9. Electric Characteristics
̰
Wiring of Main Power Supply and Equipment Capacity
1. The power supply work is needed only to the outdoor unit. The power supply to the indoor unit is conducted
through the transmission wiring. Therefore, the power supply work can be carried out at just one place of the
outdoor unit. It will contribute to simplify the work procedure and to save cost.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain liquid,etc.) when proceeding with the
wiring and connections
3. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker taking
into account the line voltage drops. Make sure the power-supply voltage does not drop more than 10%.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use should not be lighter than polychloroprene sheathed
flexible cord.
6. Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power
supply.
WARNING
•
Follow ordinance of your governmental organization for technical standard related to electrical
equipment, wiring regulations and guidance of each electric power company.
•
Make sure to use specified wires for connections so that no external force is imparted to terminal
connections. If connections are not fixed firmly, it may cause heating or fire.
•
Make sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent
may include some amount of direct current.
CAUTION
•
Some installation site may require attachment of an earth leakage breaker. If no earth leakage breaker
is installed, it may cause an electric shock.
•
Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper
wire with too large capacity may cause a malfunction of unit or fire.
Circuit breaker
Earth
Power supply
Outdoor unit
※
This figure is representative example for field wiring. Actual appearance of outdoor and indoor units
could be different with installed product.
[ Field Wiring (Single Phase, 2 Wiring Type) ]
Summary of Contents for UU48W U32
Page 1: ...FDF Heat Pump 50Hz 410A 5CSL0 02C Replaces 5CSL0 02B P No MFL67502810 ...
Page 3: ...General Information Single CAC Outdoor Unit FDF 1 Model Line Up 2 Nomenclature ...
Page 41: ...Single CAC Outdoor Unit 3 Dimensions 34 Standard Inverter AUUW85LAE UU85W U74 Chassis code U7 ...
Page 51: ...Single CAC Outdoor Unit 5 Wiring Diagrams 44 Standard Inverter AUUW18GAE UU18W UE4 ...
Page 53: ...Single CAC Outdoor Unit 5 Wiring Diagrams 46 Standard Inverter AUUW366D2 UU36W UO2 ...
Page 55: ...Single CAC Outdoor Unit 5 Wiring Diagrams 48 Standard Inverter AUUW368D2 UU37W UO2 ...
Page 57: ...Single CAC Outdoor Unit 5 Wiring Diagrams 50 Standard Inverter AUUW70LAE UU70W U34 ...
Page 58: ...5 Wiring Diagrams 51 Single CAC Outdoor Unit Standard Inverter AUUW85LAE UU85W U74 ...
Page 126: ...6 Single CAC Outdoor Unit Compact Inverter 3 Dimensions AUUW18GC0 UU18WC UL0 Chassis code UL2 ...
Page 128: ...Single CAC Outdoor Unit 3 Dimensions 8 Compact Inverter AUUW36GC0 UU36WC U40 Chassis code U4 ...
Page 130: ...10 Single CAC Outdoor Unit Compact Inverter 5 Wiring Diagrams Models AUUW18GC0 UU18WC UL0 ...
Page 132: ...Single CAC Outdoor Unit 5 Wiring Diagrams 12 Compact Inverter Models AUUW36GC0 UU36WC U40 ...