122
COMMISSIONING
ENGLISH
Error No.
Error Type
Main Reasons
Outdoor unit related error (CH)
4
6
1
Inverter compressor suction pipe
temperature sensor defect
Inverter compressor suction temperature
sensor disconnection or short circuit
4
9
1
Defective IPM Temperature
Sensor
Disconnection or short circuit on IPM
temperature sensor of the outdoor unit
5
2
1
Communication error : inverter PCB ’
Main PCB
Failing to receive inverter signal at main PCB
of Outdoor Unit
5
3
1
Communication error(indoor unit ’
outdoor unit main PCB)
Outdoor unit does not receive signal from
indoor unit
5
7
1
Communication error : inverter PCB ’
Main PCB
Restriction of Outdoor Unit (Inverter PCB)
6
0
1
Inverter PCB EEPROM error
Inverter PCB EEPROM error
6
2
1
Excessive rise of inverter heatsink
temperature
Inverter PCB heat generation, causing the rise
of heatsink temperature
6
7
1
Outdoor Unit Fan Lock
Restriction of Outdoor Unit Fan
7
3
1
Overcurrent (Peak) detected at
inverter input
Error by overcurrent detection at inverter input
8
6
1
Outdoor Unit Main PCB EEPROM
Error
Communication Fail Between Outdoor Unit
Main MICOM and EEPROM or omitting
EEPROM
8
8
1
PFC PCB EEPROM Error
Communication Fail Between Outdoor Unit
PFC MICOM and EEPROM or omitting
EEPROM
1 1 3 1
Outdoor Unit Liquid pipe
Temperature Sensor Error
Liquid pipe temperature sensor of outdoor unit
is open or short
1 1 5 1
Outdoor Unit Subcooling Outlet
Temperature Sensor Error
Outdoor Unit Subcooling Outlet Temperature
Sensor open or short
1 5 1 1
Failure of operation mode
conversion at Outdoor Unit
Pressure unbalance between outdoor units