Liebert CBH 017 Service Manual Download Page 10

7

7 --- Maintenance

The Maintenance Programme below must be carried out by a

qualified technician, preferably working under a maintenance

contract.

Before any intervention on the unit or accessing the inner com-

ponents (removing the outer panels), always ensure the ma-

chine is switched off. If the front upper panels are removed (coil

compartment) wait for the fan(s) to come to a complete stop be-

fore accessing the compartment; if the front lower panels are re-

moved, pay special attention when working near the com-

pressor upper part and the discharge line: they are very hot;

possibly wait for them to cool. Be very careful when operating

close tothe finned coils, asthe finsare very sharp. Do notremove

the fan protection grille before electrically isolating the whole

machine. Do not insert foreign matter through the fan protection

grille. After the maintenance interventions, always close the unit

with the suitable panels, fastened by the tightening system.

7.1 --- Spare parts

The use of original spare parts is recommended.

When placing an order refer to the ”Component List” enclosed

with the machine and quote the unit model no. and serial no.

7.2 --- Dismantling the unit

The machine has been designed and built to ensure continuous

operation.

The working life of some of the main components, such as the

fans and the compressors, depends on the maintenance that

they receive.

If the unit has to be dismantled, the job must be done by skilled

refrigeration technicians.

The refrigerant and the lubricating oil in the circuit must be dis-

posed of in conformity with the laws in force in your country.

Maintenance programme -- Monthly check

FANS

S

Check that the fan motor rotates freely without any abnormal noise, and ensure that the

bearings are not running hot.

S

Also check the current absorption.

CONDENSER AND AIR FILTER

S

Check the conditions of the filters (if they are supplied); if necessary clean them (including

the electrical panel ventilation filter).

S

Check the condenser coils and clean if necessary with compressed air or soft brushes.

CONTROL

S

Check that the control equipment, LEDs and display are operating correctly.

ELECTRICAL CIRCUIT

S

Check the electrical supply on all phases.

S

Ensure that all electrical connections are tight.

REFRIGERATION CIRCUIT

S

Check the condensing and the evaporating pressures (to be done by a refrigeration techni-

cian).

S

Check the compressor’s current absorption, the delivery temperature and possible unusual

noises.

S

Check the refrigerant charge by means of the sight glass.

S

Check that the safety devices operate correctly.

S

Check the correct operation of the thermostatic valve (superheating between 5

û

C

---

8

û

C).

S

Check that the oil level indicated by the compressor sight glass is higher than the min. value.

CHILLED WATER CIRCUIT

S

Ensure that there are no water leaks.

S

Bleed any air out of the hydraulic circuit using the bleed valves.

S

Verify that the water flow rate is correct.

S

Check the inlet --- outlet liquid temperature and pressure.

S

Check the correct operation of the three---way valve (Versions with free---cooling only).

S

Check if the system is charged with the specified glycol percentage and that no ice has

formed in the hydraulic circuit.

S

Check the evaporator cleanliness.

8 --- Options and Accessories

8.1 --- Pump set

The centrifugal pump units are direct driven, with close---

coupled motors and a single shaft; the induction motor has 2

poles with IP 55 protection and class F insulation.
Pump casingsand impellersare in cast iron EN---GJL 200, shafts

are in stainless steel, the shaft seal is a unbalanced, mechanical

shaft seal with dimensions according to DIN 24 960 and assem-

bly length according to EN 12 756, brass neck ring permits ideal

conditions for the use of water mixtures containing ethylene gly-

col. The pump housing, the motor stool and the motor stator

housing are electrocoated.
The pump units have been chosen and sized to operate within

specific limits, namely:

S

Water / ethylene glycol mixtures up to 65% / 35% by weight;

S

Temperatures of the standard pumped fluid not lower than

4

°

C.

The motor stool forms connection between the pump housing

and the motor, and is equipped with a manual air vent screw for

venting of the pump housing and the shaft seal chamber. It is

very important to carry out this operation as the circulation of liq-

uid through the duct of the air vent screw ensures lubrication and

cooling of the shaft seal.
Between the outlets of the two chambers and the discharge

flange, twin---head pumps have a non---return flap valve in

EPDM rubber. The flap is opened by the flow of the pumped liq-

uid and cuts off the port of the idle pump chamber.
In the electrical panel there are automatic circuit breakers for

each pump; the microprocessor control manages the operating

rotation between the two pumps and start---up of the stand---by

pump if the primary pump fails.
For the technical features of the pumps and the hydraulic sche-

matic see Tab. 8, Fig. 10 and Fig. 11.

8.2 --- Water chiller with partial heat

recovery (20%)

This option enables the recovery of up to20% of the heatnormal-

ly rejected by the condensers (see Tab. 2). The system does not

require any adjustment and is made up of plate heatexchangers

installed on each circuit before the condenser. The exchangers

are protected by a suitable anti---frost heater that operates when

Summary of Contents for CBH 017

Page 1: ...HIGH PERFORMANCE AIR COOLED CHILLER S 017 032 SERVICE MANUAL English Cod 272902 Rev 25 05 2005 Issued by T D Service...

Page 2: ......

Page 3: ...read the identification labels affixed to the outside and inside of the unit IMPORTANT This manual may be subject to modification for complete and up to date information the user should always consult...

Page 4: ...of the liquid line are the charging valves filters dryers solenoid valve shut off valve moisture indicator and thermostatic expansion valve The hydraulic circuit with max working pressure 5 bar is mad...

Page 5: ...ets of the pump and water chiller Can be supplied as an optional accessory Not fitted 8 Install at the highest points in the circuit apparatus which allows the bleeding of air and possibly the filling...

Page 6: ...ing a diameter ofat leastthat of the valve outlet without burdening the valvebody Conveythe discharge to areas where the jet cannot harm people and the surrounding environment Fig a Ideal chilled wate...

Page 7: ...mpressors are equipped with anelectronic protectionde vice blocking their start if the phase sequence is not correct or stopping their operationif athermal relayintervenes Thisdevice is essential for...

Page 8: ...face and Hiromatic Service Manual 5 Refrigerant and Oil Charge All work on pipes or components of the refrigerating circuit un der pressure must be exclusively carried out by qualified staff competent...

Page 9: ...dicated below MODELS SETTINGS SAFETY VALVE CBH CLH CQH 017 020 023 025 028 SBH SLH 017 020 023 025 028 SQH 017 020 023 025 29 bar high pressure side 6 1 Setting thermostatic expansion valve THIS OPERA...

Page 10: ...es operate correctly S Check the correct operation of the thermostatic valve superheating between 5 C 8 C S Check that the oil level indicated by the compressor sight glass is higher than the min valu...

Page 11: ...dition of low condensing temperature below the safety threshold leads the Microface mi croprocessor control to disable the heat recovery protecting the system from any possible malfunctioning Fig e Re...

Page 12: ...recovery conditions water inlet outlet 40 45 C Tab 3 Total heat recovery 100 Model 017 020 023 025 028 030 032 Heating capacity kW 212 238 290 320 357 412 453 Water flow l s 10 13 11 37 13 86 15 29 1...

Page 13: ...Refrigerant charge each circuit kg 23 0 23 6 32 8 32 8 39 4 42 0 Oil charge each circuit lt 12 4 14 2 16 0 16 0 16 0 16 0 Models SBH 017 020 023 025 028 030 032 Refrigerant charge each circuit kg 19 5...

Page 14: ...1 107 0 178 72 209 299 547 119 9 198 72 Fan power input Fan nominal current Fan max current kW A A 0 95 2 2 2 4 Std head pressure pump model Opt Std head pressure pump motor max power Std head pressur...

Page 15: ...current High head pressure pump model Opt High head pressure pump motor max power High head pressure pump max current kW A kW A 65 260 2 4 0 8 00 65 340 2 5 5 11 20 65 340 2 5 5 11 20 65 410 2 7 5 15...

Page 16: ...Low pressure switch Barg Barg Barg 26 0 29 0 2 8 1 With nominal air flow water flow outlet at 7 C full load SBH R 407C Size 017 020 023 025 028 030 032 Working Range Max outdoor air temperature 2 C 4...

Page 17: ...3 63 63 Pump weight kg 74 3 149 2 89 2 178 9 2 pole pump set standard head pressure data refers to each pump Models 017 020 023 025 028 030 032 SBH 30 glycol water mixture flow m3 h 31 91 34 52 43 66...

Page 18: ...view 1000 1000 1500 1500 Extraordinary maintenance area Notes Minimum distance between 2 units from condensing coil side 3 m Do not obstruct the air exiting the fans for a minimum distance of 2 5 m AI...

Page 19: ...locking pins and split pins as shown above The capacity of the lifting gear must be adequate to lift the load in question Check the weight of the unit the capacity of the lifting gear and ropes and t...

Page 20: ...1 319 400 400 448 467 485 291 319 400 400 448 467 485 CQH 017 020 023 025 028 030 193 196 225 225 248 256 193 196 225 225 248 256 258 279 346 346 363 376 258 279 346 346 363 376 251 259 290 290 305 32...

Page 21: ...77 392 360 377 392 360 377 392 462 467 479 462 467 479 382 390 418 382 390 418 382 390 418 030 5 449 5 449 3 392 3 392 3 392 6 479 6 479 390 418 390 418 390 418 SBH 017 020 472 469 472 469 286 304 286...

Page 22: ...16 5 160 83 190 5 Rubber supports 1000 liters tank Unit Configuration Support kit code Single support code Kit support pieces CBH CLH CQH 017 020 023 025 028 030 032 Without tank 485625 270326 8 SBH S...

Page 23: ...like part G PARTIAL HEAT RECOVERY INLET TOTAL HEAT RECOVERY OUTLET SUPPLY CABLE INLET PREPUNCH 2 x 67 30 W Z CBH CLH CQH 017 030 SBH SLH SQH 017 030 M REAR VIEW from H DX LATERAL VIEW TOP VIEW FRONT...

Page 24: ...lled water connection Y OUTLET DN80 3 88 9 mm OUTLET DN80 3 88 9 mm OUTLET DN80 3 88 9 mm REMOVABLE PANEL SUPPLY CABLE INLET PREPUNCH 2 x 67 30 M REAR VIEW from H DX LATERAL VIEW TOP VIEW FRONT VIEW A...

Page 25: ...62 1300 378 M REMOVABLE PANEL F PREPUNCHED 110 for inlet outlet pipes connections TOP VIEW FRONT VIEW SX LATERAL VIEW DX LATERAL VIEW PART G N 229 L 120mm DN80 3 88 9mm N VIEW TANK CONNECTING PIPE V V...

Page 26: ...0 13 13 14 14 19 19 2 2 5 Refrigerant components Pos Item Description Pos Item Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Compressor High pressure switch HP Low pressure switch LP Crankcase heater H...

Page 27: ...ATER OUTLET VICTAULIC COUPLING DN 80 3 88 9 mm HEAT RECOVERY WATER OUTLET VICTAULIC COUPLING OPT DN 80 3 88 9 mm Refrigerant components Pos Item Description Pos Item Description 1 2 3 4 5 6 7 8 9 10 1...

Page 28: ...TION DN 80 3 88 9 mm T F 10 5 7 5 4 9 13 4 5 5 6 4 9 13 10 3 8 14 11 12 1 2 CHILLED WATER OUTLET VICTAULIC CONNECTION DN 80 3 88 9 mm WATER TANK OUTLET VICTAULIC CONNECTION DN 80 3 88 9 mm 15 15 p 16...

Page 29: ...IC CONNECTION DN 80 3 88 9 mm CHILLED WATER INLET VICTAULIC CONNECTION DN 80 3 88 9 mm CHILLED WATER OUTLET VICTAULIC CONNECTION DN 80 3 88 9 mm 15 p 21 15 Hydraulic components Item Description Item D...

Page 30: ......

Page 31: ...d Le Fabricant d clare que ce produit est conforme aux directives Europ ennes El Fabricante declara que este producto es conforme a las directivas Europeas O Fabricante declara que este produto est em...

Page 32: ...of EMERSON Tel 39 049 9719111 Telefax 39 049 5841257 Internet www liebert hiross com Printed in Italy by Liebert HIROSS S p A Issued by T D Service Since the Liebert HIROSS Company has a policy of co...

Reviews: