PFCL Elite 6 / PFCL Elite 12
- 24 -
Program Setup Screen (PC6, TypeC2):
The capacitor banks are composed of stages with different power ratings. The base power (value 1) will be
that of the stage with the lowest power. The powers of all other stages will depend on the power of the first
stage. Therefore, the following programs would be available:
Program 1:1:1… All stages have the same power as the first stage.
Program 1:2:2… After the second stage, all capacitors have a power that is twice as
much as that of the first stage.
Program 1:2:4… The second stage has a power that is twice as much as that of the first
stage and all subsequent stages have a power that is four times as much as that of the
first stage.
The unit can easily configure one of the 10 standard programs, which are as follows:
1:1:1:1, 1:2:2:2, 1:2:4:4, 1:2:4:8, 1:1:2:2, 1:1:2:4, 1:2:2:4, 1:2:3:3, 1:2:3:4, 1:2:3:6.
An open program can also be configured between 1:1:1:1 and 1:9:9:9 in special cases. To do so, select the
OPEn option, a second line that can be edited will appear in this case:
The unit is configured with the 1:1:1:1 program by default
Table 5-4.- Programs available in the PFCL Elite system
Screen Display
C-Stage Power Ratio
1111 1:1:1:1:1….
1222 1:2:2:2:2….
1244 1:2:4.4:4….
1248 1:2:4:8:8….
1122 1:1:2:2:2….
1124 1:1:2:4:4….
1224 1:2:2:4:4….
1233 1:2:3:3:3….
1234 1:2:3:4:4….
1236 1:2:3:6:6….
OPEn
1:1:1:1:1…. up to 1:9:9:9:9….
Setup Screen of the Number of Stages (PC7, TypeC2):
This screen can be used to configure the number of relay outputs for the regulator. Up
to 6 or 12 outputs can be configured, depending on the model, PFCL Elite 6 or PFCL
Elite 12.
Setup Screen of the Connection (Tc) and Reconnection (Tr) Delay Time (PC8, TypeC2):
This parameter establishes the unit's action time in seconds. The adjustment time, Tc,
establishes the delay to connect or disconnect subsequent stages. It also regulates the
time between the disconnection of a stage and its reconnection, Tr (Tr is always 5
times the Tc). This device can adjust the Tc in a range of 4 seconds to 1000 seconds
and the capacitor reconnection time, Tr, between 20 and 5000 s. The Tc parameter is
configured to 10 seconds by default and the Tr parameter is configured to 50 seconds
by default.