Liebert CBH 017 Service Manual Download Page 5

2

2.2 --- Sound pressure levels

The Tab. 4 shows the noise data for the units in standard config-

uration (without pumps), operating continuously and measured

according to the ISO 3744 norm, in free field conditions.

The highestnoise levelsare detected on the condenser coilside.
Note:

Avoid positioning in areas with possible reverberation of the

sound waves, which can adversely effect the noise levels.

2.3 --- Transport

S

Handle the unit by lifting it with a crane from above;

S

The lifting holes are positioned in the frame’s base (when lift-

ing, use spreader bars to protect the sides, see Fig. 2).

Note:

Place the lifting tubes in the holes in the base indicated by ”LIFT

HERE”. Lock the ends of the tubes with the locking pins and

splits pins as shown in Fig. 2.

The capacity of the lifting gear must be adequate to lift the load

in question. Check the weight of the units, the capacity of the lift-

ing gear and ropes and the condition and suitability of the afore-

mentioned equipment.

2.4 --- Foundations

S

The unit must be placed on a level surface which will support

its weight.

S

If necessary, position the unit on suitable anti---vibration sup-

ports that can be supplied as an option (in rubber or spring---

type). Refer to the manual ”Installation of the spring anti---

vibration supports” for their correct positioning.

S

When positioned, level the unit.

Note:

For weight distribution see Fig. 3.
Note:

The weights and their distribution refer to standard units without

options; if the pump assembly, or other options are installed on

the machine, add the weights of the installed accessories to

those of the standard units (see Tab. 8).

2.5 --- Service area

S

In order to allow free air flow and maintenance of the unit, a

minimum area must be left free of obstructions around the

unit (see Fig. 1).

S

The hot air expelled by the fans mustbe allowed to rise unim-

peded by obstacles for a minimum height of 2.5 m.

S

Avoid recirculation of hot air between the suction and dis-

charge, otherwise the unit performance may be impaired or

the standard operation can be interrupted.

3 --- Installation

3.1 --- Hydraulic connections

3.1.1 -- Hydraulic circuit construction (Fig. a)

The piping must be connected to the chiller. Construct a chilled

water circuit as described below, see Fig. a:

1) Place shut---off valves within the circuit to allow servicing;

2) Install a pump system suitable for the flow rate required at

a pressure head equal to the sum of all the pressure drops

(see project data).

Matrix S chillers can be equipped, upon request, with

pumps having performance as indicated in Tab. 8;

3) Install manometers at the chiller inlet/outlet;

4) Install thermometers at the chiller inlet/outlet;

5) Connect the pipes to the chiller by flexible joints to avoid

transmitting vibrations and to balance the thermal expan-

sion; proceed in the same way even if the pump set is out-

side the chiller;

6) It is useful to include a water pressure switch to give an early

warning of low water pressure;

7) Place a mesh filter at the inlets of the pump and water chiller

(Can be supplied as an optional accessory ---Not fitted);

8) Install, at the highest points in the circuit, apparatus which

allows the bleeding of air and possibly the filling of glycol;

9) Place a drain valve at the lowest point in the circuit and im-

mediately at the outlet of the water chiller;

10) Install a water filling set including the following:

a) filling water meter;
b) manometer;
c) non---return valve;
d) air separator;
e) removable supply tube,

which must be disconnected

after each charge/top---up;

11) For maximum protection ensure that all tubing exposed to

low outdoor temperatures is fitted with anti---freeze heaters

and insulated using closed cell synthetic rubber (elasto-

mer);

12) The circuit must include an expansion vessel (with safety

valve) of suitable capacity;

13) Connect the lines avoiding stresses on the machine inner

parts.

Note:

If the water chiller is complete with an expansion vessel (sup-

plied as an option), check if the capacity is enough, and install

a second vessel in the circuit, if required (see par. 8.4).

Follow the indications in Fig. c for the correct sizing.
Note:

The whole circuit must contain a water volume suitable for the

capacity of the installed chiller. Check if the inertial capacity giv-

en by the sum of the hydraulic volume inside the machine (in-

cluding the volume of the optional interna tank, if fitted) and the

system volume issufficient, or possibly installa tank in the circuit.

Follow the indications in Fig. b for the correct sizing.
Note:

The hydraulic circuit must ensure a constant water supply to the

evaporator in every operating condition. Otherwise, the com-

pressors may be damaged by repeated returnsof liquid refriger-

ant on their suction.
Note:

The water flow switch is a compulsory safety component that

must be installed and correctly wired to the Matrix S chillers,

otherwise the guarantee will be invalidated.

It is installed, as standard, on units with the optional on---board

pump set, and is available as a option for units without pumps

on board: in the latter case the flow switch, if not installed on the

machine, can be installed on the hydraulic circuit by the installer,

but it is compulsory that it is wired to the electric panel terminal

board, as indicated on the wiring diagram.

3.1.2 -- Addition of water and ethylene glycol

Very important:
Add water and ethylene glycol to the circuit with a % depending

on the minimum temperature of the outside air expected at the

installation site. Do not exceed the nominal operating pressure

of the circuit’s components.
Notes:

S

To avoid stratification run the circulation pump for at least 30

minutes after adding any glycol.

S

After adding water to the hydraulic circuit

always discon-

nect the water supply coming from the sanitary supply;

this avoids the danger of glycol entering the sanitary water

system.

S

After any topping---up of the water check the concentration

and add glycol if necessary.

3.1.3 -- Water--glycol mixture

Water---glycol mixtures are used as the thermal carrier fluid in

very cold climatesor with temperatures below zero degreescen-

tigrade. Determine the ethylene glycol % which must be added

to the water, with the assistance of Tab. a.

Summary of Contents for CBH 017

Page 1: ...HIGH PERFORMANCE AIR COOLED CHILLER S 017 032 SERVICE MANUAL English Cod 272902 Rev 25 05 2005 Issued by T D Service...

Page 2: ......

Page 3: ...read the identification labels affixed to the outside and inside of the unit IMPORTANT This manual may be subject to modification for complete and up to date information the user should always consult...

Page 4: ...of the liquid line are the charging valves filters dryers solenoid valve shut off valve moisture indicator and thermostatic expansion valve The hydraulic circuit with max working pressure 5 bar is mad...

Page 5: ...ets of the pump and water chiller Can be supplied as an optional accessory Not fitted 8 Install at the highest points in the circuit apparatus which allows the bleeding of air and possibly the filling...

Page 6: ...ing a diameter ofat leastthat of the valve outlet without burdening the valvebody Conveythe discharge to areas where the jet cannot harm people and the surrounding environment Fig a Ideal chilled wate...

Page 7: ...mpressors are equipped with anelectronic protectionde vice blocking their start if the phase sequence is not correct or stopping their operationif athermal relayintervenes Thisdevice is essential for...

Page 8: ...face and Hiromatic Service Manual 5 Refrigerant and Oil Charge All work on pipes or components of the refrigerating circuit un der pressure must be exclusively carried out by qualified staff competent...

Page 9: ...dicated below MODELS SETTINGS SAFETY VALVE CBH CLH CQH 017 020 023 025 028 SBH SLH 017 020 023 025 028 SQH 017 020 023 025 29 bar high pressure side 6 1 Setting thermostatic expansion valve THIS OPERA...

Page 10: ...es operate correctly S Check the correct operation of the thermostatic valve superheating between 5 C 8 C S Check that the oil level indicated by the compressor sight glass is higher than the min valu...

Page 11: ...dition of low condensing temperature below the safety threshold leads the Microface mi croprocessor control to disable the heat recovery protecting the system from any possible malfunctioning Fig e Re...

Page 12: ...recovery conditions water inlet outlet 40 45 C Tab 3 Total heat recovery 100 Model 017 020 023 025 028 030 032 Heating capacity kW 212 238 290 320 357 412 453 Water flow l s 10 13 11 37 13 86 15 29 1...

Page 13: ...Refrigerant charge each circuit kg 23 0 23 6 32 8 32 8 39 4 42 0 Oil charge each circuit lt 12 4 14 2 16 0 16 0 16 0 16 0 Models SBH 017 020 023 025 028 030 032 Refrigerant charge each circuit kg 19 5...

Page 14: ...1 107 0 178 72 209 299 547 119 9 198 72 Fan power input Fan nominal current Fan max current kW A A 0 95 2 2 2 4 Std head pressure pump model Opt Std head pressure pump motor max power Std head pressur...

Page 15: ...current High head pressure pump model Opt High head pressure pump motor max power High head pressure pump max current kW A kW A 65 260 2 4 0 8 00 65 340 2 5 5 11 20 65 340 2 5 5 11 20 65 410 2 7 5 15...

Page 16: ...Low pressure switch Barg Barg Barg 26 0 29 0 2 8 1 With nominal air flow water flow outlet at 7 C full load SBH R 407C Size 017 020 023 025 028 030 032 Working Range Max outdoor air temperature 2 C 4...

Page 17: ...3 63 63 Pump weight kg 74 3 149 2 89 2 178 9 2 pole pump set standard head pressure data refers to each pump Models 017 020 023 025 028 030 032 SBH 30 glycol water mixture flow m3 h 31 91 34 52 43 66...

Page 18: ...view 1000 1000 1500 1500 Extraordinary maintenance area Notes Minimum distance between 2 units from condensing coil side 3 m Do not obstruct the air exiting the fans for a minimum distance of 2 5 m AI...

Page 19: ...locking pins and split pins as shown above The capacity of the lifting gear must be adequate to lift the load in question Check the weight of the unit the capacity of the lifting gear and ropes and t...

Page 20: ...1 319 400 400 448 467 485 291 319 400 400 448 467 485 CQH 017 020 023 025 028 030 193 196 225 225 248 256 193 196 225 225 248 256 258 279 346 346 363 376 258 279 346 346 363 376 251 259 290 290 305 32...

Page 21: ...77 392 360 377 392 360 377 392 462 467 479 462 467 479 382 390 418 382 390 418 382 390 418 030 5 449 5 449 3 392 3 392 3 392 6 479 6 479 390 418 390 418 390 418 SBH 017 020 472 469 472 469 286 304 286...

Page 22: ...16 5 160 83 190 5 Rubber supports 1000 liters tank Unit Configuration Support kit code Single support code Kit support pieces CBH CLH CQH 017 020 023 025 028 030 032 Without tank 485625 270326 8 SBH S...

Page 23: ...like part G PARTIAL HEAT RECOVERY INLET TOTAL HEAT RECOVERY OUTLET SUPPLY CABLE INLET PREPUNCH 2 x 67 30 W Z CBH CLH CQH 017 030 SBH SLH SQH 017 030 M REAR VIEW from H DX LATERAL VIEW TOP VIEW FRONT...

Page 24: ...lled water connection Y OUTLET DN80 3 88 9 mm OUTLET DN80 3 88 9 mm OUTLET DN80 3 88 9 mm REMOVABLE PANEL SUPPLY CABLE INLET PREPUNCH 2 x 67 30 M REAR VIEW from H DX LATERAL VIEW TOP VIEW FRONT VIEW A...

Page 25: ...62 1300 378 M REMOVABLE PANEL F PREPUNCHED 110 for inlet outlet pipes connections TOP VIEW FRONT VIEW SX LATERAL VIEW DX LATERAL VIEW PART G N 229 L 120mm DN80 3 88 9mm N VIEW TANK CONNECTING PIPE V V...

Page 26: ...0 13 13 14 14 19 19 2 2 5 Refrigerant components Pos Item Description Pos Item Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Compressor High pressure switch HP Low pressure switch LP Crankcase heater H...

Page 27: ...ATER OUTLET VICTAULIC COUPLING DN 80 3 88 9 mm HEAT RECOVERY WATER OUTLET VICTAULIC COUPLING OPT DN 80 3 88 9 mm Refrigerant components Pos Item Description Pos Item Description 1 2 3 4 5 6 7 8 9 10 1...

Page 28: ...TION DN 80 3 88 9 mm T F 10 5 7 5 4 9 13 4 5 5 6 4 9 13 10 3 8 14 11 12 1 2 CHILLED WATER OUTLET VICTAULIC CONNECTION DN 80 3 88 9 mm WATER TANK OUTLET VICTAULIC CONNECTION DN 80 3 88 9 mm 15 15 p 16...

Page 29: ...IC CONNECTION DN 80 3 88 9 mm CHILLED WATER INLET VICTAULIC CONNECTION DN 80 3 88 9 mm CHILLED WATER OUTLET VICTAULIC CONNECTION DN 80 3 88 9 mm 15 p 21 15 Hydraulic components Item Description Item D...

Page 30: ......

Page 31: ...d Le Fabricant d clare que ce produit est conforme aux directives Europ ennes El Fabricante declara que este producto es conforme a las directivas Europeas O Fabricante declara que este produto est em...

Page 32: ...of EMERSON Tel 39 049 9719111 Telefax 39 049 5841257 Internet www liebert hiross com Printed in Italy by Liebert HIROSS S p A Issued by T D Service Since the Liebert HIROSS Company has a policy of co...

Reviews: