System Set-Up
• Function Code 2A
: Miscellaneous setting
- Value #1 of Function Code 2A : determine electric heater and sanitary tank heater on and off.
- Value #2 of Function Code 2A : not used.
- Example : If Value #1 is set as ‘0’, then electric heater and sanitary tank heater are on and off ac-
cording to control logic. If Value #1 is set as ‘1’, then electric heater is never turned on and only
water heater is on and off according to control logic.
• Function Code 2B
: Sanitary water heating timers
Determine following time duration : operation time of sanitary tank heating, stop time of sanitary
tank heating, and delay time of sanitary tank heater operating.
- Value #1 of Function Code 2B : This time duration defines how long time sanitary tank heating can
be continued.
- Value #2 of Function Code 2B : This time duration defines how long time sanitary tank heating can
be stopped. It is also regarded as time gap between sanitary tank heating cycle.
- Value #3 of Function Code 2B : This time duration defines how long time sanitary tank heater will
not be turned on in sanitary water heating operation.
- Example of timing chart :
Sanitary tank
heating is enabled
Sanitary tank heater
is enabled
Sanitary tank
heating is required
Sanitary tank
heating operation
Sanitary tank
heater operation
1=active / 0=not active
Time
2B.03
2B.03
2B.01
2B.01
2B.02
2B.02
2B.02
1
0
1
0
1
0
1
0
1
0
❈
Installation Manual
91
ENGLISH