79
INSTALLER SETTING
ENGLISH
NOTE
• Heater on temperature
Using Half capacity of electric heater : when DIP Switch No. 6 and 7 is set as ‘OFF-ON’ :
- Example : If Heater on temperature is set as ‘-1’ and DIP switch No 6. and 7 is set as
‘OFF-ON’, then half capacity of electric heater will start operation when outdoor
air temperature is below -1 °C and current leaving water temperature or room
air temperature is much belower than target leaving water temperature or
target room air temperature.
Using Full capacity of electric heater : when DIP Switch No. 6 and 7 is set as ‘OFF-OFF’ :
- Example : If Heater on temperature is set as '-1' and DIP switch No 6. and 7 is set as
'OFF-OFF', then full capacity of electric heater will start operation when outdoor
air temperature is below -1 °C and current leaving water temperature or room
air temperature is much belower than target leaving water temperature or
target room air temperature.
78
INSTALLER SETTING
Heater on temperature
Depending on local climatic conditions, it is necessary to change the temperature condition in
which electric heater turns on / off.
• In the installer setting list, Heater on temperature category, and press [OK] button to move to
the detail screen.
OK
NOTE
The setting range differs depending on the connected product.