Electrical Connections
15
2.3
Dry Contacts
The UPS provides input dry contacts and output dry contacts.
2.3.1 Input Dry Contacts
There are several input dry contacts at the X3 slot.
Figure 8
Input dry contacts
2.3.2 Maintenance Bypass Cabinet Interface
J26 and J30 are the MBC interface.
Table 1
Input dry contacts at X3
Position
Name
Description
J4.1
ENV
3
Battery Room Alarm (N.C.)
J4.2
BtG
Battery Ground Fault Detection (N.C.)
J4.3
GEN
1,2
Generator Join Detection (N.O.)
J4.4
+12V
+12V Power
1 - Must be configured by configuration software before becoming active.
2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current (0-100%).
3 - Activating this feature turns the battery charger off.
Table 2
Maintenance bypass cabinet interface
Position
Name
Description
J26.1
T_IT
1
Input transformer over temperature (N.C.)
J26.2
AUX_I
Reserved
J26.3
+12V
+12V Power
J26.4
GND
Power Ground
J30.1
FUSE
Reserved
J30.2
F_FAN
Fan Fail Alarm (N.C.)
J30.3
T_OT
1
Output Transformer Overtemperature (N.C.)
J30.4
AUX_O
Reserved
1 - Must be configured by software before becoming active
NOTE
All auxiliary cables of terminal must be double insulated. Wire should be 16-20AWG stranded.
Summary of Contents for NX 10kVA
Page 1: ...POWER AVAILABILITY NX INSTALLATION MANUAL 10 30kVA 208V 60Hz...
Page 54: ...Installation Drawings 48 Figure 27 Location of internal batteries Battery 417mm 687mm 186...
Page 64: ...Specifications and Technical Data 58 NOTES...
Page 65: ...Specifications and Technical Data 59...
Page 66: ...Specifications and Technical Data 60...
Page 67: ......