Specifications and Technical Data
54
Table 20
UPS terminal
Bypass input (single or dual input unit)
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Current
OCP
Device
Rating
Bolt Size
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
10
28
35
42
45
6M (1/4”)
54105
62204
15
42
53
63
70
6M (1/4”)
54106
62204
20
56
70
84
90
6M (1/4”)
54107
62204
30
83.3
104
125
125
6M (1/4”)
54152
62205
Rectifier Input (for Dual input unit only)
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Current
OCP
Device
Rating
Bolt Size
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
10
24.9
31
37
40
6M (1/4”)
54130
62204
15
37.3
47
56
60
6M (1/4”)
54106
62204
20
49.8
62
75
80
6M (1/4”)
54107
62204
30
74.7
93
112
125
6M (1/4”)
54152
62205
Output
Unit
Rating
Nominal
Output
Current
OCP
Current
OCP
Device
Rating
Bolt Size
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
10
28
35
35
6M (1/4”)
54130
62204
15
42
53
60
6M (1/4”)
54106
62204
20
56
70
70
6M (1/4”)
54106
62204
30
84
105
110
6M (1/4”)
54108
62205
Battery
Unit
Rating
Battery
Current
OCP
Current
OCP
Device
Rating
Bolt Size
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
10
37
37
40
6M (1/4”)
54130
62204
15
55
55
60
6M (1/4”)
54106
62204
20
73
73
80
8M (5/16”)
54142
62212
30
110
110
125
8M (5/16”)
54153
62212
Summary of Contents for NX 10kVA
Page 1: ...POWER AVAILABILITY NX INSTALLATION MANUAL 10 30kVA 208V 60Hz...
Page 54: ...Installation Drawings 48 Figure 27 Location of internal batteries Battery 417mm 687mm 186...
Page 64: ...Specifications and Technical Data 58 NOTES...
Page 65: ...Specifications and Technical Data 59...
Page 66: ...Specifications and Technical Data 60...
Page 67: ......