Ⅱ
. Starting after long periods of storage
1. Wipe and remove protective lubricants from all contacts
2. Remove spark plugs one at a time to remove 1oz or 30grams of engine oil from
cylinders. Use clean rag and place it in each spark plug opening and turn engine over
slowly allowing oil to soak into clean rag. Repeat this process for each cylender
3. Add light penetrant oil to all hinges.
4. Add coolant.
5. Add engine oil.
6. Check all wires and hose connections.
7. Install battery connecting positive lead first and then negative lead
7. Reconnect gas line and check for leaks using a digital gas detector.
8. Star engine to make sure operation is normal.
9. If belts are making noise, shut down generator, allow to cool down and then tighten
belts as needed
10. Check all electrical parts and digital display for normal working conditions.
11. If red indicator light on display panel is illuminated, perform trouble shooting
procedures. See trouble shooting guide.
Chapter Four: Maintenance of Generator
Regular maintenance is an important part of your investment and provides longevity
of the complete generator system. Maintaining good working condition, according to the
specifications outlined, will provide many years of dependable service.
The following generator maintenance specifications are based on a good working
environment. If working conditions are less than desirable, (such as excessive dust, dirt
and humidity, etc.) the maintenance interval periods should be performed sooner than
normal.
When maintaining the generator set, you should operate in strict accordance with the
following requirements. Improper use and operation can cause premature failure.
Ⅰ
. Breaking-in period of New Engine
The life of the engine is greatly determined by the state of the first cycle of use. It is
recommended that the oil be replaced after only 10 hours of use on the first cycle. The
new engine should be maintained and operated as required. Abnormal engine ware will
directly affect the life of generator engine.
Ⅱ
. Maintenance of the Fuel System