176
NOTES
ENGLISH
18) Cycle High Pressure (Chiller)
h
Valid Range
Output
Function
Cycle High Pressure display
Using NV
network variable : SNVT_press_f, nvoHighPress1,
nvoHighPress2, nvoHighPress3
Operation Cycle High Pressure monitor
NV
Operation
SNVT_press_f
0 ~ 90 [Mpa]
19) Cycle Low Pressure (Chiller)
h
Valid Range
Output
Function
Cycle Low Pressure display
Using NV
network variable : SNVT_press_f, nvoLowPress1,
nvoLowPress2, nvoLowPress3
Operation Cycle Low Pressure monitor
NV
Operation
SNVT_press_f
0 ~ 90 [Mpa]
20) Cycle Total Running Current (Chiller)
h
Valid Range
Output
Function
Cycle Total Running Current display
Using NV
network variable : SNVT_amp_ac, nvoRunCurrent
Operation Cycle Total Running Current monitor
NV
Operation
SNVT_amp_ac
0 ~ 90 [A]
21) Left to Start Time (Chiller)
h
Valid Range
Output
Function
Left to Start Time display
Using NV
network variable : SNVT_time_sec, nvoTimeToStart
Operation Left to Start Time monitor
NV
Operation
SNVT_time_sec
0 ~ 1
22) Error Code (Chiller)
h
Valid Range
Output
Function
Error Code display
Using NV
network variable : SNVT_hvac_status, nvoErrCode
Operation Error Code monitor
NV
Operation
SNVT_hvac_status
1~15: Common, 21~999: Outdoor Unit