SETTING AND USING METHOD
ENGLISH
17
Operation Status
Error Status
Power
AC or DC
Power
AC or DC
Operating Status
LG does not supply this
section (Field supply)
Status output Relay can
endure 250VAC, 1A.
①
Error Display
: This Module display error signal as below
- Level 1,2 error of Outdoor Unit
- Indoor Unit error _ All IDU Error.
②
Operating Display
: This function is depend on 4th Dip SW setting of ‘SW101’.
- L4 is ON : Display Indoor Unit operating status (Include FAN mode only)
- L4 is OFF : Display Outdoor Unit operating status (Compressor operating condition)
Position
Function
ON
L1 2
3 4
ON : Activate Digital Output according to Indoor Unit status
OFF : Activate Digital Output according to Outdoor Unit status
• L4 : Set Operating status output
CAUTION
When using high voltage over than AC24V, make sure to use H07RNF wire.
!