59
ACCESSORIES INSTALLATION
ENGLISH
How to wire thermostat
Follow below procedures Step 1 ~ Step 4.
Step 1. Uncover front cover of the unit and open the control box.
Step 2. Identify the power specification of the thermostat. If it is 220-240 V~, go to Step 3.
Step 3. If it is Heating only thermostat, go to step 4.
Step 4. Find terminal block and connect wire as below.
Thermostat
(L)
(N)
(H)
THERMOSTAT
(Default : 230 V AC)
L
N
L1
L2
7
8
9
10
Mechanical type thermostat.
Do not connect wire (N) as mechanical type thermostat
does not require electric power supply.
(L) : Live signal from PCB to thermostat
(N) : Neutral signal from PCB to thermostat
(H) : Heating signal from thermostat to PCB
Final check
• DIP switch setting :
Set DIP switch No. 8 to ‘ON’. Otherwise, the unit can not recognize the thermostat.
• Remote Controller :
- ‘Thermostat’ text is displayed on the remote controller.
- Button input is prohibited.
WARNING
!
Do not connect external electric loads.
Wire (L) and (N) should be used only for operation electric
type thermostat.
Never connect external electric loads such as valves, fan
coil units, etc. If connected, Main PCB (Heater) can be
seriously damaged.
CAUTION
!