Electrical Connections
19
2.5
Switching the UPS from Normal to Maintenance Bypass
Follow the procedure below to transfer the load from the inverter output to the Maintenance Bypass
line of the UPS.
This procedure assumes that UPS is operating normally.
1. Press the INVERTER OFF button on the right side of the operator control panel for longer than
2 seconds.
The Inverter indicator will turn off and the alarm indicator (6) will turn amber and an audible
alarm will sound. The load will transfer to bypass and the inverter will shut off.
2. Open the UPS door to gain access to the main power switches, SW1 and CB1.
3. Turn the rotary switch to BYPASS position. The UPS Bypass Static Switch still supply power to
load.
4. Turn the rotary switch to TEST. The load is now on maintenance bypass.
5. Turn the rotary switch to MAINT.
6. Open rectifier switch CB1. All operator indicators and messages will turn off as the utility driven
internal power supplies decay. The unit will power down, but the load will continue to be supplied
by the manual Maintenance bypass.
2.6
Powering Down the UPS
To power down the UPS completely, follow the procedures in
2.5 - Switching the UPS from Nor-
.
To completely isolate the UPS from the AC supplies, the main external power input isolator (both iso-
lators, where separate supplies are provided for rectifier and bypass) should be opened (see
!
CAUTION
Before performing this operation, read the messages on the LCD to be sure that bypass supply
is regular and the inverter is synchronous with it. If those conditions are not present, there is
a risk of a short interruption in powering the load.
NOTE
Pressing the Alarm Silence Switch cancels the audible alarm, but leaves the warning message
displayed until the appropriate condition is rectified.
!
WARNING
Wait 5 minutes for the internal DC busbar capacitors to discharge.
!
WARNING
Even with the UPS in maintenance bypass and “Off,” portions of the unit are still energized.
Service must be performed only by qualified personnel.
!
CAUTION
The load equipment is not protected from normal supply aberrations when operating in the
maintenance bypass mode.
!
WARNING
To prevent injury to personnel, lockout or tagout the service supplies.
Summary of Contents for NX 10kVA
Page 1: ...POWER AVAILABILITY NX INSTALLATION MANUAL 10 30kVA 208V 60Hz...
Page 54: ...Installation Drawings 48 Figure 27 Location of internal batteries Battery 417mm 687mm 186...
Page 64: ...Specifications and Technical Data 58 NOTES...
Page 65: ...Specifications and Technical Data 59...
Page 66: ...Specifications and Technical Data 60...
Page 67: ......