Liberty Pumps D3600- Series Installation Manual Download Page 4

                            

©Copyright 2011 Liberty Pumps Inc.    All rights reserved                                                             4 

 

 

4. 

Control Panel:

 

 

                              Risk of Electric shock:

 This pump is supplied with a grounding conductor.  To reduce the risk of 

electric shock, be certain that it is connected only to a properly grounded earth wire.  All electrical circuitry should be 
installed in accordance with the National Electric Code (NEC) and all applicable local codes or ordinances. 

 

                        

The control panel that is an integral part of this complete unit is supplied with its own separate 

Installation/Operation/Maintenance manual.  Ensure that you have received this manual, and that you read and 
understand it prior to installing this unit.  Your familiarity with the control panel manual is critical. 

A separate 115V branch circuit should be installed for the control circuit.   We do not recommend splitting the 
incoming pump power circuit to power the control circuit.  Connect the grinder pump leads and the float switch leads 
to the control panel in accordance with the instructions included with those units.   

5. 

Float Switches

The float switches are pre-mounted on a quick tree. For quick tree removal, loosen the cord nut 

and pull the tree straight out of the tank. The pump cycle is pre-

set at the factory at 12” for D3648 (approximately 

53 ga

llons) and 18” for D3672 (approximately 79 gallons).  The pump cycle can be adjusted by loosening the cord 

clamp and moving the “on” float up or down.  We do not recommend adjustments of more than 3” in either 
direction 

– please call the factory if you need to adjust the pump cycle beyond this recommended level. 

6. 

Testing and Startup:

  Follow the testing and startup procedures found in the grinder pump and control panel 

manual.

 

4

 

Maintenance and Troubleshooting

 

                            The grinder pump and control panel are supplied with their own separate 
Installation/Operation/Maintenance manuals.  Ensure that you have received these manuals, and that you read and 
understand them prior to installing this unit.  Your familiarity with the grinder pump manual and the control panel manual is 
critical.  Please follow the Maintenance and Troubleshooting procedures provided in those manuals.

 

 

 

 

 

Model 

Off 

Level 

On 

Level 

Alarm 

level 

Volume/ 

cycle 

D3648 

13”  

(33 cm) 

25”  

(64 cm) 

31”  

(79 cm) 

62 gal.  

(235 liters) 

D3660 

13”  

(33 cm) 

28” 

 (71 cm) 

34”  

(86 cm) 

75 gal.  

(284 liters) 

D3672 

13”  

(33 cm) 

31”  

(79 cm) 

37” 

(94 cm) 

88 gal.  

(333 liters) 

D3684 

13”  

(33 cm) 

34”  

(86 cm) 

40”  

(102 cm) 

101 gal.  

(382 liters) 

D3696 

13”  

(33 cm) 

37”  

(94 cm) 

43”  

(109 cm) 

115 gal.  

(435 liters) 

Summary of Contents for D3600- Series

Page 1: ...000E Features 36 Diameter Fiberglass Tank Available in 48 60 72 84 and 96 heights LSG Single or LSGX 2 Stage 2HP Grinder Pumps Factory Installed Guide Rail System Quick Tree pre mounted float system NEMA 4X Junction Box NEMA 4X Duplex Alternating Control Panel Contents 1 General Information 2 Precautions Pre Installation 3 Installation Instructions 4 Maintenance Troubleshooting 5 GR20 Assembly D36...

Page 2: ...ion and installation of the basin but it does not cover the specifics of the pump operation or the control panel operation If you have any questions call customer service at 800 543 2550 2 Precautions Pre Installation Risk of electric shock Always disconnect the pump from the power source before handling or making adjustments These pumps are not to be installed in locations classified as hazardous...

Page 3: ...rovide a solid level base that can support the weight of the filled basin If a concrete pad will be used under the basin the compacted stone sub base can be reduced to 6 inches 2 Connections Backfill Pour enough concrete over and around the anti floatation flange to anchor the basin and prevent upward movement Connect 2 schedule 80 PVC pipe to the pump discharge Do not reduce the size of the disch...

Page 4: ... loosen the cord nut and pull the tree straight out of the tank The pump cycle is pre set at the factory at 12 for D3648 approximately 53 gallons and 18 for D3672 approximately 79 gallons The pump cycle can be adjusted by loosening the cord clamp and moving the on float up or down We do not recommend adjustments of more than 3 in either direction please call the factory if you need to adjust the p...

Page 5: ...ctly it will seal and provide a means to lift the pump without disconnecting any of the discharge piping Please ensure that installation is done as per the diagrams below DISCONNECTED POSITION PIPE GUIDE ASSEMBLY OPERATING POSITION 1 1 4 GUIDE RAIL PIPE 1 1 4 DISCHARGE PIPE INSTALL 3 8X16 HEX BOLTS HERE EVENLY TIGHTEN BOTH SIDES SO THAT GASKET IS PROPERLY COMPRESSED ENSURE THAT RUBBER GROMMET IS P...

Page 6: ...rer shall not be liable under this Warranty if the product has not been properly installed if it has been disassembled modified abused or tampered with if the electrical cord has been cut damaged or spliced if the pump discharge has been reduced in size if the pump has been used in water containing sand lime cement gravel or other abrasives if the pump has been used in water above the advertised t...

Reviews: