background image

Communication

27

6.2.2 Battery Mode Shutdown

Battery Mode Shutdown permits shutting down the UPS by turning Off the rectifier, inverter and 

static switch so that there is no power to the load when the UPS is On Battery. The auxiliary power 

for the UPS will still be active.
Battery Mode Shutdown can be performed locally or remotely:

• Local Battery Mode shutdown can be performed by shorting the pins in Set 4.
• Remote Battery Mode Shutdown can be performed using a switch connected to the pins in Set 4 

and mounted at remote location.

Activation of the Battery Mode Shutdown will be logged as an event in the event history log.

6.2.3 On Battery

On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power 

from the battery this dry contact will be closed. 

6.2.4 Low Battery

Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power 

from the battery and has reached the Low Battery Warning time selected in the configuration pro-

gram, this dry contact will be closed.

6.3

UPS IntelliSlot Communication Cards

The Liebert IntelliSlot port accepts three optional cards:

• Liebert IntelliSlot SNMP Card
• Liebert IntelliSlot Relay Card
• Liebert IntelliSlot 485 Card.

The Liebert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the net-

work.
The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications 

and delivers support for built-in shutdown for AS/400 systems.
The Liebert IntelliSlot 485 Card is used to connect the UPS and computer system. 
Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink, the UPS 

or any additional ancillary product for the Liebert GXT3. These instructions are available at

multilink.liebert.com

NOTE

Remote Power Off will be performed by NO contact.
The current limited source (+12VDC, 50mA) will be available from UPS.
The connection to the Liebert GXT3 for remote connection will be via terminal block connector.
Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes 

and laws.
This signal must last for 1.5 seconds or longer.
A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute 

shutdown timer. This timer cannot be stopped once triggered. If the utility power returns 

during this countdown, the Liebert GXT3 will still shut down and must remain shut down for 

10 seconds. Whether the UPS turns back On when the power is restored depends on the 

auto-restart setting.

NOTE

The rated values for the dry contacts are:
• Rated Voltage: 5V
• Working Voltage Range: 4.5-10V
• Rated Current: 30ma

Summary of Contents for GXT3-10000T230

Page 1: ...AC Power For Business Critical Continuity Liebert GXT3 10000T230 User Manual 10kVA 50 60 Hz 230V...

Page 2: ......

Page 3: ...2 10 Clearance 7 2 11 Repacking the UPS 7 3 0 INSTALLATION 8 3 1 Electrical preparations 8 3 2 Current Table and Suggested Cable Sizes 8 3 3 Neutral Connection 9 3 4 External Protection and Isolating...

Page 4: ...unctional Test 21 4 9 Remote Emergency Power Off 22 4 10 Self Tests 22 4 10 1 Lamp Test 22 4 10 2 Battery Test 22 5 0 MAINTENANCE 23 5 1 Testing Replacing and Disposing of Batteries 23 5 2 Easy Batter...

Page 5: ...net 13 Figure 12 Overview of UPS tower 15 Figure 13 Control panel 16 Figure 14 System block menu structure 17 Figure 15 REPO connections 22 Figure 16 Removing front panel and unlocking battery trays 2...

Page 6: ...iv...

Page 7: ...e connected These battery extensions may be connected only to the compatible basic UPS unit WARNING Opening or removing the cover may expose you to lethal voltages within this unit even when it is app...

Page 8: ...cted or disconnected during a thunderstorm Remote Emergency Power Off REPO input is located on the rear of the unit see 3 8 Ter minal Blocks for UPS When this connection is open the logic circuit will...

Page 9: ...formity If required the EU Declaration of Conformity may be requested from Liebert NOTICE TO EUROPEAN UNION CUSTOMERS DISPOSAL OF OLD APPLIANCES This product has been supplied from an environmentally...

Page 10: ...c equipment operates best from sinewave power For ease of use the Liebert GXT3 10000T230 features an LCD display for comprehensive user indica tions and programmable controls It also provides self dia...

Page 11: ...0 For technical data about external battery cabinets see Table 10 UPS specifications For connection notices see Table 2 Connection data 1 2 2 Optional Interfaces Refer to 6 0 Communication for details...

Page 12: ...d damaging the UPS Do not dispose of the packing material The original packaging material should be used if the UPS needs to be repackaged such as for shipping Check all packaging to ensure that no it...

Page 13: ...ed will support the unit s weight see Table 10 for the unit s weight 2 9 Inventory List The Liebert GXT3 10000T230 comes with CD containing Liebert MultiLink Shutdown Software Configuration Software U...

Page 14: ...bles WARNING Installation may be carried out only by qualified technicians conforming to applicable safety standards Electric shock hazard Even when the unit is disconnected from the mains hazardous v...

Page 15: ...ed for the protection of both the cables and the equipment WARNING The following label must be displayed on all switching devices installed in the same electrical system as the UPS even when they are...

Page 16: ...ove the protective panel on the rear of the UPS to access the external electrical connections see figure below Once the cables have been connected they must be passed through the cable clamps that wil...

Page 17: ...t share a common conduit with input circuits or any other wiring The utility may be derived from a single phase or three phase source Figure 6 Input and output connections with single source single ph...

Page 18: ...Figure 3 5 If the reserve input is to be supplied separately connect reserve line to the Mains 2 terminals If the UPS is supplied by a common mains connect the supplied jumper in the accessory kit ma...

Page 19: ...d battery a compensating current may occur during connection Figure 11 Liebert GXT3 10000T230 with External Battery Cabinet 3 11 Connecting an External Battery Extension The unit checks the battery vo...

Page 20: ...four months Since new batteries often do not provide full capacity after the initial charge it may be necessary to carry out a number of discharge recharge cycles before optimum performance is reache...

Page 21: ...booster inverter and charger Internal electronic bypass 2 input breakers Maintenance bypass breaker TVSS filter Integrated battery expandable Figure 12 Overview of UPS tower L2 L3 at 10kVA device only...

Page 22: ...u Press Enter to choose an entry Table 4 Lighted LEDs LED Indicator LED Color Description UPS ON Green UPS is online and operating normally BYPASS Amber Load is supplied by the mains via automatic byp...

Page 23: ...Menu Setup Menu Status Menu Parallel Menu Language Tag Number UPS ID No DC Start Test Intvl Batt Pack Audible Alarm Output Volt No of Unit Control Menu Contrast Batt Test Alarm Ctrl UPS ON OFF Test Re...

Page 24: ...ENU SysOutI A SysOutV V SysOutF Hz SysOutW W SysOutVA VA SysLoadPer SETUP MENU Setting item Setting level 1 Audible Alarm Disable Enable Output Volt 220V 230V 240V Batt Pack 1 4 Test intvl DC Start Di...

Page 25: ...is window All fault displays include The nature of the event The time of the event The fault indicators are Table 6 Warning indicators Warning Cause Corrective Steps 1 No Redundancy 2 InvASynFault 3 P...

Page 26: ...y external switches connecting the load if present 7 Press the Menu button select Control and press OK 8 Select Turn UPS ON OFF and press OK The LCD will display Turn ON 9 Press OK to switch On the in...

Page 27: ...Before beginning ensure that the batteries are fully charged Simulate a mains failure by interrupting the mains supply to the UPS You can do this by switching Off the input power circuit breaker on t...

Page 28: ...s mode A system confirmation beep will sound 4 10 2 Battery Test 1 Press the Menu button 2 Select Control and press OK 3 Select BATT TEST and press OK A system confirmation beep will sound and the loa...

Page 29: ...al regulations and laws Exhausted accumulator batteries are classified as harmful toxic waste and as such the law demands that they be disposed of by an authorized recycling centre The Liebert power p...

Page 30: ...Open the battery tray DC connectors as shown 2 Remove the battery trays from the cabinet 3 Replace the old batteries with a new set Replacement batteries must be the same type installed at the factory...

Page 31: ...rcuit breaker of the UPS Then remove the UPS connections in the opposite sequence to that described in 3 0 Instal lation Record the battery charging date in the vicinity of the UPS for example on its...

Page 32: ...Any Mode Shutdown can be performed using a switch connected to the pins in Set 3 and mounted at a remote location Activation of the Any Mode Shutdown will be logged as an event in the event history l...

Page 33: ...d The Liebert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the net work The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom wired applicati...

Page 34: ...e on four comput ers and coordinate shutdown in the event of a power failure The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom wired applications and delivers support fo...

Page 35: ...t intervals No mains voltage present UPS operation control panel UPS on LED does not illuminate when mains voltage present audible alarm active at intervals Input fuse defective or input circuit break...

Page 36: ...y nominal voltage VDC 240 Battery charger input voltage range VDC 100 276 Output voltage V Multi stage charging method Charging time to 90 capacity in inverter mode hr 3 Charger output current ADCaver...

Page 37: ...ttery number pcs 40 80 Dimensions W x D x H mm in 300 x 675 x 800 11 8 x 26 6 x 31 5 Color Black Weight with integrated batteries kg lb 162 357 Performance EN 62040 3 Dynamic characteristics VFI S S 1...

Page 38: ...Level 3 Criteria A Electrical Fast Transient EN61000 4 4 Level 4 Criteria A Surge Immunity EN61000 4 5 Level 3 Criteria A Transportation ISTA Procedure 1A Table 13 Operating temperature parameters Am...

Page 39: ......

Page 40: ...ive owners Technical Support Service Web Site www liebert com Monitoring liebert monitoring emerson com 800 222 5877 Outside North America 00800 1155 4499 Single Phase UPS Server Cabinets liebert upst...

Reviews: