31
Routine Maintenance
The Liebert UPStation S™ UPS should operate for years with minimum maintenance. Keep UPS clean and cool to
enhance system reliability. Occasionally vacuum dust from around ventilation grilles and wipe UPS with a dry cloth. Do
not use liquid or aerosol cleaning fluids.
Periodically check UPS operation by switching off utility power and observing the On Battery message. Do this with only
non-critical loads connected to the unit.
Liebert UPStation S™ Specifications
SYSTEM
Safety Agencies
CSA 22.2, UL 1778 listed
Audible Noise
55 dBA at one meter
Transient/ Surge Protection
Per IEEE 587/ANSI C62.41 Class A&B
Efficiency
Minimum 87% at full load
PHYSICAL CHARACHTERISTICS (See Site Planing Data for dimensions and weight)
Operating Environment
0 degrees C to 40 degrees C
Relative Humidity
0 to 95% relative humidity (non-condensing)
Altitude
5000 feet without derating
AC INPUT
Voltage Range
176 to 264 VAC
Voltage Configuration and Connection
Single phase, 3-wire plus ground (L1-L2-N-G)
Single phase, 2-wire plus ground (L1-N-G)
Three phase, 4-wire plus ground (L1-L2-L3-N-G) (8-18 kVA only)
Three phase, 3-wire plus ground (L1-L2-L3-G) (8-18 kVA only)
Frequency Range
45 Hz to 65 Hz
Current THD
5% THD maximum at full load
Power Factor
.98 typical
AC OUTPUT
Voltage Regulation
Typically less than +/- 2%
Voltage Distortion
Max. 3% THD for linear loads, max. 5% THD for full non-linear
loads
Transient Response
Less than +/- 5% for 100% step load; recovery to within 1% in 50
ms.
Frequency
50 Hz or 60 Hz
Frequency Slew Rate
1 Hz/sec (user-selectable 0.3 to 3 Hz/sec
Frequency Sync Rate
+/- 1 Hz (user sele/- 0.1 Hz to 5 Hz
Load Crest Factor
3:1
Overload
125% for 10 minutes, 150% 10 seconds
BATTERY
Type
Sealed, low maintenance, lead acid
Recharge Rate
10 times discharge duration to 95%
Battery Runtime
Minimum 10 minutes at full load
Battery Voltage
Nominal: 192 VDC Float: 220 to 230 VDC