Specifications
32
Table 11
Environmental data
Environmental Parameter
Value
Operating Temperature, °C (°F)
0 to 40 (32 to 104) refer to
Table 13 - Operating temperature parameters
Storage Temperature, °C (°F)
15 to 50 (5 to 122)
Relative Humidity
0-95% non-condensing
Operating Elevation
Up to 1000m (3281 ft) at 30°C (86°F) without derating
Audible Noise
<55 dBA, at 1 meter (39") from the rear; <50 dBA, at 1 meter (39") from the
front or sides
Table 12
Agency/safetycompliance
EMI/EMC/C-Tick EMC
IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6)
ESD
EN61000-4-2, Level 4, Criteria A
Radiated Susceptibility
EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient
EN61000-4-4, Level 4, Criteria A
Surge Immunity
EN61000-4-5, Level 3, Criteria A
Transportation
ISTA Procedure 1A
Table 13
Operating temperature parameters
Ambient Temperature, °C (°F)
pf @30°C ±3°C
(pf @ 86°F ±5.4°F)
pf @40°C ±3°C
(pf @ 104°F ±5.4°F)
10000T230
0.9pf
0.8pf
Table 14
Typical battery run times, minutes at 25°C (77°F), 100% resistive load
Number of Batteries,
Battery Cabinets
Load %
30%
40%
50%
60%
70%
80%
90%
100%
Internal Battery
21
14.5
10.75
8.5
6.5
5
3.75
3
Internal Battery
+ 1 External Battery Cabinet
43
33
26
21
17
13
11.5
10
Internal Battery
+ 2 External Battery Cabinets
74.5
55
41.5
33
28.5
24
21
18
Internal Battery
+ 3 External Battery Cabinets
95
70
58
48
40
34
29.5
26
Internal Battery
+ 4 External Battery Cabinets
99.5
96
72.5
62
51
45
40
34