Pre-installation checklist: 

 

1. 

Inspect the unit upon arrival to ensure that there is 
no shipping damage.  Pay careful attention to the 
condition of the fiberglass basin, control floats, 
pump guide rail brackets, and control panel. Notify 
the carrier immediately if there is any damage. 

2. 

Read all instructions and familiarize yourself with 
the unit’s operation prior to proceeding with the 
installation. 

3. 

A qualified licensed electrician should install and 
test all electrical circuits. 

4. 

Check to ensure that your power source is adequate 
to handle the pump amperage as noted above and on 
the pump nameplate. Ensure that the electrical supply 
circuit is equipped with fuses or breakers of the proper 
capacity. 

5. 

A separate 115V branch circuit should be installed for 
the control circuit.   We do not recommend splitting 
the incoming pump power circuit to power the control 
circuit. 

6. 

All electrical connections should be tested to ensure 
that a proper ground has been established

 

3

 

Installation Instructions

 

 

1. 

Excavation:

  Excavate the hole for the basin as small as possible, with a minimum base diameter of 50

”.  Never 

place the basin in direct contact with rocks or other sharp objects. Place enough fine, 1/8" to 3/4" pea gravel or 
1/8" to 1/2" washed, crushed stone at the bottom of the excavation to create a minimum of 12 inches stone or 
gravel after compaction.  Do not use sand or native soil as backfill*.  Properly compact underneath the basin to 
provide a solid, level base that can support the weight of the filled basin.  If a concrete pad will be used under the 
basin, the compacted stone sub-base can be reduced to 6 inches. 

2. 

Connections & Backfill:

 

 Pour enough concrete over and around the anti-floatation flange to anchor the basin 

and prevent upward movement. Connect 2

” schedule 80 PVC pipe to the pump discharge.  Do not reduce the 

size of the discharge piping, and do not increase the discharge piping to larger than 3

”.  The remainder of the 

discharge line should be as short as possible with a minimum number of turns.  Connect the inlet line 

to the 4” 

inlet hub with a rubber donut (Liberty #6112000).  Connect the electrical coupling to 2

” electrical conduit and run 

the power and float cords through the conduit to the control panel.  The remaining backfill should be only fine, 1/8" 
to 3/4" pea gravel or 1/8" to 1/2" washed, crushed stone.  Do not use sand or native soil as backfill*.  

Do Not

 exert 

heavy pressure or run heavy equipment over the backfill material, as it may cause tank collapse.  

*Other backfill options may be available 

– consult the factory for special instructions relative to your situation. 

 

3. 

Venting:

  The fiberglass basin provided 

with the system must be completely sealed 
and properly vented in order to meet health 
and plumbing code requirements.  The 
system is designed to be vented through 
the inlet to an existing building vent stack.  
In order to accomplish this, there must be 
no traps between the system inlet and the 
nearest building vent stack connection.  
See Figure A for an example.  If this is not 
possible or desirable in your application, a 
vent flange or grommet can be installed in 
a hole cut into the solid fiberglass cover. 
 

 
 
 
 
 
 

Figure A 

– Inlet Venting 

Summary of Contents for D3600- Series

Page 1: ...000E Features 36 Diameter Fiberglass Tank Available in 48 60 72 84 and 96 heights LSG Single or LSGX 2 Stage 2HP Grinder Pumps Factory Installed Guide Rail System Quick Tree pre mounted float system NEMA 4X Junction Box NEMA 4X Duplex Alternating Control Panel Contents 1 General Information 2 Precautions Pre Installation 3 Installation Instructions 4 Maintenance Troubleshooting 5 GR20 Assembly D36...

Page 2: ...ion and installation of the basin but it does not cover the specifics of the pump operation or the control panel operation If you have any questions call customer service at 800 543 2550 2 Precautions Pre Installation Risk of electric shock Always disconnect the pump from the power source before handling or making adjustments These pumps are not to be installed in locations classified as hazardous...

Page 3: ...rovide a solid level base that can support the weight of the filled basin If a concrete pad will be used under the basin the compacted stone sub base can be reduced to 6 inches 2 Connections Backfill Pour enough concrete over and around the anti floatation flange to anchor the basin and prevent upward movement Connect 2 schedule 80 PVC pipe to the pump discharge Do not reduce the size of the disch...

Page 4: ... loosen the cord nut and pull the tree straight out of the tank The pump cycle is pre set at the factory at 12 for D3648 approximately 53 gallons and 18 for D3672 approximately 79 gallons The pump cycle can be adjusted by loosening the cord clamp and moving the on float up or down We do not recommend adjustments of more than 3 in either direction please call the factory if you need to adjust the p...

Page 5: ...ctly it will seal and provide a means to lift the pump without disconnecting any of the discharge piping Please ensure that installation is done as per the diagrams below DISCONNECTED POSITION PIPE GUIDE ASSEMBLY OPERATING POSITION 1 1 4 GUIDE RAIL PIPE 1 1 4 DISCHARGE PIPE INSTALL 3 8X16 HEX BOLTS HERE EVENLY TIGHTEN BOTH SIDES SO THAT GASKET IS PROPERLY COMPRESSED ENSURE THAT RUBBER GROMMET IS P...

Page 6: ...rer shall not be liable under this Warranty if the product has not been properly installed if it has been disassembled modified abused or tampered with if the electrical cord has been cut damaged or spliced if the pump discharge has been reduced in size if the pump has been used in water containing sand lime cement gravel or other abrasives if the pump has been used in water above the advertised t...

Reviews: