TROUBLESHOOTING

This chapter describes the most frequently encountered problems with the solutions for resolving them. In certain cases, it is explicitly envisaged

that operations be performed by a professional fitter: these indications must be followed in order to avoid exposure to serious risks.

4.1  Malfunctions indicated on the control unit

The malfunctions detected by the control unit are indicated through the lighting of the 5 LEDs on the display.

The control unit also indicates the presence of a fault on the exterior through the flashing lamp: three flashes and a pause, if the motor is in motion.

SIGNAL

MALFUNCTION

ACTION

POSSIBLE SOLUTION

N.B.

Obstacle detection sensitivity regulation is 

described in the ADJUSTMENTS CHAP.

The check intervenes inverting motion, i.e. 

performing an opening, and when it reaches 

the end of the stroke, it awaits a new signal 

(even in condominium mode); however, if the 

system is opening, it intervenes inverting the 

motion for a short stretch (3/4 cm) and then 

stopping until such time as new commands 

are given.

Obstacle

N.B.

In this situation release the automation and 

call for technical assistance.

The control intervenes by passing the system 

to the operation condition with dead man command 

and reduced speeds.

This class includes 

various incorrect and 

unsafe operation 

situations

N.B. if the problems persist it is absolutely necessary to call the assistance service.

BUFFER BATTERIES (OPTIONAL)

a)   The 

RG1 24DL

 control unit can be fitted with a pair of 2Ah 12V buffer batteries (AGE 12) (optional), which allows emergency operation in the event

      of a power failure.

b)   T

he batteries must be installed and replaced at the end of their service life by a PROFESSIONAL FITTER and not by the user, as there are live parts close by.

c)   The control unit is designed to house an AGECH battery charger, which automatically charges the connected pair of batteries.

In the event of power failure, the automation operates in a partial way for a certain number of actions. 

The gate switches into “DEAD MAN” mode (persistent commands) automatically.

The photocells, flashing light, courtesy light, indicator light and other devices connected to the auxiliaries power supply do not work.

The electric lock only works manually.

Battery function is indicated on the control unit by the alternate flashing of the green LEDs:

 

:

Summary of Contents for RG1 24DL

Page 1: ...AIS DE COMANDO PARA PORT ES DE BATENTE INSTRU ES E ADVERT NCIAS PARA A INSTALA O USO E MANUTEN O STEUERUNG F R 24V ANTRIEBE ANLEITUNGEN UND HINWEISE F R INSTALLATION GEBRAUCH UND WARTUNG CENTRALA STER...

Page 2: ...os de uma automatiza o tipo Bestandteile und Vorrichtungen eines Musterantriebs Cz ci sk adowe i urz dzenia automatyki Komponenty a zariadenia pre typick automatiz cie Tartoz kok s r szegys gek ltal n...

Page 3: ...E M1 M2 L N FUSE 6AC 6AC 6AC 6AC AGECH MOTO R ENCO DER RED BLUE WHITE GREEN BROWN 230V V 0 V 2 1 V 4 2 M O C O N C N RX V 0 V 2 1 V 4 2 TX 6 11 18 19 1 2 14 16 12 16 1 2 3 4 5 6 15 16 24 Vdc 15w max...

Page 4: ...ontrol until all ve LEDs light c Wait 25 seconds or press again to quit The automation is now programmed SEMIAUTOMATIC mode is enabled by giving the STEP command the automation changes movement follow...

Page 5: ...ODE Open pause close pause CONDOMINIUM MODE Open 6 8 RESISTIVE resistive input Leave jumpered with 8 2k resistance if no device is envisaged 11 PHOTO N C input for photocells or safety devices Does no...

Page 6: ...eeded may vary depending on the installation and type and quantity of devices installed The cables used in the installation must be IEC 60335 compliant ATTENTION the cables used must be suited to the...

Page 7: ...the first two and the last two LEDs will flash alternatively After alternate flashing all initialised remote controls are reset c Wait 25 seconds or press again to quit 3 ADJUSTMENTS 3 1 Function mode...

Page 8: ...is switched on automatic reclosure is enabled to deactivate it press until all the LEDs switch off LEDS ON PAUSE TIME AUTOMATIC RE CLOSURE IS NOT ENABLED 5 s 10 s 30 s 60 s 120 s 3 2 Functions 3 2 1 C...

Page 9: ...bstacle the automation inverts motion and performs complete opening If the obstacle is detected 3 times consecutively the automation stops in a completely open position awaiting a command 2 If the con...

Page 10: ...e N B In this situation release the automation and call for technical assistance The control intervenes by passing the system to the operation condition with dead man command and reduced speeds This c...

Page 11: ...is manual must always be observed when installing connecting adjusting testing and setting the control unit The Manufacturer declines all responsibility for damage or injury caused by non observance o...

Page 12: ...a general mechanical and electrical diagram risk analysis and solutions adopted for eliminating or reducing risks manuals of the individual components list of the components used instructions for use...

Page 13: ...erson with a similar qualification in order to avoid risks Do not perform technical or programming modifications on the control unit Operations of this type may cause malfunctions and or risk of accid...

Page 14: ...ing methods EN 12453 Industrial commercial and garage doors and gates Safety in the usage of motorised doors Requisites EN 60204 1 1997 Machinery safety Electric equipment of the machine Part 1 genera...

Page 15: ...4 A Address Via Sandro Pertini 3 5 31014 COLLE UMBERTO TV Italia Telephone 39 0438 388592 Telefax 39 0438 388593 http www homelife it e mail info homelife it...

Reviews: