![Liebert PowerSure PS250-60S User Manual Download Page 11](http://html1.mh-extra.com/html/liebert/powersure-ps250-60s/powersure-ps250-60s_user-manual_1907531011.webp)
11
SPECIFICATIONS
FCC ID #
N/A
BHKAF400T-60
BKAF600T-60
Model # / Stock #
PS250-60/PS250-60S
PS400-60 / PS400-60S
PS600-60 / PS600-60S
Model Rating
250 VA / 150 W
400 VA / 240 W
600 VA / 360 W
Dimensions
Unit (W x D x H)
3.51 x 10.18 x 6.79 in
(90 x 262 x 175 mm)
4.25 x 10.18 x 7.02 in
(109 x 262 x 186 mm)
4.84 x 10.18 x 8.15 in
(124 x 262 x 216 mm)
Shipping (W x D x H)
7.13 x 14.37 x 11.93 in
(181 x 365 x 303 mm)
8.35 x 18.98 x 11.5 in
(212 x 482 x 292 mm)
9.33 x 18.98 x 13.15 in
(237 x 482 x 334 mm)
Weight
Unit
8.8 lb. (4 kg)
12.5 lb. (5.7 kg)
19.8 lb. (9 kg)
Shipping
10.1 lb. (4.6 kg)
15.4 lb. (7 kg)
23.1 lb.(10.5 kg)
AC Parameters
Receptacles
(2) NEMA 5-15
(4) NEMA 5-15
(4) NEMA 5-15
Input Voltage Range
90-135 VAC, Single Phase, 2 Wire Plus Ground
Low Voltage Transfer Point
95 VAC, User Selectable to 90 or 100 VAC
High Voltage Transfer Point
135 VAC
135 VAC, User Selectable to 140 VAC
Input Frequency Range
47 – 53 Hz, 57 – 63 Hz
Output Voltage (on battery)
115 VAC, ± 5%
Output waveform (on battery)
Stepped Sine Wave
Max. Output Current at 120 V
2.1 A
3.3A
5 A
Output Frequency
50 or 60 Hz, ±5%
Max. Overload Capacity
115% of Power Rating
Battery
Type
Sealed, Valve-Regulated Lead Acid, Maintenance-Free
Qty x Voltage x Rating
1 x 12 V x 4.5 AH
1 x 12 V x 7 AH
2 x 12 V x 7 AH
Back-up Time
6 minutes at full load
Time from Low Battery Alarm
to Shutdown
Approximately 2 Minutes, depending on load
Recharge Time
8 – 10 Hours to 90% Capacity
Battery Life
3 – 5 Years Typical
Transfer Time to/from Inverter
2 – 6 msec. Typical
Agency Approvals
Safety
UL, C-UL Listed
EMI / RFI
Meets FCC Part 15, Subpart B, Class B
Surge Protection
Meets IEEE 587, Category A and B
MTBF (Bellcore Method)
100,000 Hours (Excluding Battery)
Environmental Standards
Operating Temperatures
50° F to +104° F (10° C to +40° C)
Storage Temperatures
0° F to +104° F (-20° C to +40° C)
(High Temperatures Reduce Battery Life)
Cooling
Convection
Audible Noise
Less than 40 dB @ 1 meter
Operating Elevation
Up to 9,900 ft. (3,000 m)
Storage Elevation