Evacuation
(All amount of refrigerant leaked)
ï Procedure
(1) Connect the vacuum pump to the center hose
of charge set center hose
(2) Evacuation for approximately one hour.
ñ Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).
(3) Close the valve (Lo side) on the charge set,
turn off the vacuum pump, and confirm that
the gauge needle does not move (approxima-
tely 5 minutes after turning off the vacuum
pump).
(4) Disconnect the charge hose from the vacuum
pump.
ñ Vacuum pump oil.
If the vacuum pump oil becomes dirty or
depleted, replenish as needed.
Lo
Open
Open
Vacuum pump
3-Way
valve
Outdoor unit
Liquid side
Indoor unit
Gas side
3-Way
valve
CLOSE
OPEN
Use vacuum pump equipped with check value
applied to be prevented from flowing backward.
-34-
Summary of Contents for S4-S5-SE Chassis
Page 1: ...MODELS S4 S5 SE Chassis ...
Page 2: ...3 5 6 7 12 12 13 24 25 28 34 2 ...
Page 3: ...IN DOOR Lights up during indoor unit operation Optional 3 ...
Page 4: ... Optional 4 ...
Page 6: ... 6 09K 12K 18K 24K ...
Page 11: ... 11 ...
Page 12: ... 12 ...
Page 14: ... 14 More than 10cm More than 5cm More than 2 3m More than 5cm ...
Page 17: ... 17 ...
Page 19: ... 19 Piping for passage through piping hole Tubing holder ...
Page 22: ... 22 ...
Page 23: ... 23 Circuit Breaker A 15 Grade 9k 12k 20 18k 30 24k ...
Page 24: ... 24 Pull the right and the left side ...
Page 25: ... 25 Pull the right and the left side ...
Page 26: ... 26 Discharge temperature Discharge air Intake temperature ...
Page 27: ... 27 ...
Page 28: ...Earth Conductor 28 ...
Page 29: ...Screw 29 ...
Page 30: ... 30 Motor cover Bearing Cross flow fan ...
Page 31: ... 31 ...
Page 37: ... 37 ...
Page 38: ... 38 ...
Page 39: ... 39 ...
Page 40: ... 40 ...
Page 41: ... 41 ...
Page 42: ... 42 ...
Page 43: ... 43 ...
Page 44: ...P No 5400575301 ...