOL ROOM EXHAUST TO OUTSIDE FROM POOL ROOM FROM POOL ROOM Ø FRESH AIR FROM OUTSIDE DAMPER CLO...

Page 14: ...d develops in one of the devices Stale Air Return System Fresh Air Supply System Adjustable Grilles The stale air return system is used to draw air from the points in the building where the highest humidity levels exist Balancing dampers and or adjustable grilles are recommended on all return air lines which are used during installation to help balance the draw from different areas of the pool roo...

Page 15: ...rcuit board Switch T37 and T39 on the Aircom circuit board Switch T37 red wire and T39 yellow wire on the Aircom circuit board if you wish to reverse the Supply Air From Outside and Pool and Defrost Air ports This illustration shows the factory configuration T31 T32 T33 T34 T35 T36 T37 T38 T39 T40 T41 T42 Contact 1 N 0 COM N C N 0 COM N C N 0 COM N C N 0 COM Contact 2 Contact 3 Contact 4 N C RED Y...

Page 16: ...T HIGH OFF OFF OFF MED LOW Optional 3 Speed Control Part 99 500 Connect to R W Y and G on Thermostat O G Y W R C Thermostat 24V Jumper Wire HIGH MED LOW Jumper Wire Placement on Micro Processor Board SPEED High R W Medium R Y Low R G JUMPER T18 T5 T13 C4 T17 T19 T1 T2 T3 T4 T6 T14 T15 T16 C3 C2 C1 RELAY Fan Hi Fan Med Fan Low FEED Line Ligne Neutral Neutre T20 CHASSIS T11 T12 T44 N O N O N O N O C...

Page 17: ...ss and release the Dehumidistat button until the Dehumidistat Light is at the desired setting After 5 seconds the Dehumidistat light will either flash or be on continuous A flashing light indicates the humidity level is higher than the setting and the unit is operating on high speed ventilation A continuous light indicates the humidity level is lower than the setting Refer to the unit s Operation ...

Page 18: ...n the Back Plate Figure C 8 Attach the Back Plate to the wall using the 2 supplied screws and anchors 9 Attach the Face Plate to the Back Plate Figure B Note Be careful to correctly align the Face Plate to avoid damaging the Face Plate Contact Pins 10 Insert the Operating Instructions Card into the control Figure A 11 Connect the 3 wire 20 gauge min 100 ft length max to the digital controls termin...

Page 19: ...der to prevent electric shock when cleaning or servicing the HRV it is extremely important to confirm the polarity of the power line that is switched by the safety disconnect switch whose control arm is located on the outside of the electrical control box area The hot line black is the proper line to be switched To confirm the proper polarity use a voltmeter or test lamp to make sure there is no p...

Page 20: ...nit Drill a small hole in the duct about 3 16 three feet downstream of any elbows or bends and one foot upstream of any elbows or bends These are recommended distances but the actual installation may limit the amount of straight duct The Pitot tube should be connected to a manometer capable of reading 3 digits of resolution The tube coming out of the top of the pitot is connected to the high press...

Page 21: ...e any of the other DIP switch settings Only available when unit is operating in ventilation mode Factory Setting DIP Switch 8 OFF The HRV enters defrost mode when outdoor temperatures drop below 27 F 3 C The factory defrost cycle is 4 minutes defrost with a 30 minute run time Increased Defrost Time DIP Switch 8 ON Cooler climates may require a more aggressive defrost cycle Positioning DIP switch 8...

Page 22: ...temporarily preventing its removal In most cases all the core requires is a wash in a mild detergent and warm water to completely clean it Do not use harsh chemicals as their use may cause corrosion in the HRV The time required between each core service depends on the application in which the HRV is installed Service may be required as often as one month two months or at the very least cleaned eve...

Page 23: ...drain completely and in a reasonable amount of time Note if the water does not drain right away check for blockage in the drain line also check that the drain line has a good slope to it 1 8 1 4 per foot The drain line itself should have a P trap in it below the HRV which is to be filled with water to prevent odors or gases from entering back into the unit Duct Work It is a good idea to inspect du...

Page 24: ...rt the shim around the damper rod ensuring it is placed on the opposite side of the rod from the set screws Both of the set screws should screw directly into the damper rod not the shim 17 Prior to tightening the set screws ensure proper alignment of the damper door such that it is evenly spaced over the port collars providing a good seal in both directions 18 Once alignment is confirmed tighten t...

Page 25: ...the lower blower motor wires through the hole in the divider panel into the electrical box 29 Route upper motor wires into the electrical box 30 Route damper motor wires into e box and connect the motor wires to the circuit board relays and capacitors using wiring diagram found in manual for reverse installations 31 Connect damper motor wires to circuit board using wiring diagram found in manual f...

Page 26: ...ior hoods or vents remove and clean filter remove and clean core check and open grilles open and adjust dampers have electrician check supply voltage at house check duct installation increase the speed of the HRV have contractor balance HRV locate the grilles high on the walls or under the baseboards install ceiling mounted diffuser or grilles so as not to directly spill the supply air on the occu...

Page 27: ...27 Wiring Diagram Models 700 1200 POOL ...

Page 28: ...ects please contact AIRIA BRANDS INC 511 McCormick Blvd London Ontario N5W 4C8 519 457 1904 or fax 519 457 1676 to find the name of your nearest dealer in order to repair the product The labor required to install any replacement part s shall be dealt with at the option of the customer in either of the following ways a the customer may supply labor at their own expense or b if the product was purch...

Page 29: ...29 ...

Page 30: ...30 ...

Page 31: ...31 ...

Page 32: ...info lifebreath com T 1 855 247 4200 F 1 800 494 4185 69 POOL 100516 ...

Reviews: