Water components
484
13
9
10
12
6
8
14
15
4
3
2
16
16
1
5
484
123
116
84.5
63.
4
36.
9
46.
4
76 41
847.
8
7
11
289.6
No
Name
Remark
1
Leaving Water Pipe
Male PT 1 inch
2
Entering Water Pipe
Male PT 1 inch
3
Refrigerant Pipe
Ø9.52mm
4
Refrigerant Pipe
Ø15.88mm
5
Water Pump
Max Head 9.5 / 7 / 6 m
6
Safety Valve
Open at water pressure 3 bar
7
Control Box
PCB and terminal blocks
8
Thermal switch
Cut-off power input to electric heater at 90 °C (manual return at 55 °C)
9
Flow Switch
Minimum operation range at 15 LPM.
10
Plate Heat Exchanger
Heat exchange between refrigerant and water
11
Pressure Gage
Indicates circulating water pressure
12
Expansion Tank
Absorbing Volume change of heated water
13
Air Vent
Air purging when Charging water
14
Electric Heater
Please refer to the below Page ‘Model name and related information’
15
Strainer
Filtering and stacking particles inside circulating water
16
Shut-off valve
To drain or to block water when pipe connecting
II. System Design
Applications
1. System 1
2. System 2
3. System 3
4. System 4
5. System 5
6. System 6
7. System 7
8. System 8
9. System 9
10. System 10
11. System 11
12. System 12
Installation check list