16
INSTALLATION OF OUTDOOR UNIT
ENGLISH
• Single Operation
1) Standard Inverter / High Inverter
2) Compact Inverter
* Connector information
If installed tube is shorter than 7.5 m,
additional charging is not necessary.
Additional Refrigerant
= [A-7.5 (m)] x Additional refrigerant (g/m)
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
Piping length and the elevation
ODU
Capacity
(kBtu/h)
Pipe Size mm(inch)
Length A(m)
Elevation B(m)
Additona
refrigerant
(g/m)
Gas
Liquid
Standard Max Standard
Max
UUA1
9/12
Ø 9.52 (3/8)
Ø 6.35 (1/4)
7.5
20
5
15
20
UUB1
18
Ø 12.7(1/2)
Ø 6.35 (1/4)
7.5
30
5
30
20
UUC1
24/30
Ø 15.88 (5/8)
Ø 9.52 (3/8)
7.5
50
5
30
40
UUD1/UUD3
36/42/48/60
Ø 15.88 (5/8)
Ø 9.52 (3/8)
7.5
85
5
30
40
ODU
Capacity
(kBtu/h)
Pipe Size mm(inch)
Length A(m)
Elevation B(m)
Additona
refrigerant
(g/m)
Connector
Type
Gas
Liquid
Standard Max Standard
Max
UUA1
18
Ø 12.7 (1/2)
Ø 6.35 (1/4)
7.5
30
5
30
20
b
UUB1
24/30
Ø 15.88 (5/8)
Ø 9.52 (3/8)
7.5
35
5
30
40
a, c
UUC1
36
Ø 15.88 (5/8)
Ø 9.52 (3/8)
7.5
50
5
30
40
-
Connector
a
b
c
Ø 6.35
→
Ø 9.52
Ø 9.52
→
Ø 12.7
Ø 12.7
→
Ø15.88
UUA1
**09F
X
X
X
**12F
X
X
X
**18F
X
O
X
UUB1
**18F
X
X
X
**24F
O
X
O
**30F
O
X
O
ex.) UUA1 + CT18F
Summary of Contents for UUA1 Series