Installation, Operation and Maintenance Manual 

12 

Liebert TVSS  Units SL-22085 Rev 2, 11/2006

Surge Suppression Systems

Liebert PanelGuard Series - Type LPGE

Surge Protective Device (SPD)

Installation Instructions

1.  Insure that all power is removed before beginning installation. A qualifi ed licensed electrician shall install all electrical 

connections

2.  The unit is provided in a NEMA 1 rated industrial-use enclosure and should be installed in areas only appropriate for NEMA 1.

3.  The unit is to be wall mounted in an area where suffi cient access and working space around the cabinet can be assured. (See 

NEC Section 110-16.) Position the SPD opposite the incoming feed to the panelboard. For example, if the panelboard is 
supplied through the top of its enclosure, mount the SPD at the bottom of the panelboard.

4.  Knockouts for connection of the suppressor to the panelboard back box are provided on top, bottom, and sides of the unit’s 

enclosure. The diameters of the knockouts vary to accommodate conduit / collar diameters of 1/2 in. to 1 1/4 in. The proper 
size busing (diameter and length) must be selected to protect the conductors as they transition from the SPD to the panelboard 
conductor, and to maintain the cosmetic integrity of the Liebert LPGE Series Surge Protection Device.

5.  When connecting the SPD to the panelboard, it is important that the panelboards interior and the SPD are protected from any 

metal shavings, which may result. An inspection and cleaning of the LPGE should be performed before applying power.

6.  Representative samples of this product have been investigated by Underwriters Laboratories, Incorporated to withstand, 

without exposing live circuits or components at system voltages and fault currents of up to 200,000 AIC, as described in the 

Standard for Safety, Transient Voltage Surge Suppressor (TVSS), Standard 1449, Second Edition,

 dated August 15, 1996.

7.  An external circuit breaker is not necessary for over-current protection. However, it is recommended that the SPD be connected 

in series with a 30A circuit breaker. The SPD shall be connected in accordance with all national and local electrical codes.

8.  To obtain the suppression voltage ratings (SVRs), as obtained by Underwriters Laboratory, Incorporated, in accordance with 

the 

Standard for Safety, Transient Voltage Surge Suppressors (TVSS), Standard 1449, Second Edition,

 dated August 15, 1996, 

marked on this product, #8 AWG wire must be utilized to connect the unit to your facilities power grid. Connections made 
with conductors other that #8 AWG may result in different SVRs.

9.  Connect black wires (line or phase) marked L1/A, L2/B or L3/C, the white wire (neutral) marked N, and the green wire (ground) 

marked G, of the SPD using the wire range listed in the table below in accordance with the National Electric Code (NEC) Article 
285 and all local codes. To yield the best performance of the SPD within the electrical distribution system, keep all conductors 
as short as possible and avoid sharp bends.

10.  Connection to the Form ‘C’ contacts shall be with #18 – 22 AWG. Contacts are rated 5 amps at 250 VAC maximum with a 

power factor of 1.0.

11.  Apply power. The surge protector is fully operational when the GREEN LEDs are illuminated. If the GREEN LEDs are extinguished, 

check to ensure that power is applied to the SPD. If an abnormal indication is present, remove power to the SPD and contact 
Liebert/Emerson Network Power Surge Protection  at 1-800-288-6169 or 1-607-724-2484.

12.  Periodically monitor the status of the LEDs. Reduced protection exists if the GREEN LEDs are extinguished. Please contact 

Liebert/Emerson Network Power Surge Protection  at 1-800-288-6169 or 1-607-724-2484.

13.  

The protection modules in these SPDs are replaceable, contact Liebert/Emerson Network Power Surge Protection 
for replacement.

 

  

    

 

 

Dimensions (Inches)   

  Weight

 

 

  

  

 

 

Lbs 

 

Kg

 

 

FxxxD800 

Three Phase Delta  

60.0 

48.0 

12.0 

500 

227

 

 

FxxxY800 

Three Phase Wye 

60.0 

48.0 

12.0 

530 

241

 

 

FxxxD1200 

Three Phase Delta 

60.0 

48.0 

20.0 

700 

318

 

 

FxxxY1200 

Three Phase Wye 

60.0 

48.0 

20.0 

750 

340

 

 

FxxxD2000 

Three Phase Delta 

60.0 

48.0 

20.0 

875 

397

 

 

FxxxY2000 

Three Phase Wye 

60.0 

48.0 

20.0 

950 

431

 

 

FxxxD4000 

Three Phase Delta 

60.0 

48.0 

20.0 

1175 

533

 

 

FxxxY4000 

Three Phase Wye 

60.0  

48.0 

20.0 

1300 

590

 NOTE: Consult factory for special instructions on caseless and switchgear models.

 Current 

Model 

 

Dimensions 

(Inches) 

Weight

 

Rating 

XXX = VOLTAGE  

Application

 A 

Lbs 

Kg

  

FxxxN/L30  Single 

Phase 

24.0  20.0 9.0 

21.25 10.0  .44 

35 15.9

  

FxxxS30 

Split 

Phase 

24.0  20.0 9.0 

25.25 14.0  .44 

45 20.4

 

 

FxxxD30 

Three Phase Delta 

24.0 

20.0 

9.0 

25.25 

14.0 

.44 

50 

22.7

 

 

FxxxY30 

Three Phase Wye 

24.0 

20.0 

9.0 

25.25 

14.0 

.44 

60 

27.2

  

FxxxN/L60  Single 

Phase 

24.0  20.0 9.0 

21.25 10.0  .44 

35 15.9

  

FxxxS60 

Split 

Phase 

24.0  20.0 9.0 

25.25 14.0  .44 

45 20.4

 

 

FxxxD60 

Three Phase Delta 

24.0 

20.0 

9.0 

25.25 

14.0 

.44 

50 

22.7

 

 

FxxxY60 

Three Phase Wye 

24.0 

20.0 

9.0 

25.25 

14.0 

.44 

60 

27.2

  

FxxxN/L100  Single 

Phase 

30.0  24.0 9.0 

25.25 14.0  .44 

60 27.2

  

FxxxS100 

Split 

Phase 

30.0  24.0 9.0 

31.25 18.0  .44 

70 31.8

 

 

FxxxD100 

Three Phase Delta 

30.0 

24.0 

9.0 

31.25 

18.0 

.44 

70 

31.8

 

 

FxxxY100 

Three Phase Wye 

30.0 

24.0 

9.0 

31.25 

18.0 

.44 

80 

36.3

 

 

FxxxN/L225 

Single Phase L – N 

30.0 

24.0 

9.0 

25.25 

14.0 

.44 

60 

27.2

  

FxxxS225 

Split 

Phase 

30.0  24.0 9.0 

31.25 18.0  .44 

70 31.8

 

 

FxxxD225 

Three Phase Delta 

30.0 

24.0 

9.0 

31.25 

18.0 

.44 

70 

31.8

 

 

FxxxY225 

Three Phase Wye 

30.0 

24.0 

9.0 

31.25 

18.0 

.44 

80 

36.3

 

 

FxxxD400 

Three Phase Delta 

48.0 

36.0 

12.0 

49.25 

30.0 

.44 

275 

125

 

 

FxxxY400 

Three Phase Wye 

48.0 

36.0 

12.0 

49.25 

30.0 

.44 

300 

136

Surge Suppression Systems

Installation, Operation and Maintenance Manual 

17 

Liebert TVSS  Units SL-22085 Rev 2, 11/2006

Active Tracking Filter Series - Type F

Typical Cabinet Data (30 to 400Amps)                       

 Typical Cabinet Data (800 to 4000Amps)

F

B

A

D

E

B

2.0” Max.

Large Bezel 2.0” Max. (Options)
Small Bezel .50” Max. (No Options)

A

C

12”

Application

30A

60A

100A

225A

400A

800A

1200A

2000A

4000A

Current

Rating

Model

XXX = VOLTAGE

Liebert Interceptor II Printer S14   14

12/29/06   1:38:00 PM

Summary of Contents for AccuVar

Page 1: ...rid Advantage Type SS LM AccuVar PowerSure LPM LPL Series ATF Series PanelGuard Extension AccuGuide Products Installation Operation and Maintenance Manual Surge Protection For Business Critical Continuity 12 29 06 1 37 52 PM ...

Page 2: ...12 29 06 1 37 53 PM ...

Page 3: ...ing 6 SPD Monitoring 6 TROUBLESHOOTING SERVICING MAINTENANCE 7 Troubleshooting 7 Servicing 7 Corrective Maintenance 7 Preventative Maintenance Inspection and Cleaning 7 PRODUCT INSTALLATIONS 8 Typical Parallel Installation Type SI H SS LM ACV AII LPM LPL 8 Active Tracking Filter Type F Series 10 PanelGuard Series Type LPGE Series 12 AccuGuide Series Type ACG 13 DIMENSIONAL INFORMATION 15 Intercept...

Page 4: ... designed for operation indoors in ambient temperatures of 40ºC 40ºF to 60ºC 140ºF with a relative humidity of 0 to 95 non condensing The unit is provided in an industrial use enclosure which is dust tight and drip tight and should not be installed in areas with excessive dust corrosive vapors flammable materials or explosive atmospheres Audible Noise The audible noise of the unit is less than 40 d...

Page 5: ...e The transient voltage surge suppressor shall be connected on the load side of the first overcurrent device at the building or structure Exceptionto 1 and 2 WheretheTVSSisalsolistedasasurge arrestor the connection shall be as permitted by Article 280 3 Separately Derived System The TVSS shall be connected on the load side of the first overcurrent device in a separately derived system Disconnect Swi...

Page 6: ...20 L N 240S 240 277 240 277 480 130 L L 150 L L 275 L L 275 L L 420 L L 208L or 208 240L or 240 400L or 400 480L or 480 600L or 600 N A 208 208 N A 240 240 N A 400 400 N A 480 480 N A 600 600 Note 1 For other voltages or source confi gurations consult factory 150 L N 150 L N 320 L N 320 L N 320 L N 320 L N 420 L N 120Y 127Y 230Y 230Y 254Y 277Y 347Y 120 120 208 127 127 220 220 220 380 230 230 400 25...

Page 7: ...otary Disconnect To Protected Loads Liebert Surge Protective Device Protected Panel Wireshouldbe lessthan5feet andstraight aspossible Neutral Phase s Transient Ground Safety Ground Neutral Phases Ground To Protected Loads Liebert Surge Protective Device Protected Panel Wireshouldbe lessthan5feet andstraight aspossible Neutral Phase s Transient Ground Safety Ground Neutral Phases Ground Rotary Disc...

Page 8: ...TION THE NEUTRAL IF PROVIDED MUST BE RELIABLY CONNECTED TO THE NEUTRAL OF THE SOURCE FAILURE TO PROVIDE A RELIABLE NEUTRAL CONNECTION MAY RESULT IN MODULE FAILURE SPD Monitoring External Status Indicators These indicators provide a summary of the status of the surge SPD module For normal conditions the green OK LED is illuminated and the red Service LED is extinguished If the surge SPD module requ...

Page 9: ...assistance contact your local Liebert Sales Representative or Liebert at 800 288 6169 or 607 724 2484 Corrective Maintenance TheLiebertSPDisdesignedforyearsoftrouble freeoperation However even the most reliable equipment may fail under abnormal conditions Diagnostic indicators are provided to indicate when the unit needs replacement see individual SPD operation of this manual for details To ensure...

Page 10: ...ional Enclosures SPD Standard Enclosure Optional Enclosures Type SI NEMA 4 NEMA 4X Type ACV AII NEMA 4X N A Type H NEMA 12 NEMA 3R 4 4X Type LPM NEMA 12 NEMA 3R 4 4X Type SS NEMA 4X N A Type LPL ABS Plastic 94V 0 NEMA 1 Type LM NEMA 12 NEMA 3R 4 4X 3 Determine where the SPD is to be mounted allowing for minimum length of wire between itself and the input power terminals of the service panel Punch ...

Page 11: ...nnections see page 15 7 Apply power The surge protector is fully operational when the GREEN LEDs on the modules and the front door of enclosure are illuminated If the GREEN LEDs are extinguished or a RED LED is illuminated check to ensure that power is applied to the SPD If an abnormal indication is present remove power to the SPD and contact Liebert Emerson Network Power Surge Protection at 1 800...

Page 12: ...nput to output coupling of noise and transients Do not route input and output wiring in the same raceway If practical terminate input and output raceways conduits at opposite ends of the active tracking filter enclosure input near the top and output near the bottom 7 The Liebert Active Tracking Filter System is wired in line in series with the protected load s See Figures on the following page 8 Te...

Page 13: ... WIRE SIZE RANGE FILTER CONTINUOUS PHASE AND TRANSIENT SAFETY CURRENT RATING NEUTRAL TERMINALS GROUND TERMINAL GROUND TERMINAL 30 100 A 14 2 0 1 14 2 0 5 14 4 4 225 A 6 250 kcmil 1 14 2 0 5 10 1 0 4 400 A 6 250 kcmil 2 6 250 kcmil 2 6 250 kcmil 4 800 A 2 75 x 50 Cu Busbar 3 6 250 kcmil 2 6 250 kcmil 4 1200 A 2x 6 0 x 25 Cu Busbar 3 6 250 kcmil 2 6 250 kcmil 4 2000 A 3x 6 0 x 25 Cu Busbar 3 6 250 k...

Page 14: ...oltage Surge Suppressor TVSS Standard 1449 Second Edition dated August 15 1996 7 Anexternalcircuitbreakerisnotnecessaryforover currentprotection However itisrecommendedthattheSPDbeconnected in series with a 30A circuit breaker The SPD shall be connected in accordance with all national and local electrical codes 8 To obtain the suppression voltage ratings SVRs as obtained by Underwriters Laboratory...

Page 15: ...ating of the device supplied by the tap conductors or not less than the rating of the over current protective device at the termination of the tap conductors 2 The tap conductors do not extend beyond the switchboard panelboard disconnecting means or control devices they supply 3 Except at the point of connection to the feeder the tap conductors are enclosed in a raceway which shall extend from the...

Page 16: ...close to the protected bus as possible This product was designed to address those instances when a close installation is not possible However while the voltage drop experienced with an AccuGuide assembly is significantly reduced care should be taken to keep connection lengths to a minimum Each end of the AccuGuide assembly is shipped with five foot pigtails The length is offered as a worst case need...

Page 17: ...ions Inches Weight lbs Suggested Breaker Size Suggested Wire Size AWG Allowable Breaker Range Allowable Wire Range Dimensions Inches Unit Weight lbs Suggested Breaker Size Suggested Wire Size AWG Allowable Breaker Range Allowable Wire Range A B C D E F A B C D E F SI016 SI025 SI032 SI040 SI050 SI060 SI075 SI100 16 20 20 20 12 16 16 20 8 8 8 8 17 25 17 25 21 25 21 25 9 5 10 10 14 0 44 0 44 0 44 0 4...

Page 18: ...1 2006 Surge Suppression Systems Hybrid Advantage Series Type H AccuVar Series Type ACV AII E F 4X B A D C 1 840 Max 2 625 Max Service Panel for Loads to be Protected Phase L1 A Phase L2 B Phase L3 C Disconnect Main Breaker for Panel Neutral Buss Ground Buss Dedicated Disconnect Optional Recommended Wire Entrance 6 875 7 375 0 212 8 125 3 088 4 125 4 750 Slots Will Accept 8 32 Screws 1 2 Flexible ...

Page 19: ... 4 FxxxD60 Three Phase Delta 24 0 20 0 9 0 25 25 14 0 44 50 22 7 FxxxY60 Three Phase Wye 24 0 20 0 9 0 25 25 14 0 44 60 27 2 FxxxN L100 Single Phase 30 0 24 0 9 0 25 25 14 0 44 60 27 2 FxxxS100 Split Phase 30 0 24 0 9 0 31 25 18 0 44 70 31 8 FxxxD100 Three Phase Delta 30 0 24 0 9 0 31 25 18 0 44 70 31 8 FxxxY100 Three Phase Wye 30 0 24 0 9 0 31 25 18 0 44 80 36 3 FxxxN L225 Single Phase L N 30 0 2...

Page 20: ...Panel For Loads to be Protected Disconnect Main Breaker For Panel Dedicated Disconnect Optional Neutral Buss Ground Buss Phase A Phase B Phase C Polycarbonate Window B A C E F D Type SS Series Unit Dimensions Inches Weight lbs Suggested Breaker Size Suggested Wire Size AWG Allowable Breaker Range Allowable Wire Range A B C D E F 1 Phase 3 Phase 13 32 17 32 6 6 9 6 14 75 18 75 10 12 0 32 0 32 26 43...

Page 21: ...sted Wire Size AWG Allowable Breaker Range Allowable Wire Range A B C D E F LM060 LM080 LM100 LM125 LM150 LM200 LM225 LM250 14 14 16 8 8 9 16 75 16 75 21 25 12 12 10 0 31 0 31 0 44 32 41 56 40 A 40 A 100 A 8 8 2 15A 100A 14 2 16 16 20 LM Series with Rotary Disconnect Unit Dimensions Inches Weight lbs Suggested Breaker Size Suggested Wire Size AWG Allowable Breaker Range Allowable Wire Range A B C ...

Page 22: ...anel for Loads to be Protected Phase L1 A Phase L2 B Phase L3 C Disconnect Main Breaker for Panel Neutral Buss Ground Buss Dedicated Disconnect Optional Unit is supplied from the factory with a minimum length of 18 of 12 wire for connection It is recommended that a 30A circuit breaker be used for installation Unit is equipped with Summary Alarm Contacts The 18 wires are designated as follows YELLO...

Page 23: ...r Loads to be Protected Phase L1 A Phase L2 B Phase L3 C Disconnect Main Breaker for Panel Neutral Buss Ground Buss Dedicated Disconnect Unit is equipped with Summary Alarm Contacts The 18 wires are designated as follows YELLOW Normally Open ORANGE COMMON BLUE Normally Closed Unit is supplied from the factory with a minimum length of 18 of 12 wire for connection It is REQUIRED that a 30A circuit b...

Page 24: ...PanelGuard Series Type LPGE Customer Supplied PanelBoard Neutral Bar Uninsulated Ground Bar Conduit Collar Conduit Collar Slots for Sliding Trim To Ensure Proper Fit Liebert Supplied LPGE Unit 3 Pole 30 Amp Circuit Breaker Summary Alarm Contacts Inside Module Remove Cover for Access Liebert Interceptor II Printer S9 9 ...

Page 25: ...Surge Suppression Systems Installation Operation and Maintenance Manual 23 Liebert TVSS Units SL 22085 Rev 2 11 2006 Example Installations 12 29 06 1 37 57 PM ...

Page 26: ...Installation Operation and Maintenance Manual 24 Liebert TVSS Units SL 22085 Rev 2 11 2006 Surge Suppression Systems Liebert Interceptor II Printer S7 7 ...

Page 27: ...Liebert s final invoices and to applicable Liebert product brochures and manuals current as of the date of product shipment Descriptions Liebert does not control the installation and use of any Liebert product Accordingly it is understood that the Descriptions are NOT WARRANTIES OF PERFORMANCE and NOT WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE Obtaining Performance Under This Warranty Within a ...

Page 28: ...D APPLIED MEDICAL AND DENTAL APPLICATIONS REPAIR OR REPLACEMENT OF A DEFECTIVE PRODUCT OR PART THEREOF DOES NOT EXTEND THE ORIGINAL WARRANTY PERIOD Limitations THIS WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE USER S SOLE AND EXCLUSIVE REMEDY IS REPAIR OR REPLACEMENT OF THE LIEBERT PRODUCT AS SET FORTH HE...

Page 29: ...Surge Suppression Systems Installation Operation and Maintenance Manual 27 Liebert TVSS Units SL 22085 Rev 2 11 2006 Limited Warranty 12 29 06 1 37 54 PM ...

Page 30: ...Installation Operation and Maintenance Manual 28 Liebert TVSS Units SL 22085 Rev 2 11 2006 Items Not Covered By Warranty Liebert Interceptor II Printer S3 3 ...

Page 31: ...e 852 28029250 FAX Liebert com Technical Support 607 724 2484 Phone 607 722 8713 FAX 800 288 6169 Toll Free While every precaution has been taken to ensure the accuracy and completeness of this literature Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions 2006 Liebert Corporation All rights res...

Reviews: