26
BATTERY CABINET SPECIFICATIONS
MODEL NUMBER
GXT36VBATT
GXT48VBATT
GXT96VBATT
Used w/ UPS Model
1000RT
1500RT
2000RT/3000RT
DIMENSIONS: in (mm)
Unit
W x D x H
177 x 522 x 430
(7.0 x 19.3 x 16. 9)
177 x 522 x 430
(7.0 x 19.3 x 16. 9)
177 x 522 x 430
(7.0 x 19.3 x 16. 9)
Shipping
W x D x H
13.38 x 26.0 x 22.25
(340 x 660 x 565)
13.38 x 26.0 x 22.25
(340 x 660 x 565)
13.38 x 26.0 x 22.25
(340 x 660 x 565)
WEIGHT: lbs (kg)
Unit
61.3 (27.9)
71.6 (32.5)
71.6 (32.5)
Shipping
68.4 (31)
78.7 (35.7)
78.7 (35.7)
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, lead acid
# of Strings x Qty/Str. x
Batt. Voltage x Batt.
Rating
2x3x12Vx7.0 or 7.2 AH
2x4x12Vx7.0 or 7.2 AH
1x8x12Vx7.0 or 7.2
AH
Batt. Mfg./ Part #
CSB GP1270F2 or Panasonic LC-R127R2CH1
Back-up Time
See Typical Battery Discharge Curves
Recharge Time
5 Hours to 95% capacity after full discharge into 100% load
ENVIROMENTAL
Operating
Temperature
+32° F to +104° F (0° C to +40° C)
Storage
Temperature
+5° F to +122 °F (-15° C to +50° C)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 10,000 ft. (3000 m) at 40° C without derating
Storage Elevation
50,000 ft. (15.000 m) maximum
AGENCY
Safety
UL 1778, c-UL Listed; TUV, CE LVD compliant
RFI/EMI
FCC Part 15, Subpart B, Class A; EN5022 Class B; CE ECM compliant
IEEE 587 Category A; IEC 801-2, Level 4;
Immunity
IEC801-3, Level 3
IEC801-4, Level 4
IEC801-5, Level 3
DISCONTINUED
PRODUCT