Installation, Operation and Maintenance Manual
12
Liebert TVSS Units SL-22085 Rev 2, 11/2006
Surge Suppression Systems
Liebert PanelGuard Series - Type LPGE
Surge Protective Device (SPD)
Installation Instructions
1. Insure that all power is removed before beginning installation. A qualifi ed licensed electrician shall install all electrical
connections
2. The unit is provided in a NEMA 1 rated industrial-use enclosure and should be installed in areas only appropriate for NEMA 1.
3. The unit is to be wall mounted in an area where suffi cient access and working space around the cabinet can be assured. (See
NEC Section 110-16.) Position the SPD opposite the incoming feed to the panelboard. For example, if the panelboard is
supplied through the top of its enclosure, mount the SPD at the bottom of the panelboard.
4. Knockouts for connection of the suppressor to the panelboard back box are provided on top, bottom, and sides of the unit’s
enclosure. The diameters of the knockouts vary to accommodate conduit / collar diameters of 1/2 in. to 1 1/4 in. The proper
size busing (diameter and length) must be selected to protect the conductors as they transition from the SPD to the panelboard
conductor, and to maintain the cosmetic integrity of the Liebert LPGE Series Surge Protection Device.
5. When connecting the SPD to the panelboard, it is important that the panelboards interior and the SPD are protected from any
metal shavings, which may result. An inspection and cleaning of the LPGE should be performed before applying power.
6. Representative samples of this product have been investigated by Underwriters Laboratories, Incorporated to withstand,
without exposing live circuits or components at system voltages and fault currents of up to 200,000 AIC, as described in the
Standard for Safety, Transient Voltage Surge Suppressor (TVSS), Standard 1449, Second Edition,
dated August 15, 1996.
7. An external circuit breaker is not necessary for over-current protection. However, it is recommended that the SPD be connected
in series with a 30A circuit breaker. The SPD shall be connected in accordance with all national and local electrical codes.
8. To obtain the suppression voltage ratings (SVRs), as obtained by Underwriters Laboratory, Incorporated, in accordance with
the
Standard for Safety, Transient Voltage Surge Suppressors (TVSS), Standard 1449, Second Edition,
dated August 15, 1996,
marked on this product, #8 AWG wire must be utilized to connect the unit to your facilities power grid. Connections made
with conductors other that #8 AWG may result in different SVRs.
9. Connect black wires (line or phase) marked L1/A, L2/B or L3/C, the white wire (neutral) marked N, and the green wire (ground)
marked G, of the SPD using the wire range listed in the table below in accordance with the National Electric Code (NEC) Article
285 and all local codes. To yield the best performance of the SPD within the electrical distribution system, keep all conductors
as short as possible and avoid sharp bends.
10. Connection to the Form ‘C’ contacts shall be with #18 – 22 AWG. Contacts are rated 5 amps at 250 VAC maximum with a
power factor of 1.0.
11. Apply power. The surge protector is fully operational when the GREEN LEDs are illuminated. If the GREEN LEDs are extinguished,
check to ensure that power is applied to the SPD. If an abnormal indication is present, remove power to the SPD and contact
Liebert/Emerson Network Power Surge Protection at 1-800-288-6169 or 1-607-724-2484.
12. Periodically monitor the status of the LEDs. Reduced protection exists if the GREEN LEDs are extinguished. Please contact
Liebert/Emerson Network Power Surge Protection at 1-800-288-6169 or 1-607-724-2484.
13.
The protection modules in these SPDs are replaceable, contact Liebert/Emerson Network Power Surge Protection
for replacement.
Dimensions (Inches)
Weight
A
B
C
Lbs
Kg
FxxxD800
Three Phase Delta
60.0
48.0
12.0
500
227
FxxxY800
Three Phase Wye
60.0
48.0
12.0
530
241
FxxxD1200
Three Phase Delta
60.0
48.0
20.0
700
318
FxxxY1200
Three Phase Wye
60.0
48.0
20.0
750
340
FxxxD2000
Three Phase Delta
60.0
48.0
20.0
875
397
FxxxY2000
Three Phase Wye
60.0
48.0
20.0
950
431
FxxxD4000
Three Phase Delta
60.0
48.0
20.0
1175
533
FxxxY4000
Three Phase Wye
60.0
48.0
20.0
1300
590
NOTE: Consult factory for special instructions on caseless and switchgear models.
Current
Model
Dimensions
(Inches)
Weight
Rating
XXX = VOLTAGE
Application
A
B
C
D
E
F
Lbs
Kg
FxxxN/L30 Single
Phase
24.0 20.0 9.0
21.25 10.0 .44
35 15.9
FxxxS30
Split
Phase
24.0 20.0 9.0
25.25 14.0 .44
45 20.4
FxxxD30
Three Phase Delta
24.0
20.0
9.0
25.25
14.0
.44
50
22.7
FxxxY30
Three Phase Wye
24.0
20.0
9.0
25.25
14.0
.44
60
27.2
FxxxN/L60 Single
Phase
24.0 20.0 9.0
21.25 10.0 .44
35 15.9
FxxxS60
Split
Phase
24.0 20.0 9.0
25.25 14.0 .44
45 20.4
FxxxD60
Three Phase Delta
24.0
20.0
9.0
25.25
14.0
.44
50
22.7
FxxxY60
Three Phase Wye
24.0
20.0
9.0
25.25
14.0
.44
60
27.2
FxxxN/L100 Single
Phase
30.0 24.0 9.0
25.25 14.0 .44
60 27.2
FxxxS100
Split
Phase
30.0 24.0 9.0
31.25 18.0 .44
70 31.8
FxxxD100
Three Phase Delta
30.0
24.0
9.0
31.25
18.0
.44
70
31.8
FxxxY100
Three Phase Wye
30.0
24.0
9.0
31.25
18.0
.44
80
36.3
FxxxN/L225
Single Phase L – N
30.0
24.0
9.0
25.25
14.0
.44
60
27.2
FxxxS225
Split
Phase
30.0 24.0 9.0
31.25 18.0 .44
70 31.8
FxxxD225
Three Phase Delta
30.0
24.0
9.0
31.25
18.0
.44
70
31.8
FxxxY225
Three Phase Wye
30.0
24.0
9.0
31.25
18.0
.44
80
36.3
FxxxD400
Three Phase Delta
48.0
36.0
12.0
49.25
30.0
.44
275
125
FxxxY400
Three Phase Wye
48.0
36.0
12.0
49.25
30.0
.44
300
136
Surge Suppression Systems
Installation, Operation and Maintenance Manual
17
Liebert TVSS Units SL-22085 Rev 2, 11/2006
Active Tracking Filter Series - Type F
Typical Cabinet Data (30 to 400Amps)
Typical Cabinet Data (800 to 4000Amps)
F
B
A
D
E
B
2.0” Max.
Large Bezel 2.0” Max. (Options)
Small Bezel .50” Max. (No Options)
A
C
12”
Application
30A
60A
100A
225A
400A
800A
1200A
2000A
4000A
Current
Rating
Model
XXX = VOLTAGE
Liebert Interceptor II Printer S14 14
12/29/06 1:38:00 PM