Leakage Current 

ELECTROMAGNETIC COMPATIBILITY

—The Liebert

®

 GXT3

 complies with the limits for a 

Class A Digital Device, Pursuant to Part 15 of FCC rules. Operation is subject to the following 

conditions:

• This device may not cause harmful interference
• This device must accept any interference received, including interference that may cause 

undesired operation. Operating this device in a residential area is likely to cause harmful 

interference that users must correct at their own expense.

The Liebert GXT3 series complies with the requirements of EMC Directive 2004/108/EC and the 

published technical standards. Continued compliance requires installation in accordance with these 

instructions and use of accessories approved by Emerson.

NOTICE

Operating the Liebert GXT3 in residential areas may cause radio interference that the user 

must to correct at his own expense.

Information for the Protection of the Environment

UPS SERVICING

—This UPS makes use of components dangerous for the environment (electronic 

cards, electronic components). The components removed must be taken to specialized collection and 

disposal centers.

!

WARNING

Connect the ground (earth) safety conductor before connecting any other cables.

Summary of Contents for GXT3-10000T220

Page 1: ...More user manuals on ManualsBase com AC Power For Business Critical Continuity Liebert GXT3 10000T220 User Manual 10kVA 50 60 Hz 120 208 220V...

Page 2: ...More user manuals on ManualsBase com...

Page 3: ...nd Isolating Devices 8 3 4 External Electrical Connections 9 3 5 Connecting Utility and Load 9 3 6 Terminal Blocks for UPS 9 3 6 1 Input and Output Connection Requirements 10 3 7 Connecting Power Cabl...

Page 4: ...packing 6 Figure 4 Side view 9 Figure 5 Single source input supply input and output connections 9 Figure 6 Dual source input supply input and output connections 10 Figure 7 Hardwire terminals 10 Figur...

Page 5: ...do not electrically isolate internal parts Under no circumstances attempt to gain access internally due to the risk of electric shock or burn Do not continue to use the UPS if the front panel indicat...

Page 6: ...3 0 Installation In emergencies e g damaged case controls or power cables penetration of liquids or for eign matter switch off the device and contact the appropriate customer service representa tive D...

Page 7: ...nse The Liebert GXT3 series complies with the requirements of EMC Directive 2004 108 EC and the published technical standards Continued compliance requires installation in accordance with these instru...

Page 8: ...onic equipment operates best from sinewave power The liquid crystal display is used for controlling operation of the UPS as well as monitoring its status condition alarm status and history For ease of...

Page 9: ...wer UPS with Integrated Battery Liebert GXT3 10000T220 10000VA 90000W Battery Cabinet Liebert GXT3 240TBATTCE Control Panel Liquid Crystal Display Push Button Controls Ventilation Louvers Bypass Circu...

Page 10: ...00T220 near its installation site 2 Unlock all the snaps securing the shipping case to the shipping pallet 3 Lift the shipping case off the UPS 4 Remove the EPE packing cushions from around the Lieber...

Page 11: ...rea The area where the Liebert GXT3 10000T220 is to be placed must have sufficient space for installation procedures and for routine maintenance The UPS is narrow enough to pass through standard doorw...

Page 12: ...osition output power is available immediately upon application of AC input Table 2 Connection data Description Units Liebert GXT3 10000T220 Connector size AWG mm2 6 10 Max input current Arms 56 Input...

Page 13: ...0T220 is supplied by single phase utility connect the live phase to input L1 3 6 Terminal Blocks for UPS Figure 5 Single source input supply input and output connections WARNING Before removing electr...

Page 14: ...e in the building grounding electrode system If the grounding electrode conductor must be protected non metallic conduit is recommended If metal conduit must be used bond both ends of the conduit to t...

Page 15: ...iebert GXT3 10000T220 is supplied with each battery cabinet Open the breaker before making battery cable connections Plug one end of this cable into the UPS and the other end into the battery cabinet...

Page 16: ...with separate breakers utility and bypass rectifier booster inverter and charger electronic bypass 2 position Maintenance Bypass Breaker UPS and BYPASS integrated battery Figure 9 System block diagram...

Page 17: ...2 1 Controls and Messages Lighted LEDs UPS ON UPS is in normal online operation BYPASS Load is supplied by the utility via automatic bypass BATTERY Load is supported by the battery FAULT A problem has...

Page 18: ...Main Setup Control Contrast Set Battery Test Alarm Control Turn UPS On Off Status Log About Version Language Tag Number UPS Address DC Start Battery Test Interval Battery Pack Audible Alarm Output Vol...

Page 19: ...tup Menu Setting item Setting level 1 Audible alarm Disable Enable Output voltage 208 220 230 240V Battery pack 1 3 1 Battery Test interval DC start Disable Enable Tag Number 00000 99999 Language Engl...

Page 20: ...ry Test Battery Test Report Contrast Darker Lighter Battery Test Report Test in progress Test to Low Battery Test OK Cancel Battery test Test fail Battery Test report Test stop by user Test unknown 1...

Page 21: ...m of 4 fault events may be displayed in this window All fault displays include the nature of the fault event and the time it occurred the time is relative to the UPS operating time Display faults The...

Page 22: ...ontrol and press the Enter key 2 Select Turn UPS On Off and press the Enter key The LCD displays Turn UPS to BYPASS 3 Press the Enter key to switch off the inverter 4 Open any external circuit breaker...

Page 23: ...to Bypass mode 5 A single acoustic signal confirms the operation 6 Select Turn UPS On Off and press OK to place the UPS back in Normal Mode operation The UPS performs the test during Start up 4 8 2 Ba...

Page 24: ...ient temperature of 25 C but is also dependent on the frequency and duration of utility failures The BATTERY TEST see 4 8 2 Battery Test should be run periodically 6 to 12 months to ascertain the gene...

Page 25: ...Set 3 Remote Any Mode Shutdown can be performed using a switch connected to the pins in Set 3 and mounted at a remote location Activation of the Any Mode Shutdown will be logged as an event in the ev...

Page 26: ...rd Liebert IntelliSlot 485 Card The Liebert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the network The Liebert IntelliSlot Relay Card provides dry contact relay outpu...

Page 27: ...MultiLink software on four computers and coordinate shutdown in the event of a power failure The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom wired applications and de...

Page 28: ...mains voltage present Have utility mains inspected by a qualified technician UPS on LED does not illuminate when utility mains voltage present acoustic alarm active at intervals Input fuse defective o...

Page 29: ...0 seconds 105 130 1 minute Battery Parameters Type Valve regulated non spillable lead acid Quantity x V 20 x 12V Battery Mfr Part CSB HR1234R or Panasonic UP RW1245 Backup Time See Table 11 Recharge T...

Page 30: ...able 11 Environmental Operating Temp F C 32 to 80 0 to 27 Storage Temp 5 to 104 15 to 40 Transportation Temp F C 5 to 122 15 to 50 Relative Humidity 0 95 non condensing Operating Elevation Up to 3281...

Page 31: ...RATION To register for warranty protection Visit the Quick Links section of Liebert s Web site at http www liebert com Click on Product Warranty Registration and fill in the form If you have any quest...

Page 32: ...change without notice Liebert is a registered trademark of Liebert Corporation All names referred to are trademarks or registered trademarks of their respective owners Technical Support Service Web Si...