10
ENGLISH
INSTALLATION PLACES
INSTALLATION PLACES
Install the air conditioner in the location that satisfies the following conditions.
- The place shall easily bear a load exceeding four times the indoor unit’s weight.
- The place shall be able to inspect the unit as the figure.
- The place where the unit shall be leveled.
- The place shall allow easy water drainage.
(Suitable dimension “H” is necessary to get a slope to drain as figure.)
- The place shall easily connect with the outdoor unit.
- The place where the unit is not affected by an electrical noise.
- The place where air circulation in the room will be good .
- There should not be any heat source or steam near the unit.
Ceiling Concealed Duct – Low Static
Ceiling Concealed Duct – Mid Static
Inspection hole (600 x 600)
Control box
H=20 or more
• Suitable dimension "H" is necessary to get a slope
to drain as shown in the figure
600
600
Air outlet
Air outlet
Top view
(unit: mm)
Front view
Inspection hole
(600 x 600)
Control box
1000
H
600
600
Front
Top view
(unit: mm)
(unit: mm)
Side view
CAUTION
• In case that the unit is installed near the sea, the installation parts may be corroded by salt,
The installation parts (and the unit) should be taken appropriate anti-corrosion measures.
!
[Inspection Hole Standard]
Number of
Inspection hole
Distance between
False ceiling & Actual ceiling
Remarks
1
More than 100cm
Sufficient space in the ceiling for servicing.
2
20cm to 100cm
Insufficient space. Difficult for servicing
Hole size should be
more than the size
of IDU.
Less than 20cm
Minimum height for motor replacement.
1,MFL67939930,영영 2018. 3. 16. 영영 2:25 Page 10
Summary of Contents for UM30R.N10
Page 41: ......