18
THE INDOOR UNIT INSTALLATION
ENGLISH
1
Compare the flared work with the figure
by.
2
If a flared section is defective, cut it off
and do flaring work again.
1
Align the center of the pipes and suffi-
ciently tighten the flare nut by hand
2
Tighten the flare nut with a wrench
3
When needed to extend the drain hose of
indoor unit, assembly the drain pipe as
shown on the drawing
1
Overlap the connection pipe insulation ma-
terial and the indoor unit pipe insulation
material. Bind them together with vinyl
tape so that there may be no gap.
Check
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Connecting the installation pipe
and drain hose to the indoor unit.
Indoor unit tubing
Flare nut Pipes
Outside diameter
Torque
mm
inch
kgf.m
Ø6.35
1/4
1.8~2.5
Ø9.52
3/8
3.4~4.2
Ø12.7
1/2
5.5~6.5
Ø15.88
5/8
6.3~8.2
Ø19.05
3/4
9.9~12.1
Wrench
Indoor unit tubing
Open-end wrench
(fixed)
Connection
pipe
Flare nut
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
Wrap the insulation material
around the connecting portion.
Insulation material
CAUTION
• When mechanical connectors are
reused indoors, sealing parts shall be
renewed.
• When flared joints are reused indoors,
the flare part shall be re-fabricated.
!