UPSTATION GXT BATTERY RUN TIMES

(Discharge times are at 25° C ambient)

Internal Battery (minutes)

Load%

700MT

1000MT

1000RT

1000RTE

1500RT

2000RT

3000RT

10%

52

95

95

170

80

160

101

20%

38

46

46

128

40

83

51

30%

30

33

33

95

29

47

28

40%

23

26

26

70

21

34

20

50%

16

19

19

50

15

27

15

60%

12

14

14

37

11

21

12

70%

10

12

12

29

9

18

10

80%

8

9

9

24

7

15

8

90%

7

8

8

20

6

13

7

100%

5

7

7

18

5

11

6

Internal B 1 External Battery Cabinet (minutes)

Load%

700MT

1000MT

1000RT

1000RTE

1500RT

2000RT

3000RT

10%

N/A

N/A

479

554

408

343

273

20%

N/A

N/A

255

337

215

204

140

30%

N/A

N/A

150

212

125

133

78

40%

N/A

N/A

110

154

95

100

57

50%

N/A

N/A

85

116

75

77

44

60%

N/A

N/A

66

89

57

60

35

70%

N/A

N/A

56

73

48

50

30

80%

N/A

N/A

48

63

40

43

26

90%

N/A

N/A

41

53

35

36

22

100%

N/A

N/A

35

46

29

31

18

Internal B 2 External Battery Cabinets (minutes)

Load%

700MT

1000MT

1000RT

1000RTE

1500RT

2000RT

3000RT

10%

N/A

N/A

848

923

718

623

444

20%

N/A

N/A

425

507

365

345

236

30%

N/A

N/A

243

305

208

211

138

40%

N/A

N/A

196

240

164

156

100

50%

N/A

N/A

168

199

139

120

75

60%

N/A

N/A

133

156

112

94

59

70%

N/A

N/A

109

126

94

81

50

80%

N/A

N/A

89

104

78

70

43

90%

N/A

N/A

77

89

68

62

36

100%

N/A

N/A

66

77

58

54

31

DISCONTINUED 

PRODUCT

Summary of Contents for UPStation GXT1000MT-120

Page 1: ...POWER PROTECTION USER MANUAL English Espa ol R 700 3000 VA 120V UPStation GXT DISCONTINUED PRODUCT...

Page 2: ...POSAL OF BATTERIES IS REQUIRED REFER TO YOUR LOCAL CODES FOR DISPOSAL REQUIREMENTS POUR LE REMPLACEMENT UTILISER LE M ME NOMBRE ET TYPE DE BATTERIES L LIMINATION DES BATTERIES EST R GLE MENT E CONSULT...

Page 3: ...s section The UPStation GXT is a compact on line UPS An on line UPS continuously conditions and regulates its output voltage whether the utility power is present or not It supplies connected equipment...

Page 4: ...inewave input current achieves two objectives the utility power is used as efficiently as possible by the UPS and the amount of distortion reflected on the utility is reduced This results in cleaner p...

Page 5: ...the rack tower RT models For battery run times refer to the Typical Battery Discharge Curves DYNAMIC BYPASS The UPStation GXT provides an alternate path for utility power to the connected load in the...

Page 6: ...or 1500 VA units a 20 amp device for the 2000 VA unit and a 30 amp device for the 3000 VA unit The wall receptacle must be grounded 6 Locate the UPS indoors in a controlled environment where it cannot...

Page 7: ...ight side and remove the six rubber feet with the screw driver Remove and retain screws from the two front feet NOTE The rubber feet are not used for rack mount installations 6 Locate securing flanges...

Page 8: ...the connected load equipment The UPS is ready for normal operation OPTIONAL BATTERY CABINET S INSTALLATION Up to two optional battery cabinets may be connected to the UPS to provide additional run ti...

Page 9: ...e bead so that the ferrite bead s case snaps closed with the cable routed inside the ferrite bead s case SNMP Installation Attach the larger enclosed ferrite bead clamp to the network cable as shown i...

Page 10: ...oad Battery Level Indicators 700 1000 VA Mini Tower 1000 1500 VA Rack Tower 2000 VA Rack Tower 3000 VA Rack Tower 2 6 4 5 3 1 1 6 2 4 6 6 2 2 4 4 3 5 7 5 7 7 5 1 3 5 3 3 1 Output Receptacles 2 DB 9 In...

Page 11: ...result in loss of power to the output sockets and connected loads Perform all necessary shutdown procedures on connected loads before pressing this button twice Load Battery Level Indicators 4 Green 1...

Page 12: ...both switches up 110 VAC first switch up second down 120 VAC both switches down Factory Default 127 VAC first switch down second up NOTE Setting output voltage to 100 VAC will cause UPS unit to be de...

Page 13: ...indicators remain illuminated Refer to the Troubleshooting Guide For battery run times refer to the Typical Battery Discharge Curves To increase this time turn off non essential pieces of equipment s...

Page 14: ...Station GXT UPS has the capability of being monitored with stand alone computers network workstations network servers or UNIX hosts via the DB 9 female connector located on the rear of the UPS This ca...

Page 15: ...l internal Ethernet SNMP card Optional SiteNet SNMP Manager software is available to allow communication through several network management systems Contact your local Liebert representative dealer or...

Page 16: ...ated at the end of this section MINI TOWER BATTERY REPLACEMENT Battery connector Battery door screws FOR 700 1000 VA MINI TOWER MODELS 1 Gently lay the UPS on its right side 2 Loosen and remove the fi...

Page 17: ...ttery door Remove the door by pulling it forward and lifting it off Lay aside for reassembly 4 Pull battery assembly out approximately 50mm 2 in Gently pull the battery wiring out and disconnect the b...

Page 18: ...battery door Battery connector Large battery door Screw hidden by small battery door Small battery door Two front rubber feet Front bezel cover Rear View Aerial View w top cover removed Flange screws...

Page 19: ...N A 479 554 408 343 273 20 N A N A 255 337 215 204 140 30 N A N A 150 212 125 133 78 40 N A N A 110 154 95 100 57 50 N A N A 85 116 75 77 44 60 N A N A 66 89 57 60 35 70 N A N A 56 73 48 50 30 80 N A...

Page 20: ...s into position 5 Reconnect the input power lead to the UPS and the input power lead to the input AC supply 6 Restart the UPS The UPS is ready for normal operation NOTE For 2000 VA units press the res...

Page 21: ...ass due to output overload beep every half second A On bypass due to over temperature condition beep every 4 seconds B On bypass due to DC bus overvoltage beep every 4 seconds C On bypass due to contr...

Page 22: ...y and remove non essential loads Recalculate load VA and reduce number of loads connected to UPS Check load equipment for faults Fault and Bypass indicators and diagnostic LED A are illuminated UPS in...

Page 23: ...eptacles 4 NEMA 5 15R 4 NEMA 5 15R Voltage 100 110 120 127 switch selectable VAC 3 Frequency 50 Hz or 60Hz Waveform Sinewave Main Mode Overload 200 for 8 cycles 130 for 10 seconds with transfer to byp...

Page 24: ...NEMA 5 15R Voltage 100 110 120 127 switch selectable VAC 3 Frequency 50 Hz or 60Hz Waveform Sinewave Main Mode Overload 200 for 8 cycles 130 for 10 seconds with transfer to bypass BATTERY PARAMETERS T...

Page 25: ...6 ft detached w NEMA L5 30 plug OUTPUT AC PARAMETERS Output Receptacles 8 NEMA 5 15R 6 NEMA 5 15R 2 NEMA 5 20R 6 NEMA 5 15R 1 NEMA L5 30R Voltage 100 110 120 127 switch selectable VAC 3 Frequency 50 H...

Page 26: ...oltage x Batt Rating 2x3x12Vx7 0 or 7 2 AH 2x4x12Vx7 0 or 7 2 AH 1x8x12Vx7 0 or 7 2 AH Batt Mfg Part CSB GP1270F2 or Panasonic LC R127R2CH1 Back up Time See Typical Battery Discharge Curves Recharge T...

Page 27: ...ed modification alteration or repair use beyond rated capacity or improper installation maintenance application or use including without limitation use in a manner contrary to the accompanying instruc...

Page 28: ...to more than 1000 kVA Integrated systems that provide both environmental and power protection in a single flexible package Monitoring and control on site or remote from systems of any size or location...