14
INSTALLATION INSTRUCTIONS
ENGLISH
Mode Override
This Function is only for Non-Auto Changeover H/P model.
Ceiling Height Selection
Our products provide variety of air volumes and capacities according to the selection of ceil-
ing heights.
Cooling/Heating performance is enhanced with relation to ceiling height.
- The highest/cooling heating performance and efficiency are provide at super high.
(Some noise may be generated according to the level height setting.)
Group Control
This function is only for group control. Please don’t set this function in case of non-group
control.
After setting Group Control of the product, turn off the power then turn it back on after 1
minute.
Auxiliary heater
This function is only applied to models with Auxiliary Heater function being activated.
Installer Setting - Installer Setting Code Table
Installer Setting Code Table
No.
Function
Function Code
Setting Value
Remote Controller LCD
0
Mode Override
0
0 : Set to Master
1 : Set to Slave
1
Ceiling Height
Selection
1
1 : Standard
2 : Low
3 : High
4 : Super High
2
Group Control
2
0 : Set to Master
1 : Set to Slave
2 : Check Master/Slave
Auxiliary heater
2
3 : Set to Auxiliary heater
4 : Cancel Auxiliary heater
5 : Check Auxiliary heater Installation