Liebert CBH 017 Service Manual Download Page 8

5

4.2 --- First start---up

(or after a long stop)

Operate as follows:

1)

At least 8 hours before the start---up, power the crank-

case heaters by setting the main isolator switch ON.

Make sure the auxiliary circuit has been powered and

check the operation (a fault due to an incorrect proce-

dure will invalidate the compressor guarantee).

2) Open the valves of the refrigeration circuit that had been

closed before the initial check.

3) Check the machinery supplying the thermal load connected

with the unit and start the system pump(s).

4) MAKE SURE THE COMPRESSOR OIL HAS BEEN HEATED

FOR AT LEAST 8 HOURS; start the unit only then.

5) Make sure the fans rotate in the correct direction (anticlock-

wise): check the electrical connections, if necessary.

6) Make sure the pumps rotate in the correct direction.

7)

During the unit start---up an inlet water temperature

higher than 20

û

C is allowed. Under standard operating

conditions check that the limits indicated in paragraph

2.1 are not exceeded.

8) Check the correct operation of the control and safety de-

vices.

9) Check the outlet temperature of the chilled water (check if

the set---point set on the controller is reached).

10) Check the oil level in both compressors.

11) With the compressors at full load, check there are no

bubbles visible in the frefrigerant sight glass. If there are any,

charge the unit according to par. 5.

4.3 --- Starting and stopping

ALWAYS ENSURE THAT THE COMPRESSOR OIL HAS BEEN

PREHEATED.

FOR BRIEF STOPPAGES MAINTAIN THE SUPPLY TO THE

CRANKCASE HEATER.

S

Start the unit setting the Microprocessor switch

ON.

S

Stop the unit setting the Microprocessor switch

OFF

.

S

In case of long stops, turn the machine off using the Micro-

processor switch OFF.

In this case the compressor crankcase heaters remain pow-

ered.

S

For seasonal shutdown of the unit operate the main switch

located on the main electrical power supply. This will discon-

nect the compressor crankcase heaters.

4.4 --- Chillers serving special plants

The units are capable of cooling a water---glycol mixture to tem-

peratures close to 0

û

C without the need for significant modifica-

tions. In the case of modification, the set values of the safety and

control components must also be changed. This can be carried

out in the factory (at the time of testing) or at the time of installa-

tion, only by qualified and authorised personnel.

4.5 --- Freecooling

The “freecooling” is a system of pre---cooling and/or cooling the

water/glycol mixture using ambient air when the latter isat a tem-

perature below the return mixture temperature. If the outside

temperature is sufficiently low to dissipate the entire heat load,

the refrigeration compressors automatically switch off, and the

mixture’s temperature is controlled by the fan speed adjust-

ment.

If the mixture temperature is too high for freecooling, the com-

pressors will operate as long as necessary to ensure the correct

water/glycol mixture temperature.

4.6 --- Microprocessor control

Consult the ”Microface and Hiromatic” Service Manual.

5 --- Refrigerant and Oil Charge

All work on pipes or components of the refrigerating circuit un-

der pressure must be exclusively carried out by qualified staff,

competent in such works.

5.1 --- Refrigerant charge

WHILST REPAIRING THE REFRIGERATING CIRCUIT RE-

COVER ALL THE REFRIGERANT IN A CONTAINER: DO NOT

ALLOW IT TO ESCAPE. NEVER USE THE COMPRESSOR

FOR THE SYSTEM VACUUM (THIS INVALIDATES THE

WARRANTY).

S

The unit is delivered charged according to the Tab. 5.

Warning for the refrigerant charge:

S

Ensure there are no refrigerant leaks.

S

Check the refrigerant type in the refrigeration circuit: a unit

originally charged by the manufacturer with R407C cannot

be charged with R22 and vice versa; possibly apply to the

Technical Support Department.

S

Charge with the compressor in operation, connecting the

cylinder with the charge connector after the thermostatic ex-

pansion valve.

Flush the connection pipe between the cylinder and the

charging point; tighten the seal joint and then start charging

the unit. It is imperative that the cylinder is weighed both be-

fore and after the operation.

S

For the units with R407C the refrigerant charge must be

made exclusively with liquid refrigerant.

S

Charge the unit until the bubbles in the sight glass have dis-

appeared and the working conditions of the entire refrigera-

tion circuit have returned to normal (sub---cooling and su-

perheating within the limits indicated below).

S

Measure the superheating as follows:

1) Detect the temperature on the suction line, close to the

bulb of the thermostatic expansion valve, using a contact

thermometer.

2) Connect a pressure gauge (by max. a 30---cm pipe) with

the Schraeder connection and read the corresponding

saturated evaporating temperature.

3) The superheating is the difference between the two

readings.

4) For the units with R407C refer to the pressure gauge

scale indicated with the initials D.P. (Dew Point)

S

Verify that the superheating is 5

û

C --- 8

û

C.

S

Measure the sub---cooling as follows:

1) Detect the temperature on the liquid line using a contact

thermometer.

2) Connect a pressure gauge (by max. a 30---cm pipe) with

the Schraeder connection on the liquid line and read the

corresponding saturated condensing temperature.

3) The sub---cooling is the difference between the tworead-

ings.

4) For the units with R407C refer to the pressure gauge

scale indicated with the initials B.P. (Bubble Point)

S

Verify that at the condenser outlet, sub---cooling is 3

û

C ---

5

û

C.

IT IS IMPORTANT TO CARRY OUT CHARGING CORRECTLY.

An excess of refrigerant causes an increase in sub---cooling and

consequent operating difficulties in the hot season; a shortage

of charge generates an increase in superheating and possible

compressor stoppages. Whenever work is carried out on the

unit, ensure afterwards that the working conditions are correct,

checking sub---cooling and superheating.

5.2 --- Oil charge

Contact the Technical Support Department for the specifications

of the oil to be used for topping up; the oil changes according to

the type of used refrigerant.
NEVER MIX DIFFERENT OILS TOGETHER. CLEAN THE PIP-

ING COMPLETELY BEFORE CHANGING THE TYPE OF OIL

USED.

Summary of Contents for CBH 017

Page 1: ...HIGH PERFORMANCE AIR COOLED CHILLER S 017 032 SERVICE MANUAL English Cod 272902 Rev 25 05 2005 Issued by T D Service...

Page 2: ......

Page 3: ...read the identification labels affixed to the outside and inside of the unit IMPORTANT This manual may be subject to modification for complete and up to date information the user should always consult...

Page 4: ...of the liquid line are the charging valves filters dryers solenoid valve shut off valve moisture indicator and thermostatic expansion valve The hydraulic circuit with max working pressure 5 bar is mad...

Page 5: ...ets of the pump and water chiller Can be supplied as an optional accessory Not fitted 8 Install at the highest points in the circuit apparatus which allows the bleeding of air and possibly the filling...

Page 6: ...ing a diameter ofat leastthat of the valve outlet without burdening the valvebody Conveythe discharge to areas where the jet cannot harm people and the surrounding environment Fig a Ideal chilled wate...

Page 7: ...mpressors are equipped with anelectronic protectionde vice blocking their start if the phase sequence is not correct or stopping their operationif athermal relayintervenes Thisdevice is essential for...

Page 8: ...face and Hiromatic Service Manual 5 Refrigerant and Oil Charge All work on pipes or components of the refrigerating circuit un der pressure must be exclusively carried out by qualified staff competent...

Page 9: ...dicated below MODELS SETTINGS SAFETY VALVE CBH CLH CQH 017 020 023 025 028 SBH SLH 017 020 023 025 028 SQH 017 020 023 025 29 bar high pressure side 6 1 Setting thermostatic expansion valve THIS OPERA...

Page 10: ...es operate correctly S Check the correct operation of the thermostatic valve superheating between 5 C 8 C S Check that the oil level indicated by the compressor sight glass is higher than the min valu...

Page 11: ...dition of low condensing temperature below the safety threshold leads the Microface mi croprocessor control to disable the heat recovery protecting the system from any possible malfunctioning Fig e Re...

Page 12: ...recovery conditions water inlet outlet 40 45 C Tab 3 Total heat recovery 100 Model 017 020 023 025 028 030 032 Heating capacity kW 212 238 290 320 357 412 453 Water flow l s 10 13 11 37 13 86 15 29 1...

Page 13: ...Refrigerant charge each circuit kg 23 0 23 6 32 8 32 8 39 4 42 0 Oil charge each circuit lt 12 4 14 2 16 0 16 0 16 0 16 0 Models SBH 017 020 023 025 028 030 032 Refrigerant charge each circuit kg 19 5...

Page 14: ...1 107 0 178 72 209 299 547 119 9 198 72 Fan power input Fan nominal current Fan max current kW A A 0 95 2 2 2 4 Std head pressure pump model Opt Std head pressure pump motor max power Std head pressur...

Page 15: ...current High head pressure pump model Opt High head pressure pump motor max power High head pressure pump max current kW A kW A 65 260 2 4 0 8 00 65 340 2 5 5 11 20 65 340 2 5 5 11 20 65 410 2 7 5 15...

Page 16: ...Low pressure switch Barg Barg Barg 26 0 29 0 2 8 1 With nominal air flow water flow outlet at 7 C full load SBH R 407C Size 017 020 023 025 028 030 032 Working Range Max outdoor air temperature 2 C 4...

Page 17: ...3 63 63 Pump weight kg 74 3 149 2 89 2 178 9 2 pole pump set standard head pressure data refers to each pump Models 017 020 023 025 028 030 032 SBH 30 glycol water mixture flow m3 h 31 91 34 52 43 66...

Page 18: ...view 1000 1000 1500 1500 Extraordinary maintenance area Notes Minimum distance between 2 units from condensing coil side 3 m Do not obstruct the air exiting the fans for a minimum distance of 2 5 m AI...

Page 19: ...locking pins and split pins as shown above The capacity of the lifting gear must be adequate to lift the load in question Check the weight of the unit the capacity of the lifting gear and ropes and t...

Page 20: ...1 319 400 400 448 467 485 291 319 400 400 448 467 485 CQH 017 020 023 025 028 030 193 196 225 225 248 256 193 196 225 225 248 256 258 279 346 346 363 376 258 279 346 346 363 376 251 259 290 290 305 32...

Page 21: ...77 392 360 377 392 360 377 392 462 467 479 462 467 479 382 390 418 382 390 418 382 390 418 030 5 449 5 449 3 392 3 392 3 392 6 479 6 479 390 418 390 418 390 418 SBH 017 020 472 469 472 469 286 304 286...

Page 22: ...16 5 160 83 190 5 Rubber supports 1000 liters tank Unit Configuration Support kit code Single support code Kit support pieces CBH CLH CQH 017 020 023 025 028 030 032 Without tank 485625 270326 8 SBH S...

Page 23: ...like part G PARTIAL HEAT RECOVERY INLET TOTAL HEAT RECOVERY OUTLET SUPPLY CABLE INLET PREPUNCH 2 x 67 30 W Z CBH CLH CQH 017 030 SBH SLH SQH 017 030 M REAR VIEW from H DX LATERAL VIEW TOP VIEW FRONT...

Page 24: ...lled water connection Y OUTLET DN80 3 88 9 mm OUTLET DN80 3 88 9 mm OUTLET DN80 3 88 9 mm REMOVABLE PANEL SUPPLY CABLE INLET PREPUNCH 2 x 67 30 M REAR VIEW from H DX LATERAL VIEW TOP VIEW FRONT VIEW A...

Page 25: ...62 1300 378 M REMOVABLE PANEL F PREPUNCHED 110 for inlet outlet pipes connections TOP VIEW FRONT VIEW SX LATERAL VIEW DX LATERAL VIEW PART G N 229 L 120mm DN80 3 88 9mm N VIEW TANK CONNECTING PIPE V V...

Page 26: ...0 13 13 14 14 19 19 2 2 5 Refrigerant components Pos Item Description Pos Item Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Compressor High pressure switch HP Low pressure switch LP Crankcase heater H...

Page 27: ...ATER OUTLET VICTAULIC COUPLING DN 80 3 88 9 mm HEAT RECOVERY WATER OUTLET VICTAULIC COUPLING OPT DN 80 3 88 9 mm Refrigerant components Pos Item Description Pos Item Description 1 2 3 4 5 6 7 8 9 10 1...

Page 28: ...TION DN 80 3 88 9 mm T F 10 5 7 5 4 9 13 4 5 5 6 4 9 13 10 3 8 14 11 12 1 2 CHILLED WATER OUTLET VICTAULIC CONNECTION DN 80 3 88 9 mm WATER TANK OUTLET VICTAULIC CONNECTION DN 80 3 88 9 mm 15 15 p 16...

Page 29: ...IC CONNECTION DN 80 3 88 9 mm CHILLED WATER INLET VICTAULIC CONNECTION DN 80 3 88 9 mm CHILLED WATER OUTLET VICTAULIC CONNECTION DN 80 3 88 9 mm 15 p 21 15 Hydraulic components Item Description Item D...

Page 30: ......

Page 31: ...d Le Fabricant d clare que ce produit est conforme aux directives Europ ennes El Fabricante declara que este producto es conforme a las directivas Europeas O Fabricante declara que este produto est em...

Page 32: ...of EMERSON Tel 39 049 9719111 Telefax 39 049 5841257 Internet www liebert hiross com Printed in Italy by Liebert HIROSS S p A Issued by T D Service Since the Liebert HIROSS Company has a policy of co...

Reviews: